background image

 

4 - 

 

6/07 A1

PROGRAMMABLE PARAMETERS 

 

The following settings MUST be programmed by the user in order to provide proper protection for 
the application. All parameters are actual values except for the VUB and CUB settings; these are 
programmed as percentages. The range each parameter can be programmed to is found on the 
electrical specifications table on pages 15 and 16. See pages 9 and 10 for programming examples.  

 
LV/HV 

- The recommended settings for LV (low voltage) and HV (high voltage) according to the 

NEMA MG1 standard are ±10% of the motors nameplate voltage. For other settings, the 
motor manufacturer should be contacted. 

 

Example:

 The motor nameplate voltage is 230 volts. 90% and 110% of 230 is 0.9 x 

230=207 volts for the LV setting and 230 x 1.1=253 volts for the HV setting. These 
parameters are based on the average voltage going to the motor. 

 

VUB 

-   VUB (voltage unbalance) is factory set to 6%. The NEMA MG1 standard says a motor 

should not be operated above a 1% voltage unbalance without derating

 

the motor. Most 

utility supplied power sources have a difficult time sustaining a 1% VUB. The motor 
manufacturer should be consulted for an exact VUB setting. Setting VUB to 999 will disable 
voltage unbalance protection but will not disable voltage SP protection. 
V

 

oltage unbalance is calculated as follows: 

%

 

Voltage Unbalance = [(Maximum deviation from the average)/Average] x 100% 

Example:  

Measured line-line voltages = 203, 210, and 212. The average = 

(203+210+212)/3 = 208.3. The maximum deviation from the average is the greatest 
difference between the average voltage (208.3) and any one voltage reading; 212-
208.3 = 3.7, 210-208.3 = 1.7 and 208.3-203 = 5.3. The maximum deviation from the 
average is 5.3, thus voltage unbalance = 5.3/208.3 x 100= 2.5%. 

 

MULT 

-  MULT (multiplier) setting is found on Table 1. The MULT setting is determined by the 

current the unit will be monitoring. This allows the unit to display the correct current. Set 
MULT first then set UC, OC and GF.  

 

OC

-  

OC (overcurrent) is typically set to the service factor amperage (SFA) of the motor or 100-
115% of motor full-load amps (FLA), which are determined by the motor manufacturer. If 
any one leg exceeds the OC setting, the 777-P will follow the TC settings to determine 
when to trip; in seconds or by following the trip class curve (see Figure 4). 

 
UC 

-  

UC (undercurrent) is typically set to 80% of the full-load amperage (FLA) of the motor. This 
is usually adequate for protection of loss of load for many pumps and motors, including 
submersibles. If the motor is not pulling near full load amperage then the UC may have to 
be set to something higher than 80% of FLA for adequate protection. UC can be set to 0 if 
UC protection is not desired. The 777-P examines average current to determine if an 
undercurrent trip condition exists. 

 

CUB 

-   CUB (current unbalance) is factory set to 7%. SymCom recommends contacting the motor 

manufacturer for a specific setting. Current unbalance is calculated the same way voltage 
unbalance is calculated (see formula above). Current unbalance protection can be disabled 
by programming CUB to 999. This will disable current unbalance protection and current 
single phasing protection. 

 

TC 

-  

The TC (trip class) setting determines how quickly the 777-P will trip when an overload 
(overcurrent) condition is detected. TC is a dual-function setting—both a thermal trip class 
(NEMA standard) and a linear trip delay (in seconds) can be set to establish when the 777-

Summary of Contents for MotorSaver Plus 777-575-P

Page 1: ...ps onto the rail 3 A For amperages from 25 90 amps insert the motor conductors through the holes marked A B and C Make certain the conductor through each hole corresponds to the right motor conductor...

Page 2: ...0 3 3 32 6 3 3 12 25 10 50 3 0 5 49 2 2 25 90 20 100 0 10 98 1 1 80 110 80 140 0 40 140 5 100 100 5 110 160 120 210 0 60 210 5 150 150 5 160 220 160 280 0 80 280 5 200 200 5 220 320 240 420 0 120 420...

Page 3: ...Figure 2 Typical Wiring Diagram Using External CTs Figure 3 Looping Example Showing Three Conductors MULT 3 from Table 1 3 6 07 A1 No other necessary connections are shown...

Page 4: ...7 210 208 3 1 7 and 208 3 203 5 3 The maximum deviation from the average is 5 3 thus voltage unbalance 5 3 208 3 x 100 2 5 MULT MULT multiplier setting is found on Table 1 The MULT setting is determi...

Page 5: ...hase or RP reverse phase condition exists when power is applied to the device the output relay will energize the NO will close and the NC will open as soon as RD1 expires Typically this is set to 20 3...

Page 6: ...only used when communicating with an RM 2000 RM 1000 COM DN CIO DN a PLC or a PC The address can be 1 99 A01 A99 RF RF is the number of restarts the 777 P will attempt after current unbalance or curre...

Page 7: ...played will be the number corresponding to where the DISPLAY PROGRAM knob is pointed It will do this for the amount of time programmed into RD1 After this time has expired the relay will energize NO c...

Page 8: ...will be protected by this setting 30 Slow Trip Motors with long acceleration times 10 seconds or high inertia loads J Prefix Programming any of the trip classes with the J prefix will enable jam prote...

Page 9: ...RD3 does not have any function RF Because an overload overcurrent fault signals a serious problem in this application e g worn bearings oc should not be included in the RF setting so that a manual res...

Page 10: ...h line current or each individual line line voltage The display is also used for programming the operating parameters of the device The display also identifies what caused the unit to de energize its...

Page 11: ...tion signal conditioning for compatibility with Modbus RTU and RS 485 networks and provides terminals for terminating the shielded communications cable Up to 99 units can be installed on one RS 485 ne...

Page 12: ...rameter value The incoming voltage is not within the limits programmed in the VUB HV and LV settings Adjust the DISPLAY PROGRAM switch to read the incoming line voltage values Correct the incoming pow...

Page 13: ...rmer must be between 115 and 150 of the GF setting and pass through only one CT window 5 The values of V and R will be determined by the current required to generate a GF trip condition I Vrms R where...

Page 14: ...14 6 07 A1 GROUND FAULT TEST RESULTS Date Performed by Results Location A copy of this form should be retained by the building s electrical foreman...

Page 15: ...ge 0 5 of nominal voltage Current 1 100A direct Trip Times Those not shown have user selectable trip times Ground Fault Trip Time 101 200 of Setpoint 201 300 of Setpoint 301 400 of Setpoint 401 or Gre...

Page 16: ...0 10 98A MULT or 40 140 of CT Primary CUB Current Unbalance Threshold 2 25 or 999 disabled 02 30 J02 J30 TC Overcurrent Trip Class and Linear Overcurrent Trip Delay L00 L60 or oFF RD1 Rapid Cycle Tim...

Reviews: