Superior SSDVPF-CNE Installation Instructions Manual Download Page 24

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

24

D. Install Firestop / Spacers at ceilings and walls 

When Secure Flex penetrates a wall or ceiling, 

a fi restop / spacer is required: use the SF4.5 VF 
fi restop / spacer for ceilings and the SF4.5 HF 
fi restop / spacer for walls. See the appropriate 
sections and 

Figures 

 shown throughout the vent-

ing section for their installation requirements. 

Note:  Outer Pipe Is Pulled Away To Show 
The Detail of The Inner Pipe

APPLY ONLY MIL-PAC BLACK 
HIGH TEMPERATURE SEALANT 
(Cat. No. 10K81) to the outside 
surface of both collars of the 
adapter (be especially careful to 
fi ll the grooves of the outer collar 
to be covered by the fl exible pipe) 
and slide fl exible pipe over inner 
and outer adapter collars.

1-3/4 inch (44 mm) Flexible 
Pipe and Adapter Outer Collar 
Overlap

Adapter (SV4.5RF)

Attach Adapter to Appliance 

Collar, or Secure Vent Sections

Flex Vent

Gear Clamps

Securing Screw 
- 3 Places, 120° apart 
(equally spaced) Just 
Below Gear Clamp

1-3/4  in. (44 mm) Flexible 
Pipe and Adapter Inner Collar 
Overlap

Securing Screw - 3 Places 
Equidistant (equally spaced) 
Just Below Gear Clamp)

Figure 41

VERTICAL OR HORIZONTAL VENTING USING 

SECURE FLEX

 KITS AND COMPONENTS

Secure Flex

 venting kits and components 

may be used in any venting application in 
place of rigid 

Secure Vent

 (SV4.5) direct vent 

components.  All restrictions, clearances and 
allowances that pertain to the rigid piping apply 
to the fl exible venting.  

Secure Flex

 kits may 

not be modifi ed; also, under no circumstances 
may separate sections of fl ex pipe be joined 
together

Using adapter (SV4.5RF),

 Secure Flex

 kits 

may be added to the end of a vent run made 
up of rigid 

Secure Vent

 (SV4.5) vent sections 

provided that doing so does not violate any of 
the venting length, height, routing, horizontal 
to vertical ratio requirements or clearance 
considerations detailed in this manual.

Secure Flex

 kits come with an adapter that 

can be fi tted to the inclined channel end of the 
last 

Secure Vent

 (SV4.5) vent section in a rigid 

system in the exact same fashion as any other 

Secure Vent 

section.

Align the dimpled end of the adapter over 
the previously installed section or appliance 
collar, adjusting the radial alignment until the 
four locking dimples of the adapter are aligned 
with the inlets of the four incline channels of 
the last vent section or collar.  Push on the 
adapter until it fully engages, then twist the 
adapter clockwise running the dimples down 
and along the incline channels until they seat 
at the end of the channels.

Attach the fl exible vent to the adapter as fol-
lows 

(see also 

Figure 41

)

:

A. Install the Inner Flex Pipe - 

1.

 Install the small  gear clamp loosely around 

the inner fl exible vent pipe, push it back out 
of the way.

2.

  Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 10K81

 

to the inner adapter collar, approximately 
1/2 inch from the end.

3.

 Pull and extend the inner fl exible vent pipe. 

4.

   Slide the inner fl ex pipe over the adapter col-

lar. Ensure the fl exible vent pipe completely 
engages the adapter collar to a distance of 1 
3/4 inches from the end, and that it is free  
from damage or tears. 

5

. Slide the gear clamp down and tighten it 

fully to secure the fl exible vent to the adapter 
inner collar approximately 3/4 inch from the 
end of the fl ex.

6

. Install 

three screws 120 degrees apart

 through 

the fl exible vent pipe and into the adapter collar 
just below the gear clamp to provide additional 
security to the connection.

B. Install the Outer Flex Pipe - 

1.

 Install the large gear clamp loosely around 

the outer fl exible vent pipe, push it back out 
of the way.

 

2.

  Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 10K81)

 

to the outer adapter collar; to the grooves 
of the collar which extend approximately 1 
inch from the end and to the fl at surface, 
approximately 1-3/8 inches from the end. 

3.

 Pull and extend outer fl exible vent pipe. 

4.

  Slide the outer fl ex pipe over the adapter col-

lar. Ensure the fl exible vent pipe completely 
engages the adapter collar to a distance of 
1-3/4 inches from the end, and that it is free 
from damage or tears. 

