Superior SSDVPF-CNE Installation Instructions Manual Download Page 4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Note:

 The following requirements reference various Massachusetts 

and national codes not contained in this document.

Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every 
dwelling, building or structure used in whole or in part for residential 
purposes, including those owned or operated by the Commonwealth and 
where the side wall exhaust vent termination is less than seven (7) feet 
above fi nished grade in the area of the venting, including but not limited 
to decks and porches, the following requirements shall be satisfi ed: 

Installation Of Carbon Monoxide Detectors 

At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfi tter shall observe that a hard 
wired carbon monoxide detector with an alarm and battery back-up is 
installed on the fl oor level where the gas equipment is to be installed. 
In addition, the installing plumber or gasfi tter shall observe that a bat-
tery operated or hard wired carbon monoxide detector with an alarm is 
installed on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equipment. It shall 
be the responsibility of the property owner to secure the services of 
qualifi ed licensed professionals for the installation of hard wired carbon 
monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment 
is installed in a crawl space or an attic, the hard wired carbon monoxide 
detector with alarm and battery back-up may be installed on the next 
adjacent fl oor level.

 In the event that the requirements of this subdivision can not be met at 
the time of completion of installation, the owner shall have a period of 
thirty (30) days to comply with the above requirements; provided, how-
ever, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the 
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certifi ed.

Signage

A metal or plastic identifi cation plate shall be permanently mounted to 
the exterior of the building at a minimum height of eight (8) feet above 
grade directly in line with the exhaust vent terminal for the horizontally 
vented gas fueled heating appliance or equipment. The sign shall read, in 
print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

Inspection

The state or local gas inspector of the side wall horizontally vented gas 
fueled equipment shall not approve the installation unless, upon inspection, 
the inspector observes carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

•  The equipment listed in Chapter 10 entitled “Equipment Not Required 

To Be Vented” in the most current edition of NFPA 54 as adopted by 
the Board; and

•  Product Approved side wall horizontally vented gas fueled equipment 

installed in a room or structure separate from the dwelling, building 
or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally 
vented gas equipment provides a venting system design or venting sys-
tem components with the equipment, the instructions provided by the 
manufacturer for installation of the equipment and the venting system 
shall include:

•  Detailed instructions for the installation of the venting system design 

or the venting system components; and 

•  A complete parts list for the venting system design or venting sys-

tem.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally 
vented gas fueled equipment does not provide the parts for venting the 
fl ue gases, but identifi es “special venting systems”, the following require-
ments shall be satisfi ed by the manufacturer:

•  The referenced “special venting system” instructions shall be included 

with the appliance or equipment installation instructions; and 

•  The “special venting systems” shall be Product Approved by the 

Board, and the instructions for that system shall include a parts list 
and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall 
horizontally vented gas fueled equipment, all venting instructions, all 
parts lists for venting instructions, and/or all venting design instructions 
shall remain with the appliance or equipment at the completion of the 
installation.

•  Installation and repair must be done by a plumber or gas fi tter licensed 

in the Commonwealth of Massachusetts.

•  The fl exible gas line connector used shall not exceed 36 inches (92 

centimeters) in length.

•  The individual manual shut-off must be a T-handle type valve.

4

Summary of Contents for SSDVPF-CNE

Page 1: ...uch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If your gas supplier cannot be reach...

Page 2: ...sted for operation and installation with the following vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter nat...

Page 3: ...H I LO W H T P T H T P T P I L O T P I L O T O N i t OFF IN OUT Manifold Pressure Tap Inlet Pressure Tap SIT Millivolt Gas Valve Pilot Adjustment Screw HI LO Variable Flame Height Adjustment Main Gas...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...mproper installation or use of this appli ance can cause serious injury or deathfromfire burns explosion or carbon monoxide poisoning IMPORTANT These appliances must not be connected to a chimney or f...

Page 6: ...le home where not prohibited by local codes This appliance may be installed as an OEM installation in a manufactured home USA only or mobile home and must be installed in accordance with the manufactu...

Page 7: ...CES These instructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1...

Page 8: ...3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 fee...

Page 9: ...on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air g...

Page 10: ...1 2 3 8 10 40 1 2 1 2 40 100 1 2 1 2 100 150 3 4 1 2 150 200 3 4 1 2 Table 8 Notes All appliances are factory equipped with a flexiblegaslineconnectorand1 2inchshutoff valve see Figure 47 on Page 27 S...

Page 11: ...0 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left S...

Page 12: ...ry installed vent seal cap see Figures 15 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door Left Side View T...

Page 13: ...nal Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Use only approved venting components See Approved Vent Compo nents Page 2 These fireplaces must...

Page 14: ...1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2...

Page 15: ...n installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telesc...

Page 16: ...tions See Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm atal...

Page 17: ...needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run...

Page 18: ...1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet...

Page 19: ...with 8d nails or other ap propriate fasteners at each corner Remembertomaintain1 25mm clearance tocombustibles framingmembers andattic or ceiling insulation when running vertical chimney sections Atti...

Page 20: ...seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal te...

Page 21: ...ionKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 3 4 to 20 299 to...

Page 22: ...Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 11 as an aid in venting component selection for a particular range...

Page 23: ...s Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For ev...

Page 24: ...y around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from th...

Page 25: ...el OFF ON Switch TP TH TH Install OFF ON Switch millivolt models 1 Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve 2 Pass the 2 wires through the opening w...

Page 26: ...h wires CAUTION Remove the carton support from the control compartment before operating the appliance Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 FBK 250 Kit...

Page 27: ...igure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The incoming gas line should be piped into th...

Page 28: ...ce Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the t...

Page 29: ...top louver assembly by lifting it up and pulling it out 2 Remove the control compartment access door see removal instructions on Page 27 Removing Control Compartment Door 3 Locate the two 2 latches at...

Page 30: ...erving the flame continu ouslytoensurethattheproperflameappear ance has been achieved see Figure 52 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the...

Page 31: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 32: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 33: ...stallation is not proper and completeuntiltheoperationofthe convertedapplianceischeckedas specifiedintheownerinstructions suppliedwiththekit Thequalified service agency performing this installationass...

Page 34: ...kit is available order Catalog No 87L54 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 61 and the instructions provided with the kit Remove the slotted cap screw o ring pressure...

Page 35: ...nstall the rear burner in the front burner s position BRACKET A BURNER PORTS NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step9 Reassembletheremainingcomponents by reversing the pro...

Page 36: ...o make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP...

Reviews: