background image

MECHANICAL   

 

Mounting details and information are summarized in 

figures 2-6 on subsequent pages. 

The Surna dehumidifier is designed for overhead 
mounting within the space that requires conditioning. 
Prior to mounting, confirm that the supporting 
surface and mounting means are suitably rated for the 
dehumidifier weight load (see 

specifications

 section 

of this document). When mounting, verify the tops of 
the mounting brackets are leveled with respect to one 
another to ensure proper drainage. When the brackets 
are level, the unit will be sloped towards the condensate 
drain.

The Surna dehumidifier requires a minimum of 12 
inches (30.5 cm) vertical clearance above the unit, and a 
minimum of 24 inches (61 cm) (recommended 72 inches 
(182.8 cm)) of clearance on the air intake and exhaust 
sides when placed next to walls or structures. When 
placed next to fan coils or other mechanical equipment, 
the Surna dehumidifier requires 36 inches (91.5 cm) of 
clearance on the air intake and exhaust sides.  
 
DO NOT position the Surna dehumidifier air intake/
exhaust in-line with cold air exhaust from other air 
handling or cooling units/circulatory fans. Improper 
positioning will decrease unit efficiency and could cause 
damage to the unit. 
 
 

ELECTRICAL 

This unit includes a plug and power cord, and should 
be plugged into a dedicated outlet. DO NOT use an 
extension cord. Read the 

specifications

 section of this 

document for more information on the power and circuit 
breaker requirements.  
 
An On/Off switch located on the control box is used 
to provide power to the equipment. The fan in the unit 
will run with the switch in the “OFF” position, but the 
compressor will not run while the switch is in the “OFF” 
position. The On/Off switch should be switched to “ON” 
to begin normal operation. An external switch or circuit 
breaker shall be used as the primary disconnect device. 
The disconnect device shall be accessible to users, have 
a clearly marked On/Off position and must disconnect all 
current carrying conductors simultaneously. 

A humidity controller (humidistat) is supplied with the 
Surna dehumidifier. To use the humidistat as a controller, 
install the switch wire in the provided connector block 
and make the connection to the mating end attached to 
the exterior of the unit.

INSTALLATION 

INSTRUCTIONS

1 0

Summary of Contents for 250 PPD

Page 1: ...SURNA 250 PPD DEHUMIDIFIER OPERATING AND MAINTENANCE MANUAL surna com Model 3 250 March 2019...

Page 2: ......

Page 3: ...TABLE OF CONTENTS Specifications 4 Technical Description 5 Warnings 6 Warranty Information 8 Installation Instructions 10 Operation Instructions 18 Routine Maintenance 19 Troubleshooting 21 3...

Page 4: ...Condensate Drain 3 4 NPT ELECTRICAL Volts Phase 208 230V Single Nominal Current Draw 12 8A 12 0A Maximum Overcurrent Protection 20A Power Factor 99 PERFORMANCE 40 45 50 55 60 65 70 50 100 150 200 250...

Page 5: ...hich act like an expansion valve Refrigerant then flows to the evaporator coil The evaporator coil is where heat is transferred from the incoming air to the liquid refrigerant causing it to evaporate...

Page 6: ...adhere to all applicable safety guideline requirements in this document and all applicable electrical and mechanical jurisdictional codes Using Surna dehumidifying equipment in a manner not described...

Page 7: ...fied licensed service technician DO NOT use extension cords or plug adapters These actions may result in a fire hazard or electric shock This unit must be connected to a protective earthing system pri...

Page 8: ...bilities under this Warranty are limited to furnishing replacement equipment or parts at its option FCA Incoterms 2000 factory or warehouse f o b factory or warehouse for US domestic purposes at Compa...

Page 9: ...vidual order 1 Surna 250 PPD dehumidifier 2 Surna 250 PPD dehumidifier product manual 3 Humidistat 4 15 ft of thermostat wire 5 PVC condensate trap INTENDED APPLICATION The Surna dehumidifier is inten...

Page 10: ...ust in line with cold air exhaust from other air handling or cooling units circulatory fans Improper positioning will decrease unit efficiency and could cause damage to the unit ELECTRICAL This unit i...

Page 11: ...n overflow Use of a p trap reference figure 2 is required to avoid pressure and vacuum related issues which can negatively affect condensate drainage Following plumbing installation the system should...

Page 12: ...Pan Vent Mounting Brackets P Trap Drain Airflow In Airflow Out Ceiling 12 min clearance Exhaust min 24 Clearance Air Intake min 24 Clearance Figure 2 Installation diagram shows proper mounting of Sur...

Page 13: ...tructure in front of intake or discharge A FLOW FLOW 3 W O L F W O L F REQUIRED UNIT CLEARANCES Figure 3 Required minimum clearances for Surna dehumidifier A Minimum 12 inches 30 5 cm of clearance abo...

Page 14: ...a e l c f o s e h c n i 2 1 n i M A B Min 24 inches recommended 72 inches between 2 units with adjacent intakes FLOW FLOW FLOW FLOW B 4 FLOW FLOW 3 1 or 2 5 A A Minimum 12 inches 30 5 cm of clearance...

Page 15: ...ing fans within 3 feet recommended 72 inches from intake or discharge of unit A Min 12 inches of clearance above and below FLOW FLOW FLOW FLOW FLOW FLOW A A 3 A Minimum 12 inches of clearance above an...

Page 16: ...humidifier Oppose flow by 90 degrees for neighboring units No conditioned air discharge or circulating fans within 3 feet minimum recommended 72 inches from intake or discharge of unit A Minimum 24 in...

Page 17: ...DELAY RELAY HUMIDITY CONTROL FAN MOTOR COMPRESSOR CAP FAN RELAY COMPRESSOR RANCO TEMP CONTROL RED YELLOW BLUE BLK WHITE RED BLUE BLK RED BLUE LINE NEUTRAL WHITE COM ORANGE 240 VAC RED 24 VAC BLUE BLUE...

Page 18: ...ont of the unit to the ON position and set the provided humidity controller to the desired setting for the space A D DRAWN Mounting Brackets Filter Set Screw Dehumidistat Switch Connector ON OFF Toggl...

Page 19: ...e of the unit DO NOT use coil cleaner that is designed for outdoor coils as it may be corrosive The Surna Dehumidifier comes equipped with an electrostatic filter If properly maintained electrostatic...

Page 20: ...f it is not possible to clean the filter to the point where light is able to shine through the filter should be replaced 6 Let filter air dry for at least 10 minutes The filter can be used damp but no...

Page 21: ...istat is set to on NOTE The Surna dehumidifier is intended to operate in temperatures above 70 F 21 C and relative humidity of 45 or higher Temperature and relative humidity affect performance Contact...

Page 22: ...NOTES 22...

Page 23: ...NOTES 23...

Page 24: ...surna com 1780 55th Street Boulder CO 80301 303 993 5271 info surna com A P E 24...