NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

start

cHecK

• turn off Gas supply.
• ensure Valve switch is in on position.
• disconnect control Harness.
• set thermostat to call For Heat.

•  check  for  proper  volt-

age at control harness  
(see insert a).  Voltage 
should be 24V   between 
thermostat or pressure 
switch and 24V common 
and 24V hot.

no

•  Line voltage power
•  Low voltage transformer
•  Limit controller
•  thermostat
•  Wiring

                      Yes

•  plug  control  harness  into 

valve.  Wait for internal check 
delay.

 • igniter warms up and glows 

red. 

no

  •  With  pilot  burner  cable  con-

nected,  measure  voltage  at 
valve Hsi element output.  24V 
nominal.  (see insert B)

no

•  replace valve.

                         Yes

                      Yes

•  replace igniter/flame rod 
    assembly.

                         Yes

• turn on gas supply.   
• pilot burner lights.

no

•  check that pilot gas is flowing.  Wait 

to ensure pilot gas tubing is purged.  
recycle call for heat if necessary.

no

•  replace valve.

                         Yes

                      Yes

•   Measure voltage between 24V hot and 

24V common leads to valve control.  
Must measure at least 9.5 Vac with 
igniter powered (see insert a).  to 
identify proper lead, this check must 
be done with the valve control con-
nected and igniter powered.

no

•  check transformer and    

line volt supply.

                         Yes

•    replace pilot assembly.

•  Main valve opens and main 

burner lights.

no

•  check that pilot flame makes good 

contact with pilot burner flame rod.

•    check for good electrical connection 

through the pilot tubing.

•   if both of the above are good, replace 

igniter/flame rod assembly.

                      Yes

                         Yes

•  system is okay.

•    cycle thermostat off and back on.

   

Igniter  will  cycle  off  and 

back on once during the 90 
second  ignition  trial.    All 
voltage measurements must 
be taken while the igniter is 
powered.

 

      

When measuring voltage 

at connections, use care 
to ensure terminals are 
not damaged.

•    Main burner lights.

no

 •  replace valve.

insert a

end View of control Harness connector

24 Volt

common

24 Volt Hot

24 Volt 

switched

check For damaged or Missing

terminals in connector

insert B

igniter terminals

1

2

2

1

2

1

trouBLesHootinG procedure - eLectronic iGnition sYsteM

Summary of Contents for SSDVR-3328C

Page 1: ...u de tout autre appareil POUR VOTRE S CURIT Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Ne touchez aucun interrupteur Ne pas vous servir des t l phones se trouvant dan...

Page 2: ...lves millivolt models NATURAL PROPANE GAS Models Input Rate BTU HR SSDVT R 3328 17 500 high 13 500 low Table 1 Provide adequate clearances around air open ings and adequate accessibility clearance for...

Page 3: ...re The gas valve for electronic systems is also located below the glass enclosure panel See Figure 1 Reinstalling Control Compartment Door Toreinstall insertthehookcatchesoneachside of the door into t...

Page 4: ...ell Millivolt Gas Valve Figure 5 O N OFF P I L OT L O H I OFF ON OFF ON Figure 3 Optional Blower OFF ON Rocker Switch SIT Millivolt Gas Valve Gas Outlet Gas Inlet Pilot Adjustment Screw Terminals TPTH...

Page 5: ...see Page 23 for ordering information Re Install Embers Logs and Volcanic Stone Carefully follow placement instructions on Pages 7 to 9 All logs should fit onto cor responding pins and or log stoppers...

Page 6: ...ut and adjust ment period a potential safety hazard exists EXERCISE EXTREME CAUTION to prevent the occurrence of any burn injuries from the exposedflamesorhotsurfaces Alsonote that while the front gla...

Page 7: ...t the rear log on the raised log support brackets at the rear of the firebox fitting the slots in the logs over the brackets 2 Position the front log with the pins for the two side twigs in the up pos...

Page 8: ...NOTE DIAGRAMS ILLUSTRATIONSNOTTOSCALE NOTES...

Page 9: ...ew more minutes to ensure that the flame normalizes and the flames do not appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation...

Page 10: ...ANCAUSEIMPROPERAND DANGEROUS APPLIANCE OPERATION Figure 13 3 8 to 1 2 9 13 mm Ground Electrode Flame Rod Hot Surface Igniter Proper Flame Adjustment Pilot Nozzels ELECTRONIC PILOT ASSEMBLY Proper Pilo...

Page 11: ...icsattacheddirectlytothe appliance on a pullout panel located within the control compartment TH TP TH TP Thermopile If any of the original wire as supplied must be replaced it must be replaced with Ty...

Page 12: ...12 NOTE DIAGRAMS ILLUSTRATIONSNOTTOSCALE NOTES...

Page 13: ...perature variables using the hand held remote control transmitter The Model RCL T Deluxe remote control system is installed in the same manner as the standard system may be operated with electronic an...

Page 14: ...vers Kits These kits include a top 4 louver assembly and a bottom 4 louver assembly They provide a touch of elegance These kits can be retrofitted to previously installed appliances Door Frame Kits A...

Page 15: ...l painted surfaces may be accomplished with the touch up paint kit PA I N T Bag of Glowing Embers Bag of Volcanic Stone Replacement ember materials or volcanic stone are available for use with these a...

Page 16: ...ualified service technician Force or attempted repair may result in a fire or an explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician...

Page 17: ...ecompagniedegazenutilisantlet l phone du voisin S il vous est impossible de contacter votre compagnie de gaz appelez le service des incendies C N utilisez que votre main pour manipuler le bouton de r...

Page 18: ...gas control which has been under water Lighting Instructions Electronic 1 For complete shut down turn remote wall switch to OFF 2 Open lower control compartment door 3 Turn the OFF ON switch to OFF D...

Page 19: ...s l eau 1 ARR TEZ Lisez les consignes de s curit au verso de cette plaque 2 Tournez l interrupteur mural la position d arr t OFF 3 Ouvrez la porte du compartiment de contr le du bas 4 Assurez vousquel...

Page 20: ...eral runs too many elbows and or exterior portions of the system being exposed to cold weather Also inspect wall straps or plumbers s tape to ensure it is secure and in place Appliance Checkout Qualif...

Page 21: ...itch is used for burner operation if the standard burner OFF ON switch is still installed on appliance it must be in the OFF position Optional remote switch kits wall switch wall thermostat or remote...

Page 22: ...common leads to valve control Mustmeasureatleast19 5VACwith igniter powered see insert A To identifyproperlead thischeckmust be done with the valve control con nected and igniter powered NO Check tra...

Page 23: ...s Fireplace Assembly 1 1 d o o H 1 1 1 r Upper e v u o L 2 1 1 Lower r e v u o L 3 4 Enclosure Glass Front Complete 1 1 5 Nameplate Brand 56L93 1 56L93 1 2 2 h c t a L 6 7 Catch Door Magnetic 69L31 1...

Page 24: ...e in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP 1110 West Taft Avenue Orange CA 92865 R...

Reviews: