18 INFORMATIVE MESSAGES
Informative messages are displayed in the hand-held micro
terminal. Informative messages are displayed only when
the user is viewing the Main menu.
Informative messages provide particulars about neces-
sary settings that have not been entered or unfavourable
operating scenarios, for instance.
Message no.
Message text
1
FILTER CALIBRATION NOT EXECUTED
The pressure across the filters was not calibrated after the first start. Recurrent at 24-hour intervals. The mes-
sage will not be received after the pressure across the filters has been calibrated.
2
H EXCH CALIBRATION NOT EXECUTED
The pressure across the heat exchanger was not calibrated after the function was activated for the first time.
Recurrent at 24-hour intervals. The message will not be received after the pressure across the heat exchanger
has been calibrated.
3
INCORRECT DIP SWITCH SETTINGS
DIL switches on the control circuit card are set in a forbidden combination.
4
SPARE
5
MODEM/E-MAIL ERROR
Error in communication to the modem or error when e-mail is being delivered. The message will be displayed
after ten attempts.
6
PREFILTER CAL NOT EXECUTED
The pressure across the prefilters was not calibrated after the first start. Recurrent at 24-hour intervals. The
message will not be received after the pressure across the prefilters has been calibrated.
7
ReCO
2
CALIBRAT NOT EXECUTED
ReCO was not calibrated after the function was activated for the first time. Recurrent at 24-hour intervals. The
message will not be received after the RecCO has been calibrated.
8
INCORRECT ReCO
2
SETTING
Pressure control, slave control or wrong type of air handling unit has been selected. Recurrent at 5-minute
intervals