21
Manufacturer reserves the right to alter specifications
Parameter
Parameter information
Factory setting
Adjustable value
0
Supply temperature
21°C
15-25°C
1
Supply airflow in normal mode
70%
35-99%
Adjust and measure airflow.
2
Extract airflow in normal mode
70%
35-99%
Adjust and measure airflow.
3
Supply airflow in away mode
30%
20-99%
Adjust and measure airflow.
4
Extract airflow in away mode
30%
20-99%
Adjust and measure airflow.
5
Supply airflow in forced ventilation mode
85%
35-99%
Adjust and measure airflow.
6
Extract airflow in forced ventilation mode
85%
35-99%
Adjust and measure airflow.
7
Winter adjustment increased airflow extract
10%
0-20%
Adjust and measure airflow.
8
Fire place reduced extract airflow
10%
0-20%
Adjust and measure airflow.
9
Cool function temperature decrease
5°C
0-10°C
Negativ adjustment in cool mode.
The unit has five different modes, of which
there, normal and forced to be adjusted:
• Away Mode (min. flow)
• Passive ventilation (unit calculates the pas-
sive flow)
• Normal ventilation (normal flow)
• Active ventilation (unit calculates the active
flow)
• Forced ventilation (forced flow)
Winter adjustment function
• If the unit is not equipped with heating coil
or if the battery capacity is not enough, this
function can be selected.
• Exhaust fan increases speed with 0-20%
(adjustable) to increase the energy efficiency
of the heat exchanger and increases supply
air temperature.
Fire place funtion
• Via an external switch connected to the units
connecting board you can activate this fea-
ture, see DI4 page 18.
• Exhaust fan control signal then decreases
with 0-20% (adjustable), as long as this input
is activated.
• This produces a positive pressure in the buil-
ding to assist in the start up of the fireplace.
• Recommended time of the function is 0-30
minutes.
Do not forget
Fill in the aligned values in the Protocol Opera-
ting Parameters on page 31, and the little table
in the Quick Guide. Inform finally the end user of
what is done!