Function
Factory preset value
adjusted value
temperature
8)
Temp. regulation function
X ERS 1
ERS 2
SA
EA
ERS 1
ERS 2
SA
EA
Differential SA/EA (°C)
3.0
Step
2
Breakpoint (°C)
22.0
X1
15.0
Y1
20.0
X2
20.0
Y2
18.0
X3
22.0
Y3
14.0
Setpoint (°C)
21.5
21.5
Min SA temp (°C)
15.0
temperature control
Xzone
8)
Temp control function
ERS 1
ERS 2 X
SA
EA
ERS 1
ERS 2
SA
EA
Difference TL/FL (°C)
3,0
Steps
2
Breakpoint (°C)
22,0
X1
15,0
Y1
20,0
X2
20,0
Y2
18,0
X3
22,0
Y3
14,0
Setpoint (°C)
21,5
21,5
Min. SA temp. (°C)
15,0
Max. SA temp. (°C)
28,0
Max SA temp (°C)
28.0
Outdoor temp. compensation
8)
X
Inactive
Active
Inactive
Active
Temperature
Winter comp. Y1 (°C)
3.0
End point, winter X1 (°C)
-20.0
Start point winter X2 (°C)
10.0
Start point, summer X3 (°C)
25.0
End point, summer X4 (°C)
40.0
Summer comp. Y2 (°C)
2.0
Summer night cooling
8)
X
Inactive
Active
Inactive
Active
EA temp. start (°C)
22.0
EA temp. stop (°C)
16.0
Outd. air temp. stop (°C)
10.0
SA Setpoint (°C)
10.0
Op. period start (hh:mm)
23:00
Op. period stop (hh:mm)
06:00
Intermittent nighttime heating
8)
X
Inactive
Active
Inactive
Active
SA/Room start (°C)
16.0
EA/Room stop (°C)
18.0
SA Night setpoint (°C)
28.0
SA flow (m²/s / Pa)
1)
EA flow (m²/s / Pa)
0.0
Control output
X
IQnomic
IQnomic
Damper output
=0