Installation and Location

Install the smoke detector with the airflow direction arrow 
on its cover pointing in the direction of airflow through the 
ducting. The detector can be mounted on the side or top of 
the duct for vertical or horizontal air flow.
If the ambient temperature varies radically, for example 
outdoors or in cold attics, insulate the detector to protect it 
from the ambient air and prevent the formation of conden-
sation inside the detector housing.
To ensure satisfactory smoke detection, the smoke detector 
should be located at a distance, in the direction of airflow, 
that is equivalent to at least 3 x the hydraulic diameter of 
the duct 

upstream of the nearest source of disturbance 

in the ducting (see the examples of sources of disturbance 
below). If it is located 

downstream 

of the nearest source 

of disturbance, its distance from this source should be equi-
valent to at least 5 x the hydraulic diameter of the ducting.

Hydraulic diameter
  CIRCULAR DUCT 

 

 

  RECTANGULAR DUCT

AIR HANDLING UNIT

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 3xdh

MIN 5xdh

GX

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

MIN 5xdh

GX

M

IN 3xd

h

GX

GX

MIN 3xdh

GX

GX

MIN 3xdh

MIN 5xdh

d  = D

Ø D

h

d  = 

h

2xHxB

H+B

H

B

Examples of sources of disturbance

FAN

DAMPER

SILENCER

COIL

BEND

BRANCH

ADAPTER

EXTRACT AIR

SUPPLY AIR

AIR HANDLING UNIT

Summary of Contents for GOLD ELQZ-2-428-2

Page 1: ...tor transmits an alarm signal to the con trol unit Any accumulation of impurities in the smoke detector will make it more sensitive and gradually approach its alarm condition To avoid unnecessary alarms caused by fouling the detector is equipped with a service alarm green LED When lit this LED indicates that the detector ought to be cleaned Tecnical details Type of detector Ionising Power supply 2...

Page 2: ...conden sation inside the detector housing To ensure satisfactory smoke detection the smoke detector should be located at a distance in the direction of airflow that is equivalent to at least 3 x the hydraulic diameter of the duct upstream of the nearest source of disturbance in the ducting see the examples of sources of disturbance below If it is located downstream of the nearest source of disturba...

Page 3: ...m dia opening for smoke detector with mounting bracket see item 10 3 Do not cut this end Measure the ventilation duct Cut the tube to an appropriate length if needed The tube should penetrate 90 of the duct diameter into the duct Insert the end plug End plug Lock the tube in position by means of the stop screw Slip the seal onto the tube Insert the tube in the bottom of the detector housing 4 Moun...

Page 4: ...sable to consider relocating the detec tor 6 Insert the block 7 Electric wiring Connect the electric wiring as shown in the wiring diagram If only one smoke detector is connected to the system install the final resistor 2 2kΩ in this detector If several smoke detectors are to be connected to one control unit wire the final resistor 2 2kΩ in the last detector in the loop Fit only one resistor per loo...

Page 5: ...era tes correctly Expose the detec tor to smoke from a match or a suitable spray for testing smoke detectors Secure the cover by means of screws Fit the cover on the detector Do not drill any holes in the plastic cover for fitting identification plates or the like Doing so will cause leakage which will seriously impair detector performance ...

Page 6: ...n no smoke is present The smoke detector has been located where condensa tion can form inside it such as outdoors in a cold attic a kitchen or the like An alarm is indicated by the control unit only Measure the resistance of the loop 2 2kΩ from the control unit Check that the control unit is OK by wiring the final resistor to the smoke detector output on the control unit Use a voltmeter to check th...