AMI Codes-II TC
Installation
A-96.250.631 / 280219
33
3.9.
Signal Outputs
3.9.1
Signal Output 1 and 2 (current outputs)
NOTICE:
Max. burden 510
Ω
If signals are sent to two different receivers, use signal isolator
(loop isolator).
Signal output 1: Terminals 14 (+) and 13 (-)
Signal output 2: Terminals 15 (+) and 13 (-)
For programming see
, Menu Installation
3.10
Interface Options
The slot for interfaces can be used to expand the functionality of
the AMI instrument with either:
Third signal output
a Profibus or Modbus connection
a HART connection
a USB Interface
A
B
C
D
AMI Transmitter
Slot for interfaces
Frontend PCB
Screw terminals
A
B
C
D