GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 35
Settings for cooling functions on this page and the next:
Value
Setting
Factory
range
settings
Operation mode
Inactive/active Inactive
Cooling regulation
CoolDX
Stepless 0-10 V Stepless 0-10 V
Stepless10-0 V
On/Off 1 step
On/Off 2 step
On/Off 3 step binary
COOL DXS
Periodic operation
Cooling relay 1
Inactive/pump/ Inactive
pump+valve/valve
Cooling relay 2
Inactive/pump/ Inactive
pump+valve/ valve
Exercise period 1 – 60 min.
3 min.
Interval
1 – 168 hrs.
24 hrs.
Regulation speed
between steps
0-600 sec
300 sec
Outdoor temperature limit
Step 1
0-25 °C
3 °C
Step 2
0-25 °C
5 °C
Step 3
0-25 °C
7 °C
Restart time
0-900 sec
480 sec
Cooling min air flow
Supply air
0-Max flow
–
Extract air
0-Max flow
–
Neutral zone
0-10 °C
2.0 °C
Cooling BOOST
Inactive
Inactive
Comfort
Economy
Sequence
economy
sequence
Start limit in
connection to
min supply air temp
2-10 °C
3 °C