Software
30
sysmik.de
Manual SCA-340 / SCA-340-L
The page
Overview
shows host ID and version information of several software
components.
Page
Settings
allows to configure several settings:
Network
to configure IP addresses
Webserver
to configure the port at which the restricted webserver (without
device settings) is accessible
Date/Time
to configure current time and time zone
IO Server
to configure the IO server (port number, remote access)
Run
to activate/deactivate Niagara and Sedona
Switch
to configure the Ethernet switch (Ethernet port assignment, RSTP,
ring monitoring, broadcast storm protection)
On the page
Terminals
, the data points of the connected IO terminals can be
observed and manually overridden (see 4.2.3).
The webserver hosts further web pages, which are alternatively also available via
Ethernet:
DALI configurator to assign addresses to DALI ballasts (connected via
DALI terminals) and configure them
User defined visualization pages, which are created using Sedona
programming [4].
4.1.3
File Access via FTP
The Scalibur has an SFTP server to access the file system. This can be used to
load software updates from the PC to the Scalibur. The SFTP server can only be
activated and deactivated from the SCA System Shell (see chapter 4.1.1). A
password for the user “sftpuser” can be defined.
In parallel to SFTP an SSH server can be activated. It can be used for command
line based diagnosis of the controller by the manufacturer only.
4.2
Commissioning Scalibur
Scalibur comes with a default configuration and settings like IP addresses, time,
time zone, and others have to be specifically configured.
The following Scalibur functions are active:
The SCA System Shell expects input.
The IO server detects the connected IO terminals and opens its interface
for commissioning website, Sedona, and Niagara.
The commissioning webserver hosts the commissioning website.
The Niagara daemon is ready for a Platform connection with Workbench
(user sysmik / password intesa). Though there is no station running – these
can be loaded later during the Niagara commissioning.
Changing IP addresses or time zone becomes effective only after reboot.