GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 55
a
larm no.
alarm text
Function
Priority
Stop
Indication
LeD
Delay
Resetting
0=blocked 0=In operat.
0=Off
s=seconds
M=manual
A=A alarm
1=Stop
1=On
m=minutes
A=automatic
B=B alarm
105
HEAT. CIRCUIT PUMP I/O-7 TRIPPED
Controls of the heating circuit pump do not obtain
correct signal according to set function.
A***
1
1
30 s
M
106
COOLING WATER TEMP I/O-7 BELOW SET POINT
Temperature for cooling water control on I/O module
is continuously 7°C below its current set point.
B***
1
1
30 m
M
107
HEATING WATER TEMP I/O-7 BELOW SET POINT.
Temperature for heating water control on I/O module
is continuously 7°C below its current set point.
A***
1
1
30 m
M
108
COOLING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for cooling water control on I/O module
is continuously 7°C above its current set point.
0***
1
1
30 m
M
109
HEATING WATER TEMP I/O-7 ABOVE SET POINT
Temperature for heating water control on I/O module
is continuously 7°C above its current set point.
0***
1
1
30 m
M
110
COOLING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the cooling water temperature sensor
temp is not connected or is defective.
B
1
1
3 s
A
111
HEATING WATER TEMP SENSOR I/O-7 DEFECTIVE
Obtained if the heating water temperature sensor is
not connected or is defective.
A
1
1
3 s
A
112-
134
SPARE
135
SA FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A***
1
1
3 sec.
M
136
EA FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A***
1
1
3 sec.
M
137
SA-2 FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A***
1
1
3 sec.
M
138
EA-2 FAN MOTOR BLOCKED
Motor shaft does not rotate during start up.
A***
1
1
3 sec.
M
139
FLUCTUATION VOLTAGE BETWEEN THE PHASES, SA
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A***
1
1
3 sec.
M
140
FLUCTUATION VOLTAGE BETWEEN THE PHASES, EA
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A***
1
1
3 sec.
M
141
FLUCTUATION VOLTAGE BETWEEN THE PHASES,
SA-2
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A***
1
1
3 sec.
M
142
FLUCTUATION VOLTAGE BETWEEN THE PHASES,
EA-2
High voltage difference between the phases
(3-phase, 400 V), which causes rippling.
A***
1
1
3 sec.
M