TROUBLESHOOTING GUIDE - MILLIVOLT GAS CONTROL SYSTEM

Note: Before troubleshooting the gas control system, Ensure external gas shut off valve, located at gas supply inlet, (and wall switch, iff applicable), 

is in the “ON” position.
Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

sYMptoM

possiBLe causes

correctiVe action

.

  Spark igniter will not light pilot after 

repeated triggering of igniter button.

  WARNING: if the pilot will not light 

after 1 minute of attempting, wait 

for at least 5 minutes for gas to 

clear before attempting again.

a.

  Defective igniter

  (no spark at electrode).

Check for spark at electrode and pilot; if no spark and 

electrode wire is properly connected, replace igniter.

B.

  Defective or misaligned electrode at pilot 

(spark at electrode).

Using a match, light pilot. If pilot lights, turn off pilot 

and trigger the igniter button again. If pilot lights, an 

improper gas mixture caused the bad lighting and a 

longer purge period is recommended. If pilot will not 

light – check gap at electrode and pilot – should be 1/8" 

to have a strong spark. If gap measures 1/8", replace 

pilot (see 

Figure

s

11 or 12 

on 

Page 10)

.

c.

  Gas supply pressure errant.

Check inlet gas pressure. It should be within the limits 

as marked on the rating plate.

d.

  Pilot orifice plugged.

Clean or replace pilot orifice.

2.

  Pilot will not stay lit after  

carefully following the lighting 

instructions.

a.

  Defective pilot generator 

(thermocouple).

Check pilot flame, it must impinge on thermocouple  

(see 

Figure

s

11  or  12 

on 

Page  10

). 

Clean  and/or 

adjust  pilot  for  maximum  flame  impingement  on 

thermocouple. Ensure that the connection between 

the valve and thermocouple are tight and secure.

3.

  Pilot burning, no gas to burner, Valve 

knob “ON,” and the (standard) burner 

OFF/ON switch is “ON."  Read impor-

tant note below.

 

IMPORTANT NOTE: If an optional 

*remote switch is used for burner 

operation, if the standard burner 

OFF/ON switch is still installed on 

appliance it must be in the "OFF" 

position.

  *

Optional remote switch kits - wall 

switch, wall thermostat or remote 

control.

a.

  Wall switch or wires defective.

Check wall switch and wires for proper connections. 

Jumper wire across terminals at wall switch, if burner 

comes on, replace defective wall switch. If okay, jumper 

wires across wall switch wires at valve, if burner comes 

on, wires are faulty or connections are bad.

B.

  Thermopile may not be generating suf-

ficient millivolts.

Check thermopile with millivolt meter. Take reading 

at  thermopile  terminals  of  gas  valve.  Should  read 

325  millivolts  minimum  with  optional  wall  switch 

“OFF.” Replace faulty thermopile if reading is below 

specified minimum.

c.

  Plugged burner orifice.

Check burner orifice for blockage and remove.

d.

  OFF/ON Switch & *Remote Switch are in 

the "ON" position resulting in excessive 

resistance.

When turning on the burner using a *remote switch, 

ensure that the standard OFF/ON switch is in the "OFF" 

position.  If both switches are in the ON position, it 

may result in excessive resistance (& millivolt drain-

age) and the burner may not come on.

4.

  Frequent pilot/burner outage prob-

lem.

a.

  Pilot flame may be too low or blowing (high) 

causing the pilot/valve safety to drop out.

Clean and/or adjust pilot flame for maximum flame 

impingement  on  thermocouple    (see 

Figure

s

11  or 

12 

on 

Page 10

).

sYMptoM

possiBLe causes

correctiVe action

.

  Burner will not light.

a.

  Faulty Valve System.

See Below.

B.

  “OFF/ON” or wall switch defective.

Disconnect the two black wires from the wire nuts. 

Test  switch(s)  for  continuity  with  a  multimeter.  If 

continuity is not indicated, switch(s) is defective and 

must be replaced.

Note: 

Before replacing “OFF/ON” switch, Ensure to 

check wiring for loose connections or broken wires 

and repair as needed.

2.

  Burners come “ON,” then turns “OFF.”

a.

  Burner orifice plugged.

Check  main  burner  orifice(s)  for  blockage.  Clean 

or replace.

B.

  Obstructed vent system.

Check vent system for obstructions.  

trouBLesHootinG

TROUBLESHOOTING GUIDE - ELECTRONIC IGNITION SYSTEM

Summary of Contents for SSDVR-3328C

Page 1: ...u de tout autre appareil POUR VOTRE S CURIT Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Ne touchez aucun interrupteur Ne pas vous servir des t l phones se trouvant dan...

