Sutron Corporation Satlink Operations & Maintenance Manual, Rev 8.04.2 11/3/2016 pg. 29
Steinhart((10000)*X/(vref-X), A, B, C) (see table below for A, B, C)
Note: The 10000 is the reference resistor value in ohms.
Slope: 1.8; Offset: 32 to convert to Fahrenheit.
Model
TYPE
A
B
C
44007
44034
YSI MIX B, 5K
0.0012829
0.0002365
9.1883E-08
44006
44031
YSI MIX H, 10K
0.0010295
0.0002391
1.568E-07
44005
44030
YSI MIX B, 3K
1.40510E-03
2.36900E-04
1.019E-07
44008
44032
YSI MIX H, 30K
9.35401E-04
2.21060E-04
1.2747E-07
44016
44036
5600-0025
5600-0030
YSI MIX B, 10K
1.12610E-03
2.34545E-04
8.6359E-08
Campbell Scientific’s CS205 & CS107 temperature probe requires different wiring than the
above since it has a reference resistor built into the probe. The wires are connected as indicated
below on the left and the equation will use the built in template for CS205/107. The image on
the right indicates the probe’s internal wiring for reference.
Jumper C+ to Vref
Purple (AG) ----------------- C+
Red (HI) ---------------------- C-
Black (EX) -------------------- AGND
Clear (G) --------------------- Earth Ground
4.18.
Connecting Thermocouples
Thermocouples connect to SL3 to the C, D or E channels as shown below.