background image

SS-400-012  3 I56-3749-006

Mounting

Slot

Mounting

Slot

ASP17-00

FIGURE 2. MOUNTING SLOTS FOR MOUNTING STUDS

Connecting the Air Sampling Pipe

The input and output ports are designed to accept standard one inch pipe (25 
mm) OD. The input ports are tapered to provide fast, easy, push-fit connection 
of the sampling pipe to the unit. Perform the following procedure to connect 
the air sampling pipe to the unit.

1.   Square off and de-burr the end of the sampling air pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.   Remove the input plug from the input port being used (either the top or 

bottom of the unit).

3.   Insert the sampling air pipe into the input port, ensuring a snug fit.  

DO NOT glue these pipes.

Mounting the Detector to the Bracket

Once the mounting plate is attached, the unit is ready to be mounted onto the 
plate. Perform the following procedure to mount the unit.

1.   Before installing the unit onto the bracket, remove the appropriate con-

duit cap from the top or bottom-left side of the unit to match the orienta-
tion of the wiring. See Figure 14 for location of the wiring access plugs. 

2.   Line up the unit with the four mounting clips and the mounting studs on 

the left side.

3.   Push the unit down onto the mounting clips and secure it with the sup-

plied washer and nut on at least one of the two mounting studs protrud-
ing through the mounting slots shown in Figure 2.

Exhaust Pipe

The device should always be exhausted into the space that it is monitoring. 
There are some circumstances when it may be necessary to connect a pipe to 
the exhaust port to divert the exhaust away from the location of the unit. The 
output ports are tapered the same as the input ports, to provide fast, easy, 
push-fit connection of an exhaust pipe to the unit. Perform the following pro-
cedure to connect the exhaust pipe to the unit.

1.   Square off and de-burr the end of the exhaust pipe. Ensure that the pipe 

is free from any particles that might interfere with the pipe connection.

2.   Remove the exhaust plug from the output port being used (either the top 

or bottom of the unit).

3.   Insert the exhaust pipe into the output port, ensuring a snug fit. DO NOT 

glue these pipes.

WIRING

WARNING

Before working on the FAAST system, notify all required authorities that the 
system will be temporarily out of service. Make sure all power is removed 
from the system before opening the unit. All wiring must be in accordance 
with local codes.

Power Cables

Use the power ratings of the unit to determine the required wire sizes for each 
connection. Use the power ratings of the connected products to determine 
proper wire size.

Conduit Usage

If electrical conduit is used for system wiring, terminate the conduits at the cable 
entry ports on the top or bottom of the unit, using the appropriate conduit con-
nectors.

1.   Run all wiring, both power and alarm, through the conduit and into the 

left side of the unit enclosure, as shown in Figure 3.

2.   Attach the appropriate wires to the supplied Euro connector. Follow ap-

propriate local codes and electrical standards for all cabling.

3.   Plug the appropriate connector into the mating connector on the unit.

Power and Alarm

Connections

ASP16-00

FIGURE 3.  POWER AND ALARM CONNECTION CONNECTOR BLOCK

Summary of Contents for 8100A FAAST

Page 1: ...s 5 26 kg includes packing material 8100A FAAST Fire Alarm Aspiration Sensing Technology 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 1 800 SENSOR2 Fax 905 812 0771 www systemsensor ca INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTALLATION 2 PHYSICAL UNIT INSTALLATION 2 S...

Page 2: ...fe Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling software Acclimate mode operation for auto adjustment of sensitivity Remote monitoring via Ethernet IP Remote reset dry contact input Multi lingual support E mail notification of alarm fault or isolate conditions ITEMS INCLUDED WI...

Page 3: ...me circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to provide fast easy push fit connection of an exhaust pipe to the unit Perform the following pro cedure to connect the exhaust pipe to the unit 1 Square off and de burr the end of the exhaust pipe Ensure t...

Page 4: ...ns to flow out of the exhaust port 6 Connect a computer with the PipeIQ software installed to the unit using the Ethernet connection on the bottom of the unit 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 When the configuration is complete remove the Ethernet connection to the unit USER INTERFACE The user interface shown in Figure 4 provides t...

Page 5: ...l operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balanced level the two green segments are centered on the graph at levels 5 and 6 see Figure 7 As air flow rises and falls the green segments move right and left accordingly The segment on the far left represents a decrease in airflow of 20 Conversely movement to the segm...

Page 6: ...he user interface when the button is enabled refer to pass code access section for activation details Test mode simulates a fire con dition activating all ten segments in the Particulate Level display and each segment in the Alarm display Each corresponding alarm relay is also acti vated after any programmed delay associated with that relay Activation of the RESET button removes the device from TE...

Page 7: ...ESET button The first seg ment on the airflow display blinks green indicating the device is ready to accept the first digit To enter the passcode use the ISOLATE and TEST buttons shown in Figure 9 The ISOLATE button is used to increment the current digit As the current digit is incremented the segments of the Particulate Bar Graph illuminate accord ingly To complete entry of the digit press the TE...

Page 8: ...etector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking data may be accessed via the network through the PipeIQ software or the Web server in terface Configuration and management of the log are done using the PipeIQ software Data Trend Log The FAAST system tracks trend data for each 24 hour time period up to 1 year The device r...

Page 9: ...UL Tested and approved aerosol smoke products are listed in Table 6 MAINTENANCE The only periodic maintenance required is to replace the filter assembly when the filter light is illuminated Perform the following procedure to replace the filter assembly 1 Remove power from the system 2 Open the door on the right side of the device that covers the LED system indicators 3 Remove the plastic name card...

Page 10: ...ess Contact information Date Wiring Checked Date Yes No Detector Settings Checked Date Yes No Test Relays Date Yes No REQUIRED DOCUMENTS Copy of Commissioning Form Yes No FAAST system Bill of Material Yes No Commissioning Form for each system Yes No Smoke Test results optional Yes No Locally required forms Yes No Customer s Signature Date Commissioning Agent Signature Date FAAST System Validation ...

Page 11: ...y Yes No Is the pipe network installed and labeled properly Yes No Describe any Variations Sensitivity Obscuration ft Detector Address Detector Address FAAST System Validation Form CONT GLOSSARY KEY TERMS Configure To set up a program or computer system for a particular application FAAST Fire Alarm Aspirating Sensing Technology High sensitivity aspirating smoke detection system IP Address An Inter...

Page 12: ...ation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and ser vice during the three year period commencing with the date of manufacture After phon ing System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid...

Reviews: