Wiring and Signal
–
22
Pn-74C
Disable Encoder Ext.(2) Thermal
Protection
0~1
0
Pn-74E
Disable 2nd Int. Thermal Protection
0~1
0
Pn-74F
Disable 2nd Ext.(1) Thermal Protection
0~1
0
Pn-750
Disable 2nd Ext.(2) Thermal Protection
0~1
0
Above is the table of parameters relevant to the KTY84 thermal protection function. Set Pn-740 as 1 to enable the
function, then the system will trigger the overheat alarm AL-200 if the measured temperature exceeds the level set
in Pn-741.
To enable thermal protection for Syntec encoders, simply set the thermal protection level to a value within the
range 0~145
℃
. If this level is already factory-set, it cannot be modified.
There are two ways to disable the thermal protection function, as follows:
For drives before V2.1.8, set the thermal protection level to 0.
For V2.1.8 and onward, use the parameter "Disable Encoder Int. Thermal Protection".
Example: Set Pn-742 "Encoder Int. KTY84 Protection Lv." as 140
℃
. To disable the protection, set Pn-74A "Disable
Encoder Int. Thermal Protection" as 1.
If the temperature exceeds the protection level, a corresponding overheat alarm will be triggered as follows:
Alarm
Alarm Name
Alarm 220
Motor Over Temperature
Alarm 320
Encoder Internal Over Temperature
Alarm 321
Encoder External(1) KTY84 Over Temperature
Alarm 322
Encoder External(2) KTY84 Over Temperature
Alarm 324
2nd Encoder Internal Over Temperature
Alarm 325
2nd Encoder External(1) KTY84 Over Temperature
Alarm 326
2nd Encoder External(2) KTY84 Over Temperature
For diagnosis and troubleshooting of overheat alarms, refer to the table below: