GB.TBLE-B.050101
Specifications are subject to alteration without notice.
4 www.swegon.se
3 X 230V
Type
Output
Supply
Current
Fuse
TBLE-000-031-030-2
3 kW
3 X 230V + earth
7.5 A
10 A
TBLE-000-031-045-2
4.5 kW
3 X 230V + earth
11.3 A
16 A
TBLE-000-031-075-2
7.5 kW
3 X 230V + earth
18.8 A
25 A
TBLE-000-040-060-2 6,0 kW
3 X 230V + earth
15 A
20 A
TBLE-000-040-120-2
12,0 kW 3 X 230V + earth
30,1 A
32 A
TBLE-080-040-080-2 8 kW
3 X 230V + earth
20.1 A
25 A
TBLE-080-040-120-2
12 kW
3 X 230V + earth
30,1 A
32 A
TBLE-080-040-200-2 20 kW
3 X 230V + earth
50.2 A
63 A
TBLE-120-060-120-2
12 kW
3 X 230V + earth
30,1 A
32 A
TBLE-120-060-200-2
20 kW
3 X 230V + earth
50.2 A
63 A
TBLE-120-060-270-2
27 kW
3 X 230V + earth
67.8 A
80 A
TBLE-120-060-360-2
36 kW
3 X 230V + earth
90,5 A
100 A
TBLE-120-060-475-2
47,5 kW 3 X 230V + earth
119,2 A 125 A
Brown
= 24 V~(G)
White-brown
= 24 V~(G0)
Orange
= Control signal Y (0-10 V)
White-blue
= Control signal M (0 V)
Blue
= Overheating
White-orange = Overheating
Green
= Type of heater (resistance)
White-green
= Type of heater
��
�� ��
��
� �
Control cable
(prewired)
Control unit in
electric air heater
15
16
Applicable to electric air heaters up to 20 kW
Brown
W
hi
te
-b
ro
w
n
W
hi
te
-green
Green
W
hi
te
-o
ra
ng
e
Blue
W
hi
te
-blue
Orange
��
�� ��
��
� �
Control cable
(prewired)
Control unit in
electric air heater
3
4
10 K
Ω
Applicable to the 27 – 47.5 kW electric air heaters
Brown
W
hi
te
-b
ro
w
n
W
hi
te
-green
Green
W
hi
te
-o
ra
ng
e
Blue
W
hi
te
-blue
Orange