V90EL
The unit can be installed in left (supply) or right-
hand version. If the unit are to be installed in the
right-hand version the built in electric heater EB2
should be relocated, see picture on the right.
Change of flow direction is done as follows.
Remove the electric heater by loosening the three
mounting screws that hold the electric heater.
Unplug the connector on the electric heater.
Pull out the electric heater, turn the device so the
connector is facing down and push the electric
heater between the heat exchanger and the fan on
the right side.
Check that the heating coil moves freely and is not
resting anywhere.
Remove the blind plug (terminal cover) on the right
connecting cable and move it to the left side.
Plug the connector into the electric battery and
fastened the heater with the three screws.
Make sure the cables dont get clamped or abuts
the heat exchanger. Clearing if necessary.
Change the direction of airflow in the unit’s control
system by turning on DIP switch 4 See page 19.
Monting of comfortpanel
IMPORTANT!
Comfort panel shall be located in a conspicuous
and accessible place in your home. Remember
that by using the Comfort panel the user can affect
their indoor climate in an easy and safe way, to
change between different temperature modes and
flow settings. It is also by using the Comfort panel
the user gets information if any alarms occur.
The cable to the Comfort panel is 10 meters long.
Extension cables are available from Luftmiljö AB.
Illustration shows the wall bracket used to
attach the comfort panel.
Left hand, DIP4 left
Right hand, DIP4 right
EB2
EB2
Hazard
Ensure that power is disconnected before maintenance and electrical work.
Work with electrical connections and maintenance may only be performed by a qualified person
according to local rules and regulations.