background image

GB.TBLE-B.050101

Specifications are subject to alteration without notice.

www.swegon.se     3

2 X 400V

Type 

Output 

Supply 

Current 

Fuse

TBLE-000-031-030-1 

3 kW 

2 X 400V + earth 

7.5 A 

10 A

TBLE-000-031-045-1 

4.5 kW 

2 X 400V + earth 

11.3 A 

16 A

3 X 400V

Type 

Output 

Supply 

Current 

Fuse

TBLE-000-031-075-1 

7.5 kW 

3 X 400V + N + earth 

10,8 A 

16 A

TBLE-000-040-060-1  6,0 kW 

3 X 400V + N + earth  8,7 A 

10 A

TBLE-000-040-120-1 

12,0 kW  3 X 400V + N + earth  17,3 A 

20 A

TBLE-080-040-080-1  8 kW 

3 X 400V + N + earth 

11.6 A 

16 A

TBLE-080-040-120-1 

12 kW 

3 X 400V + N + earth 

17.3 A 

20 A

TBLE-080-040-200-1  20 kW 

3 X 400V + N + earth 

28.9 A 

32 A

TBLE-120-060-120-1 

12 kW 

3 X 400V + N + earth  17,3 A 

20 A

TBLE-120-060-200-1 

20 kW 

3 X 400V + N + earth 

28.9 A 

32 A

TBLE-120-060-270-1 

27 kW 

3 X 400V + N + earth 

39.0 A 

50 A

TBLE-120-060-360-1 

36 kW 

3 X 400V + N + earth  52,0 A 

63 A

TBLE-120-060-475-1 

47,5 kW  3 X 400V + N + earth  68,6 A 

80 A

Electrical Connection

1. The electrical installation must be carried out by a quali-
fied electrician according to local regulations.
The electric air heater has been granted approval by 
SEMKO, NEMKO, DEMKO and the Finnish Electrical Equip-
ment Inspectorate.
2. Control 
The electric heater is equipped with a 5 m long control cable 
that has a quick connector for connection to the GOLD unit. 
An extension cable is available as an accessory.
3. Power supply
Connect the heater directly to the power supply (across 
a safety switch, if required) in accordance with the tables 
and illustrations below.

Brown   

= 24 V~(G)

White-brown 

= 24 V~(G0)

Orange   

= Control signal Y (0-10 V)

White-blue 

= Control signal M (0 V)

Blue  

 

= Overheating

White-orange  = Overheating

Green   

= Type of heater (resistance)

White-green 

= Type of heater

��

�� ��

��

� �

Brown

W

hi

te

-b

ro

w

n

W

hi

te

-green

Green

W

hi

te

-o

ra

ng

e

Blue

Control cable
(prewired)

Control unit in 
electric air heater

15

16

W

hi

te

-blue

Orange

��

�� ��

��

� �

Control cable
(prewired)

Control unit in 
electric air heater

3

4

10 K

Ω 

��

�� ��

��

� �

Control cable
(prewired)

Control unit in 
electric air heater

15

16

Applicable to electric air heaters up to 20 kW

Applicable to the 27 – 47.5 kW electric air heaters

Brown

W

hi

te

-b

ro

w

n

W

hi

te

-green

Green

W

hi

te

-o

ra

ng

e

Blue

W

hi

te

-blue

Orange

Br

own

W

hi

te

-b

ro

w

n

W

hi

te

-gr

een

Gr

een

W

hi

te

-o

ra

ng

e

Blue

W

hi

te

-blue

Orange

Summary of Contents for TBLE Series

Page 1: ...won t be uniform and this may cause the overhea ting protection to trip 5 The electric air heater must be insulated according to local ventilation ducting standards The heater must be insulated with incombustible insulation material The insulation must not conceal the cover since the rating plate must be visible and it must be possible to remove the cover 6 The in duct section with built in heatin...

Page 2: ... 000 031 matches GOLD sizes 11 12 TBLE 000 040 matches GOLD size 15 TBLE 080 040 matches GOLD sizes 21 22 TBLE 120 060 matches GOLD sizes 31 32 E 35 A H C B 35 TBLE A B C H E 080 040 400 1019 800 438 420 120 060 600 1419 1200 638 370 TBLE A 000 031 315 000 040 060 400 000 040 120 1 400 TBLE 000 040 120 2 ...

Page 3: ...to local regulations The electric air heater has been granted approval by SEMKO NEMKO DEMKO and the Finnish Electrical Equip ment Inspectorate 2 Control The electric heater is equipped with a 5 m long control cable that has a quick connector for connection to the GOLD unit An extension cable is available as an accessory 3 Power supply Connect the heater directly to the power supply across a safety...

Page 4: ...A 32 A TBLE 120 060 200 2 20 kW 3 X 230V earth 50 2 A 63 A TBLE 120 060 270 2 27 kW 3 X 230V earth 67 8 A 80 A TBLE 120 060 360 2 36 kW 3 X 230V earth 90 5 A 100 A TBLE 120 060 475 2 47 5 kW 3 X 230V earth 119 2 A 125 A Brown 24 V G White brown 24 V G0 Orange Control signal Y 0 10 V White blue Control signal M 0 V Blue Overheating White orange Overheating Green Type of heater resistance White gree...

Reviews: