Suzhou Lily Tech CO., Ltd.
5
U90
Passwords
000~999
000 = no passwords
0
End
Control function
On/off: Controller is off, press
for 3 seconds, controller working. Controller is on, press
for 3 seconds, controller off.
Temperature control
1.
Main control(R1)+Auxiliary control(R2)
(T10 = 0)
a. Main temperature control work:
Measuring temperature ≤
【
Down limit temperature
】
T12, and main temperature control R1 stop time over
【
Main temperature control
(R1)mini stop time
】
T14, main control R1 working.
b Main temperature control off:
Measuring temperature ≥
【
Up limit temperature
】
T11, off main temp. Control R1.
c. Auxiliary temp. Control work:
Measuring temperature ≤
【
Auxiliary temp. Control(R2) start temperature
】
T13, and auxiliary control R2 stop time over
【
Auxiliary
temperature control (R2)mini stop time
】
T15, auxiliary control R2 working.
b Auxiliary temperature control off:
Measuring temperature ≥
【
Auxiliary temp. Control(R2) start temperature
】
T13 + 0.1 degree, auxiliary control R2 off.
2.
External SSR temp. Control up and down limit(T10=1)
Temperature node control mode.
Measuring temperature ≤
【
Down limit temperature
】
T12, and SSR temp. Control stop time over
【
SSR temperature control mini stop
time
】
T16
,
SSR is on.
Measuring temperature ≥
【
Up limit temperature
】
T11, SSR is off.
3.
External SSR PID temperature control(T10=2)
When external SSR main temperature control choose PID mode. Temp. Control will follow PID algorithm.
4.
PID procedure:(If with PID control, it is better to tuning the PID parameters, if the default the setting is not ideal.)
a. Be sure that the equipment inside temp. has been cooled to same to environment temp.
b.Press
and
simultaneously for 5 seconds to enter into tuning set mode. LCD display“Pid tun”,
c.Press
start external SSR, output power is locked,
is on. Controller start turning PID.
d.After PID turning finished,
is off.
e.When the heating temperature over 100
℃
, controller will end this turning, and display “Pid E03” warning with fail turning(press any
key will cancel E03)
f.If self turning dont finished in 60 minutes, controller will display“Pid E04”warning with fail turning(press any key will cancel E04)
g.Press
can cancel warning E03/E04, and restart turning. During turning press
can exist.
Humidity control(R3)
Humidify control(H10 = 0)
When measuring humidity ≤
【
Down limit humidity setting
】
H21, and humidity load stop time over
【
Min humidity load stop time
】
H23,
humidify is on.
When measuring humidity ≥
【
Up limit humidity setting
】
H20, humidify is off.
Dehumidify control(H10 = 1)
When measuring humidity ≥
【
Up limit humidity setting
】
H20, and humidity load stop time over
【
Min humidity load stop time
】
H23,
dehumidify is on.
When measuring humidity ≤
【
Down limit humidity setting
】
H21, dehumidify is off.
Egg-turning control(R6, R7)