6.3.4 Extra Control Parameters
No.
Parameter
Range
Default
Set
P210
InIHoldTime
0.0-999.9s
PID Initial Current Hold Time
2.0
P211
PID Ini.Cur
(PID Initial Current)
0: Present (Present Current Value)
1: Fuzzy (Fuzzy Current Value)
2: Set [P219] (Set Value of [P219])
0
P212
Fuzzy Equ.
(Fuzzy Equivalent)
0.01~100.00 [t/h]/mA
([P107] Scale Unit = kg)
Flow Increment per Increasing 1mA Adjusting
Current.
2.50
0.01~100.00 [kg/h]/mA
([P107] Scale Unit = g)
P213
ST/SP Delay
(Start/Stop Delay Time)
0.0~999.9s
Delay Time of Feeder Starting
Delay Time of Scale Stopping
0.0
P214
BatchPermit
(Batch Permission)
0: OFF; 1: ON
0
P215
Batch Loop
(Batch Loop Mode)
0: Manual Mode; 1: Auto Mode
0
P216
Batch Int.
(Batch Interval)
0.0~9999.9s
60.0
P217
Batch Set
(Batch Weight Setpoint)
0~99999999kg
([P107] Scale Unit = kg)
0
0~99999999g
([P107] Scale Unit = g)
P218
BatchPreact
0~[P217] kg
([P107] Scale Unit = kg)
Batch Preact Weight
0
0~[P217] g
([P107] Scale Unit = g)
P219
Set Current
4.00~20.00mA
Set Value of PID Initial Current
12.00
Note:
[P213] Start/Stop Delay:
1. Delay Time of Feeder Starting: When there is a “DI.Start” pulse signal input, ‘DO. Scale Start&Stop Control’ will
turn on to start the belt weigher, and after delaying this time, ‘DO. Feeder Start&Stop Control’ will turn on to start the
feeder.
2. Delay Time of Scale Stopping: When there is a “DI.Stop” pulse signal input, ‘DO. Feeder Start&Stop Control’ will
turn off to stop the feeder, and after delaying this time, ‘DO. Scale Start&Stop Control’ will turn off to stop the belt
weigher.