Superior SSDVPF-CNE Installation Instructions Manual Download Page 19

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

19

HORIZONTAL (OUTSIDE WALL) 
TERMINATION SYSTEM

See 

Figure 32

, and

 Figures 35 

to 

40 

and 

their associated Horizontal Vent Table which 
illustrates the horizontal venting confi gura-
tions that are allowed to be used with these 
appliances.  

Secure Vent

 pipe applications are 

shown in these fi gures; 

Secure Flex

 pipe may 

also be used (see

 Page 24

)

. A Horizontal Vent 

Table summarizes each system’s minimum and 
maximum vertical and horizontal length values 
that can be used to design and install the vent 
components in a variety of applications. 

Both of these horizontal vent systems terminate 
through an outside wall.  Building Codes limit or 
prohibit terminating in specifi c areas. Refer to 

Figure 6

 on

 Page 8

 for location guidelines.

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 
featuring positive twist lock connection, (

refer 

to 

Figure 20 

on

 

Page 15

).

  All of the appli-

ances covered in this document are fi tted with 
collars having locking inclined channels. The 
dimpled end of the vent components fi t over 
the appliance collar to create the positive twist 
lock connection.

A.

 

Plan the vent run -

 

Analyze the vent routing and determine the 
types and quantities of sections required 

 

 

 

 

 

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" 
(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 
mm) net section lengths are available. Plan the 
vent lengths so that a section joint does not occur 
within the space defi ned by ceiling joists, roof 
rafters or wall studs. Make allowances for elbows 
as indicated in 

Figure 23 

on 

Page 16

Figure 32 -

TYPICAL HORIZONTAL VENT INSTALLATION

See 

Figures 21 

22

  for verti-

cal vent section support.

Horizontal / Inclined Run

Support

Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

 Firestop / Spacer

SV4.5VF

 When Using Secure Flex, 

Use Firestop / Spacer SF4.5VF

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

To add another vent component to a length 
of vent run, align the dimpled end of the 
component over the inclined channel end of 
the previously installed section, adjusting the 
radial alignment until the four locking dimples 
are aligned with the inlets of the four incline 
channels of the previous section.  Push the vent 
component against the previous section until it 
fully engages, then twist the component clock-
wise running the dimples down and along the 
incline channels until they seat at the end of the 
channels.  

This seating position is indicated 

by the alignment of the arrow and dimple as 
shown in

 

Figure 20 on Page 15.

F.

 

Install fi restop / spacer at ceiling - 

When using Secure Vent, use SV4.5VF fi restop 
/ spacer at ceiling joists; when using Secure 
Flex, use SF4.5VF fi restop / spacer. If there is 
living space above the ceiling level, the fi restop/ 
spacer must be installed on the bottom side of 
the ceiling. If attic space is above the ceiling, 
the fi restop/ spacer must be installed on the 
top side of the joist. Route the vent sections 
through the framed opening and secure the 
fi restop / spacer with 8d nails or other ap-
propriate fasteners at each corner.

Remember to maintain 1" (25 mm) clearance 
to combustibles, framing members, and attic 
or ceiling insulation when running vertical 
chimney sections. Attic insulation shield 
(96K94) may be used to obtain the required 
clearances indicated here. See installation 
accessories Tables on 

Pages 31 and 32

.

G.

 

Support the vertical run sections - 

See Step E on Page 15.

H. Change vent direction - 

 At transition from 

or to a horizontal / inclined run, install the 
SV4.5E45 and SV4.5E90 elbows in the same 
manner as the straight vent sections.  The 
elbows feature a twist section to allow them to 
be routed about the center axis of their initial 
collar section to align with the required direc-
tion of the next vent run element. 

Twist elbow 

sections in a clockwise direction only so as 
to avoid the possibility of unlocking any of 
the previously connected vent sections. 

 See 

Figure 20 on Page 15

.

I.

 

Continue installation of horizontal / inclined 

sections -

  Continue with the installation of the 

straight vent sections in horizontal / inclined run 
as described in 

Step E

. Install support straps 

every 5 ft. (1.52 m) along horizontal / inclined 
vent runs using conventional plumber’s tape. 
See 

Figure 32.

 

It is very important that the 

horizontal / inclined run be maintained in a 
straight (no dips) and recommended to be in 
a slightly elevated plane, in a direction away 
from the fi replace of 1/4" rise per foot (20 mm 
per meter)

 which is ideal, though rise per foot 

run ratios that are smaller are acceptable all the 
way down to at or near level.  Use a carpenter’s 
level to measure from a constant surface and 
adjust the support straps as necessary. 

