20
6.3.3 Setpoint Parameters (SEtP)
No.
Sign
Range
Default
Description
Set
200
P1
0~99999
1000
Weight Setpoint 1
201
P2
0~99999
9000
Weight Setpoint 2
202
nL
0~50000
50
Non-load Zero Range
Peak Value Detection:
‘Weight > Non-load Zero Range’ for triggering the
peak value detection process.
‘Weight
≤
Non-load Zero Range’ for stopping the
peak value detection process.
Auto Weight-checking:
Switch Triggering Mode:
If the DI switch ‘Weight-checking Photo-electric
Identification’ is defined, the weight-checking
process will be triggered when the DI switch turns
on.
Weight Triggering Mode:
If the DI switch ‘Weight-checking Photo-electric
Identification’ is not defined, the weight-checking
process will be triggered when ‘Weight > Non-load
Zero Range’.
Once ‘Weight
≤
Non-load Zero Range’ or
‘Weight-checking Time
≥
[212] Weight-checking
Timeout’, the weight-checking process will end
automatically.
Refer to parameters [213]~[215] ‘DI1/DI2/DI3
Signal’.
203
dA
0~2
0
Data Compared with Weight Setpoints
0. nEt
[Real-time Weight]
1. PnEt
[Weight Peak Value]
2. CHC
[Checking-weight Value]
204
do
0~1
1
DO Output Permission
0: oFF
1: on