GB.ELQZ428.050101
Specifications are subject to alteration without notice.
4 www.swegon.se
5
Flow indicator.
CAUTION!
The indicator doesn't rotate;
it rocks. If the
indicator
doesn't move at all, it is advisable
to consider relocating the detec-
tor.
6
Insert the block.
7
Electric wiring.
Connect the electric
wiring as shown in the
wiring diagram.
If only one smoke detector is connected to the system, install
the final resistor (2,2k
Ω
) in this detector.
If several smoke detectors are to be connected to one control
unit, wire the final resistor (2,2k
Ω
) in the last detector in the
loop. Fit only one resistor per loop!