Page 2: ...lves millivolt models NATURAL PROPANE GAS Models Input Rate BTU HR SSDVT R 3328 17 500 high 13 500 low Table 1 Provide adequate clearances around air open ings and adequate accessibility clearance for...

Page 3: ...re The gas valve for electronic systems is also located below the glass enclosure panel See Figure 1 Reinstalling Control Compartment Door Toreinstall insertthehookcatchesoneachside of the door into t...

Page 4: ...ell Millivolt Gas Valve Figure 5 O N OFF P I L OT L O H I OFF ON OFF ON Figure 3 Optional Blower OFF ON Rocker Switch SIT Millivolt Gas Valve Gas Outlet Gas Inlet Pilot Adjustment Screw Terminals TPTH...

Page 5: ...see Page 23 for ordering information Re Install Embers Logs and Volcanic Stone Carefully follow placement instructions on Pages 7 to 9 All logs should fit onto cor responding pins and or log stoppers...

Page 6: ...ut and adjust ment period a potential safety hazard exists EXERCISE EXTREME CAUTION to prevent the occurrence of any burn injuries from the exposedflamesorhotsurfaces Alsonote that while the front gla...

Page 7: ...t the rear log on the raised log support brackets at the rear of the firebox fitting the slots in the logs over the brackets 2 Position the front log with the pins for the two side twigs in the up pos...

Page 8: ...NOTE DIAGRAMS ILLUSTRATIONSNOTTOSCALE NOTES...

Page 9: ...ew more minutes to ensure that the flame normalizes and the flames do not appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation...

Page 10: ...ANCAUSEIMPROPERAND DANGEROUS APPLIANCE OPERATION Figure 13 3 8 to 1 2 9 13 mm Ground Electrode Flame Rod Hot Surface Igniter Proper Flame Adjustment Pilot Nozzels ELECTRONIC PILOT ASSEMBLY Proper Pilo...

Page 11: ...icsattacheddirectlytothe appliance on a pullout panel located within the control compartment TH TP TH TP Thermopile If any of the original wire as supplied must be replaced it must be replaced with Ty...

Page 12: ...12 NOTE DIAGRAMS ILLUSTRATIONSNOTTOSCALE NOTES...

Page 13: ...perature variables using the hand held remote control transmitter The Model RCL T Deluxe remote control system is installed in the same manner as the standard system may be operated with electronic an...

Page 14: ...vers Kits These kits include a top 4 louver assembly and a bottom 4 louver assembly They provide a touch of elegance These kits can be retrofitted to previously installed appliances Door Frame Kits A...

Page 15: ...l painted surfaces may be accomplished with the touch up paint kit PA I N T Bag of Glowing Embers Bag of Volcanic Stone Replacement ember materials or volcanic stone are available for use with these a...

Page 16: ...ualified service technician Force or attempted repair may result in a fire or an explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician...

Page 17: ...ecompagniedegazenutilisantlet l phone du voisin S il vous est impossible de contacter votre compagnie de gaz appelez le service des incendies C N utilisez que votre main pour manipuler le bouton de r...

Page 18: ...gas control which has been under water Lighting Instructions Electronic 1 For complete shut down turn remote wall switch to OFF 2 Open lower control compartment door 3 Turn the OFF ON switch to OFF D...

Page 19: ...s l eau 1 ARR TEZ Lisez les consignes de s curit au verso de cette plaque 2 Tournez l interrupteur mural la position d arr t OFF 3 Ouvrez la porte du compartiment de contr le du bas 4 Assurez vousquel...

Page 20: ...eral runs too many elbows and or exterior portions of the system being exposed to cold weather Also inspect wall straps or plumbers s tape to ensure it is secure and in place Appliance Checkout Qualif...

Page 21: ...itch is used for burner operation if the standard burner OFF ON switch is still installed on appliance it must be in the OFF position Optional remote switch kits wall switch wall thermostat or remote...

Page 22: ...common leads to valve control Mustmeasureatleast19 5VACwith igniter powered see insert A To identifyproperlead thischeckmust be done with the valve control con nected and igniter powered NO Check tra...

Page 23: ...s Fireplace Assembly 1 1 d o o H 1 1 1 r Upper e v u o L 2 1 1 Lower r e v u o L 3 4 Enclosure Glass Front Complete 1 1 5 Nameplate Brand 56L93 1 56L93 1 2 2 h c t a L 6 7 Catch Door Magnetic 69L31 1...

Page 24: ...e in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP 1110 West Taft Avenue Orange CA 92865 R...

Reviews: