15
Manufacturer reserves the right to alter specifications
Hazard
Ensure that power is disconnected before maintenance and electrical work.
Work with electrical connections and maintenance may only be performed by a qualified person
according to local rules and regulations.
Connection parameters
L Brun
N Blå
P Gul/Grön
1 Vit
2 Svart
3 Vit
4 Svart
5 G
6 G0
7 G
8 G0
9 G
10 G0
11 G
12 G0
13 G
14 G0
15 G
16 G0
17 G
18 G0
19 24VAC
20 24VAC
21 0...10V/Y1
22 24VAC/G
23 N/G0
24 0...10V/Y1
0…10V
25 24VAC/G
26 N/G0
N
27 24VAC
28 N
29 C
30 NO
31 C
32 NO
Reläutgång, max 1A / 50V
Reläutgång, max 1A / 50V
PT1000‐givare
Max 0,7A
Endast potentialfri brytare
Endast potentialfri brytare
Endast potentialfri brytare
Endast potentialfri brytare
Endast potentialfri brytare
Endast potentialfri brytare
PT1000‐givare
Endast för isolationsklassad
transformator. Här ansluts 230VAC‐
sidan av transformatorn.
Här ansluts 24VAC‐sidan av
transformator ansluten på CONN3
J1
CONN3
Anslutning för 230VAC till
transformator 24VAC för spjäll
och ventildon (tillbehör)
Akutstopp extern ingång, normalt
sluten
Extern avstängning, normalt
öppen
Anslutning extern trafo 24VAC
(tillbehör)
Max 0,3A
Styrsignal elbatteri (ej i
kombination med VVB)
CONN11
Ventilställdon kylbatteri, 24VAC
(tillbehör)
Ventilställdon vattenbatteri,
24VAC (tillbehör)
Kanalspjäll matning 24VAC
(tillbehör)
Max 0,3A
J2
Anslutning comfortpanel 1,
modularkontakt
Anslutning comfortpanel 2,
modularkontakt
CONN4
CONN10
Frysvakt VVB (tillbehör)
Temperaturgivare tilluft
Aktivering braskamin, normalt
öppen
CONN12
Aktivering cirkulationspump VVB,
normalt öppen
Aktivering cirkulationspump KB,
normalt öppen
CONN9
Extern aktivering högfart, normalt
öppen
Extern aktivering lågfart, normalt
öppen
Används ej, får ej anslutas
Temperaturlarm elbatteri,
normalt sluten
Brown
Blue
Yellow/Green
White
Black
White
Black
G
G0
G
G0
G
G0
G
G0
G
G0
G
G0
G
G0
24VAC
24VAC
0...10V/Y1
24VAC/G
N/G0
0...10V/Y1
24VAC/G
N/G0
24VAC
N
C
NO
C
NO
Connection for 230VAC to transfor-
mer 24VAC for damper and valve
actuator (optional)
Only for rated insulation transformer.
Here you connect 230VAC of transformer
Anti freeze guard for water heater
coil (optional)
PT1000 sensor
Temperature sensor supply air
PT1000 sensor
Temperature alarm to eletrical hea-
ter. Normally closed
Only potential free switch
Emergency stop input, normally
closed
Only potential free switch
External stop, normally open
Only potential free switch
Activation from fire place input, nor-
mally open
Only potential free switch
Activation forced ventilation mode,
normaly open
Only potential free switch
Activation away ventilation mode,
normaly open
Only potential free switch
Not used, do not connect
Connection for external transformer
24VAC (optional)
Here you connect 24VAC to transformer
on CONN3
Connection for 24VAC to cooling coil
valve actuator (optional)
Max 0,3A
0...10V
N
Connection for 24VAC to water hea-
ter coil valve actuator (optional)
Max 0,3A
Signal eletrical heater (can not
be combined with water heater
Connection for damper feed 24VAC
(optional)
Max 0,7A
Connection for pump control of water
heat circut, normally open
Relay OUT, max 1A/50V
Connection for pump control of water
cooling circut, normally open
Relay OUT, max 1A/50V
Connection for comfort panel No 1
(modular connection)
Connection for comfort panel No 2
(modular connection)
You can connect two comfort panels
You can connect two comfort panels