Maintain a minimum 1" (25 mm) clearance to 
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm) 
on top, 1" (25 mm) on sides, and 1" (25 mm) 
at the bottom.

B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on the exte-
rior wall according to the dimensions shown in 

Figures 13 & 14 

on

 

Pages 11 & 12

.

Cut and/or frame an opening, 10-1/2" x 12 1/8" 
(267 mm x 308 mm) inside dimensions, about 
this center.

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 
the center above the appliance. Cut and/or frame 
an opening, 10-1/2" x 10-1/2" (267 mm x 267 
mm) inside dimensions, about this center (refer 
to 

Figure 19 

on

 

Page 15

)

.

D. Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking 
dimples are aligned with the inlets of the four 
incline channels on the collar (

refer to 

Figure 

20 

on

 Page 15

).

Push the vent component against the collar 
until it fully engages, then twist the component 
clockwise, running the dimples down and along 
the incline channels until they seat at the end of 
the channels. The unitized design of the 

Secure 

Vent

 components will engage and seal both the 

inner and outer pipe elements with the same 
procedure.  Sealant and securing screws are 
not required.

E.  Attach vent components to each other 
-

 Other vent sections may be added to the 

previously installed section in accordance with 
the requirements of the vent tables.  

SV4.5HT-2

Termination

Shown

SV4.5HT-2

Termination

Shown

Summary of Contents for SSDVPF-CNE

Page 1: ...uch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If your gas supplier cannot be reach...

Page 2: ...sted for operation and installation with the following vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter nat...

Page 3: ...H I LO W H T P T H T P T P I L O T P I L O T O N i t OFF IN OUT Manifold Pressure Tap Inlet Pressure Tap SIT Millivolt Gas Valve Pilot Adjustment Screw HI LO Variable Flame Height Adjustment Main Gas...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...mproper installation or use of this appli ance can cause serious injury or deathfromfire burns explosion or carbon monoxide poisoning IMPORTANT These appliances must not be connected to a chimney or f...

Page 6: ...le home where not prohibited by local codes This appliance may be installed as an OEM installation in a manufactured home USA only or mobile home and must be installed in accordance with the manufactu...

Page 7: ...CES These instructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1...

Page 8: ...3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 fee...

Page 9: ...on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air g...

Page 10: ...1 2 3 8 10 40 1 2 1 2 40 100 1 2 1 2 100 150 3 4 1 2 150 200 3 4 1 2 Table 8 Notes All appliances are factory equipped with a flexiblegaslineconnectorand1 2inchshutoff valve see Figure 47 on Page 27 S...

Page 11: ...0 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left S...

Page 12: ...ry installed vent seal cap see Figures 15 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door Left Side View T...

Page 13: ...nal Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Use only approved venting components See Approved Vent Compo nents Page 2 These fireplaces must...

Page 14: ...1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2...

Page 15: ...n installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telesc...

Page 16: ...tions See Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm atal...

Page 17: ...needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run...

Page 18: ...1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet...

Page 19: ...with 8d nails or other ap propriate fasteners at each corner Remembertomaintain1 25mm clearance tocombustibles framingmembers andattic or ceiling insulation when running vertical chimney sections Atti...

Page 20: ...seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal te...

Page 21: ...ionKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 3 4 to 20 299 to...

Page 22: ...Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 11 as an aid in venting component selection for a particular range...

Page 23: ...s Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For ev...

Page 24: ...y around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from th...

Page 25: ...el OFF ON Switch TP TH TH Install OFF ON Switch millivolt models 1 Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve 2 Pass the 2 wires through the opening w...

Page 26: ...h wires CAUTION Remove the carton support from the control compartment before operating the appliance Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 FBK 250 Kit...

Page 27: ...igure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The incoming gas line should be piped into th...

Page 28: ...ce Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the t...

Page 29: ...top louver assembly by lifting it up and pulling it out 2 Remove the control compartment access door see removal instructions on Page 27 Removing Control Compartment Door 3 Locate the two 2 latches at...

Page 30: ...erving the flame continu ouslytoensurethattheproperflameappear ance has been achieved see Figure 52 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the...

Page 31: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 32: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 33: ...stallation is not proper and completeuntiltheoperationofthe convertedapplianceischeckedas specifiedintheownerinstructions suppliedwiththekit Thequalified service agency performing this installationass...

Page 34: ...kit is available order Catalog No 87L54 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 61 and the instructions provided with the kit Remove the slotted cap screw o ring pressure...

Page 35: ...nstall the rear burner in the front burner s position BRACKET A BURNER PORTS NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step9 Reassembletheremainingcomponents by reversing the pro...

Page 36: ...o make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP...

Reviews: