5. Function

5.1 Xzone heating  

(wiring terminals 101-114)

IQlogic

+

module 1 is used for the extra heating control 

zone function (function selector switch 1 is set to Position 
A).

The function can be enabled in the hand-held micro termi-
nal of the GOLD unit or via a communication interface.

The module controls an electric air heater or an air heater 
for hot water.

Connect the 0-10 VDC control signal of electric air heater 
or valve actuator to the IQlogic

+

 module with an RJ 45 

connector.
Connect the conductors from the pump, if fitted, to Termi-
nals 101 and 102.
Connect the pump alarm, if required, to Terminals 103 
and 104.
Connect the freeze guard sensor of the air heater for 
water to the IQlogic

+

-module

 

with an RJ 45 connector.

Connect the conductors from the supply air temperature 
sensor (TBLZ-1-30) to wiring terminals 113 and 114.
See 6. Electrical connections on the next page.

5.2 Xzone cooling  

(wiring terminals 115-132)

IQlogic

+

module 2 is used for the extra cooling control zone 

function (function selector switch 2 is set to Position B). 
Always use this module for extract air control/room air 
control even if the room is not being cooled. However, 
there’s no need to enable the cooling function in the 
hand-held micro terminal of the GOLD unit.

The function can be enabled in the hand-held micro termi-
nal of the GOLD unit or via a communication interface.

The module controls a DX air cooler or an air cooler for 
chilled water.

Connect the 0-10 VDC control signal of valve actuator to 
the IQlogic

+

 module with an RJ 45 connector.

Connect the Cooling step 1/Pump 1 connectors (relay 
output) to Terminals 115 and 116.
Connect the Cooling step 2/Pump 2 connectors (relay 
output) to Terminals 117 and 118.
Connect the Cooling step 1/Pump 1 Alarm conductors to 
Terminals 119 and 120.
Connect the Cooling step 2/Pump 2 Alarm conductors to 
Terminals 121 and 122.
Connect the temperature sensor in the extract air duct 
(TBLZ-1-30), if required, to Terminals 131 and 132.
Connect room sensor, TBLZ-24-2 (1-4 sensors), if required, 
to the IQlogic

+

 module with RJ45 contact, see separate 

installation instructions.
See Section 6. Electric connections appear on the next 
page.