CONNECT TO THE DUCTING

1. The heater should be connected to the ducting as fol-
lows:
a) TBLE 000-031 and 000-040 
The electric heater is designed for connection directly to 
spiral ducts. Secure the heater to the ducting by means of 
pop rivets.
b) TBLE 080-040 and 120-060 
The electric air heater can be fitted in the ducting or 
directly to the air handling unit. Secure the electric heater 
with a sealing strip and slip clamps with PG connection.
2. The airflow direction through the electric heater must 
be according to the arrow on the side of the heater, at the 
base of the junction box.
3. The electric heater can be installed in a horizontal or 
a vertical duct, with the junction box either upward or 
turned within 90° toward either side. Installation with the 
junction box facing downward is not permissible.
4. The electric air heater should be located at a distance  
to or from a duct bend, damper, filter or similar compo-
nent. This distance should be at least equivalent to 
a) double the duct diameter (TBLE 000-031 and   TBLE 
000-040).
 b) its cross-section measured diagonally, i.e. from   corner 
to corner in the in-duct section of the  

heater. (TBLE 

080-040 och 120-060).
Otherwise, there is a risk that the air stream through the 
heater won't be uniform and this may cause the overhea-
ting protection to trip.
5. The electric air heater must be insulated according to 
local ventilation ducting standards. The heater must be 
insulated with incombustible insulation material. The 
insulation must not conceal the cover, since the rating 
plate must be visible and it must be possible to remove the 
cover.
6. The in-duct section with built-in heating element must 
be accessible for replacement and inspection.
7. The distance from the metal casing of the electric air 
heater to wood or any other combustible material must 
not be less than 30 mm.

INSTALLATION –TBLE ELECTRIC AIR HEATER
GOLD Sizes 11-32

OPERATION

The TBLE electric air heater has a built-in thyristor that is 
controlled across a 0–10 Volt signal from the GOLD unit. 
The electric heater has two overheating protections wired 
in series. One resets itself automatically; the other must be 
manually reset. These protections are designed to prevent 
excessively high temperature if the airflow should become 
too low and are designed to prevent overheating in the 
event of some system malfunction.
The control signal and overheating protection can be 
wired to the GOLD unit across a cable with connector. 
If overheating protection trips, an alarm indication will be 
visible in the hand-held terminal of the GOLD unit. Find 
the cause of the fault and take remedial action. Press the 
reset button on the heater to reset the overheating pro-
tection and then press the reset button on the hand-held 
terminal.

Summary of Contents for TBLE Series

Page 1: ...won t be uniform and this may cause the overhea ting protection to trip 5 The electric air heater must be insulated according to local ventilation ducting standards The heater must be insulated with incombustible insulation material The insulation must not conceal the cover since the rating plate must be visible and it must be possible to remove the cover 6 The in duct section with built in heatin...

Page 2: ... 000 031 matches GOLD sizes 11 12 TBLE 000 040 matches GOLD size 15 TBLE 080 040 matches GOLD sizes 21 22 TBLE 120 060 matches GOLD sizes 31 32 E 35 A H C B 35 TBLE A B C H E 080 040 400 1019 800 438 420 120 060 600 1419 1200 638 370 TBLE A 000 031 315 000 040 060 400 000 040 120 1 400 TBLE 000 040 120 2 ...

Page 3: ...to local regulations The electric air heater has been granted approval by SEMKO NEMKO DEMKO and the Finnish Electrical Equip ment Inspectorate 2 Control The electric heater is equipped with a 5 m long control cable that has a quick connector for connection to the GOLD unit An extension cable is available as an accessory 3 Power supply Connect the heater directly to the power supply across a safety...

Page 4: ...A 32 A TBLE 120 060 200 2 20 kW 3 X 230V earth 50 2 A 63 A TBLE 120 060 270 2 27 kW 3 X 230V earth 67 8 A 80 A TBLE 120 060 360 2 36 kW 3 X 230V earth 90 5 A 100 A TBLE 120 060 475 2 47 5 kW 3 X 230V earth 119 2 A 125 A Brown 24 V G White brown 24 V G0 Orange Control signal Y 0 10 V White blue Control signal M 0 V Blue Overheating White orange Overheating Green Type of heater resistance White gree...

Reviews: