background image

 

10 - 

 

6/07 A1

RD1- 

To protect the pump from rapid cycling, RD1 = 60 

RD2- 

Since the motor is small and submerged in water, the motor will generally cool down 
quickly. RD2=5 

RD3- 

The well history shows that it will fully recover in 2 hours. RD3 = 120 

#RU- 

In this application, we know that the well will eventually recharge itself, #RU = A 
(Automatic). 

#RF- 

This well is known for sand to jam the impeller; therefore, “oc” should be included so 
that the pump will attempt to automatically restart after an overload condition. History 
shows that 2 or 3 starts and stops usually clears the sand from the impeller. #RF= oc2 
or oc3. 

UCTD- 

This well may become air locked on startup, but will usually re-prime itself in 5 seconds 
or less. UCTD = 10 

GF- 

Because this type of fault indicates the impending failure of the motor and it may take 
several days to get a new pump and schedule for a driller to remove and replace the 
pump, GF setting of 10% of full load amperage will give the well owner enough time to 
prepare for pump replacement. GF = 15.9A x 0.10 = 1.59 

 
 

SYSTEM DISPLAY 

 

The output display can show one of the following parameters when the MODE SELECT switch is in 
the RUN position: average voltage or current, each line current, or each individual line-line voltage. 
The display is also used for programming the operating parameters of the device. The display also 
identifies what caused the unit to de-energize its relay or what is keeping the unit from energizing its 
relay. The last fault (not the current fault) can be displayed by pressing and holding the 
RESET/PROGRAM button while the MODE SELECT switch is in the RUN position. When the unit 
trips off or is holding the motor off, the current fault condition will be shown in the display without 
pressing the button. Table 4 below lists the fault codes the unit could display. 

 

Displayed 

Message 

Meaning 

oc Tripped 

on 

overcurrent 

SP 

Tripped on current single phasing or unit won’t start because the voltage is 
single phased 

ub 

Tripped on current unbalance or unit won’t start because the voltage is 
unbalanced 

uc Tripped 

on 

undercurrent 

CF 

Tripped on contactor failure 

GrF 

Tripped on ground fault 

HI 

A high voltage condition exists 

Lo 

A low voltage condition exists 

rP 

Incoming phases have been reversed, the motor may run backwards if 
started 

oFF 

A stop command was issued from a remote source 

 

Table 4: Fault Codes and Their Meaning 

 
 

On power up, the 777-P will show the current software revision. For example if the software  
revision is 2904, the 777-P will show 029 followed by 004. This can be used to determine the  
model number of 777-P. 

 

Summary of Contents for MotorSaver Plus 777-575-P

Page 1: ...ps onto the rail 3 A For amperages from 25 90 amps insert the motor conductors through the holes marked A B and C Make certain the conductor through each hole corresponds to the right motor conductor...

Page 2: ...0 3 3 32 6 3 3 12 25 10 50 3 0 5 49 2 2 25 90 20 100 0 10 98 1 1 80 110 80 140 0 40 140 5 100 100 5 110 160 120 210 0 60 210 5 150 150 5 160 220 160 280 0 80 280 5 200 200 5 220 320 240 420 0 120 420...

Page 3: ...Figure 2 Typical Wiring Diagram Using External CTs Figure 3 Looping Example Showing Three Conductors MULT 3 from Table 1 3 6 07 A1 No other necessary connections are shown...

Page 4: ...7 210 208 3 1 7 and 208 3 203 5 3 The maximum deviation from the average is 5 3 thus voltage unbalance 5 3 208 3 x 100 2 5 MULT MULT multiplier setting is found on Table 1 The MULT setting is determi...

Page 5: ...hase or RP reverse phase condition exists when power is applied to the device the output relay will energize the NO will close and the NC will open as soon as RD1 expires Typically this is set to 20 3...

Page 6: ...only used when communicating with an RM 2000 RM 1000 COM DN CIO DN a PLC or a PC The address can be 1 99 A01 A99 RF RF is the number of restarts the 777 P will attempt after current unbalance or curre...

Page 7: ...played will be the number corresponding to where the DISPLAY PROGRAM knob is pointed It will do this for the amount of time programmed into RD1 After this time has expired the relay will energize NO c...

Page 8: ...will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads J Prefix Programming any of the trip classes with the J prefix will enable jam prote...

Page 9: ...RD3 does not have any function RF Because an overload overcurrent fault signals a serious problem in this application e g worn bearings oc should not be included in the RF setting so that a manual res...

Page 10: ...h line current or each individual line line voltage The display is also used for programming the operating parameters of the device The display also identifies what caused the unit to de energize its...

Page 11: ...tion signal conditioning for compatibility with Modbus RTU and RS 485 networks and provides terminals for terminating the shielded communications cable Up to 99 units can be installed on one RS 485 ne...

Page 12: ...rameter value The incoming voltage is not within the limits programmed in the VUB HV and LV settings Adjust the DISPLAY PROGRAM switch to read the incoming line voltage values Correct the incoming pow...

Page 13: ...rmer must be between 115 and 150 of the GF setting and pass through only one CT window 5 The values of V and R will be determined by the current required to generate a GF trip condition I Vrms R where...

Page 14: ...14 6 07 A1 GROUND FAULT TEST RESULTS Date Performed by Results Location A copy of this form should be retained by the building s electrical foreman...

Page 15: ...ge 0 5 of nominal voltage Current 1 100A direct Trip Times Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpoint 201 300 of Setpoint 301 400 of Setpoint 401 or Gre...

Page 16: ...0 10 98A MULT or 40 140 of CT Primary CUB Current Unbalance Threshold 2 25 or 999 disabled 02 30 J02 J30 TC Overcurrent Trip Class and Linear Overcurrent Trip Delay L00 L60 or oFF RD1 Rapid Cycle Tim...

Reviews: