Operating Instructions
14
Following the menu parameters in detail:
7. Menu Structure of SolidFlow
1. Measuring Range
1.1 Tag No
Adjust Material (10 Digits)
1.2 Unit
Adjust Text e. g. kg
1.3 Time Scale
Choose: h / min / s
1.4 Decimal Point
Choose Position of Dec. Point
1.5 Beginning of Measuring Range
Range 0 ... 999
1.6 End of Measuring Range
Range 0 ... 999
1.7 Filter Value
Range 0.1 ... 999.9 s
2. Alarm
2.1 Type of Alarm
Choose: Min / Max
2.2 Value of Alarm
-10 to 110 % in phys. Units
2.3 Alarm Dead Time
Range 0.1 ... 99.9 s
2.4 Alarm Hysteresis
0.1 ... 99.9 %
2.5 Operation Mode
Choose: Working- / Static
Current Principle
2.6 Alarm Sensor Malfunction
Choose: on / off
3. Analog Output
3.1 Beginning of Measuring Range
Range: 0 ... 22 mA (Standard: 4 mA)
3.2 End of Measuring Range
Range: 0 ... 22 mA (Standard: 20 mA)
3.3 MIN Point
Range: 0 ... 22 mA (Standard: 3 mA)
3.4 MAX Point
Range: 0 ... 22 mA (Standard: 20 mA)
3.5 Value of Alarm
Range: 0 ... 22 mA (Standard: 3 mA)
3.6 Filter Time
Range: 0.1 ... 99.9 s (Standard: 1 s)
3.7 Calibration: 4 mA
Adjust Current Output
(4 mA calibrated)
3.8 Calibration: 20 mA
Adjust Current Output
(20 mA calibrated)