5

. Slide the gear clamp down and tighten it 

fully to secure the fl exible vent to the adapter 
outer collar approximately 3/4 inch from the 
end of the fl ex.

6.

 Install 

three screws 120 degrees apart

 

through the fl exible vent pipe and into the 
adapter collar just below the gear clamp to 
provide additional security to the connec-
tion.

C. Route Flex Vent - 

  

Ensure that the fl ex vent is properly routed to 
provide the required clearance. 

Do not 

allow the 

fl exible vent to bend in a radius tighter than 5" 
(127 mm). Refer to 

Figure 42

. Space out the 

internal fl ex vent spacers evenly - approximately 
every 6 inches - and avoid kinking of inner pipe. 
Support horizontal sections of fl ex with metal 
straps at 2 foot (0.61 m) intervals. 

E. Attach Flex Vent to Termination -

  

Secure Flex

 components can be purchased 

separately and attached to bulk lengths of 

Se-

cure Flex

 fl exible tubing cut to size at the job 

site.   Secure the fl exible vent to the 

Secure Flex

 

terminations in the same manner (see

 Figure 

41) 

as it was attached to the adapter.

Note:

 

Secure Flex vent must be attached to Secure 

Flex terminations only. DO NOT substitute Secure 
Vent terminations or the Secure Vent adapter for 
Secure Flex components. The collars of Secure 
Flex terminations and adapters have a different 
diameter than that used with the Secure Vent 
pipe.  Additionally, Secure Flex components have 
an extended length center tube for use in attaching 
the fl exible vent.

Flexible Vent 
Section

5” (127 mm)

Radius

Minimum

Figure 42

Summary of Contents for SSDVPF-CNE

Page 1: ...uch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If your gas supplier cannot be reach...

Page 2: ...sted for operation and installation with the following vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter nat...

Page 3: ...H I LO W H T P T H T P T P I L O T P I L O T O N i t OFF IN OUT Manifold Pressure Tap Inlet Pressure Tap SIT Millivolt Gas Valve Pilot Adjustment Screw HI LO Variable Flame Height Adjustment Main Gas...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...mproper installation or use of this appli ance can cause serious injury or deathfromfire burns explosion or carbon monoxide poisoning IMPORTANT These appliances must not be connected to a chimney or f...

Page 6: ...le home where not prohibited by local codes This appliance may be installed as an OEM installation in a manufactured home USA only or mobile home and must be installed in accordance with the manufactu...

Page 7: ...CES These instructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1...

Page 8: ...3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 fee...

Page 9: ...on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air g...

Page 10: ...1 2 3 8 10 40 1 2 1 2 40 100 1 2 1 2 100 150 3 4 1 2 150 200 3 4 1 2 Table 8 Notes All appliances are factory equipped with a flexiblegaslineconnectorand1 2inchshutoff valve see Figure 47 on Page 27 S...

Page 11: ...0 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left S...

Page 12: ...ry installed vent seal cap see Figures 15 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door Left Side View T...

Page 13: ...nal Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Use only approved venting components See Approved Vent Compo nents Page 2 These fireplaces must...

Page 14: ...1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2...

Page 15: ...n installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telesc...

Page 16: ...tions See Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm atal...

Page 17: ...needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run...

Page 18: ...1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet...

Page 19: ...with 8d nails or other ap propriate fasteners at each corner Remembertomaintain1 25mm clearance tocombustibles framingmembers andattic or ceiling insulation when running vertical chimney sections Atti...

Page 20: ...seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal te...

Page 21: ...ionKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 3 4 to 20 299 to...

Page 22: ...Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 11 as an aid in venting component selection for a particular range...

Page 23: ...s Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For ev...

Page 24: ...y around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from th...

Page 25: ...el OFF ON Switch TP TH TH Install OFF ON Switch millivolt models 1 Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve 2 Pass the 2 wires through the opening w...

Page 26: ...h wires CAUTION Remove the carton support from the control compartment before operating the appliance Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 FBK 250 Kit...

Page 27: ...igure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The incoming gas line should be piped into th...

Page 28: ...ce Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the t...

Page 29: ...top louver assembly by lifting it up and pulling it out 2 Remove the control compartment access door see removal instructions on Page 27 Removing Control Compartment Door 3 Locate the two 2 latches at...

Page 30: ...erving the flame continu ouslytoensurethattheproperflameappear ance has been achieved see Figure 52 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the...

Page 31: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 32: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 33: ...stallation is not proper and completeuntiltheoperationofthe convertedapplianceischeckedas specifiedintheownerinstructions suppliedwiththekit Thequalified service agency performing this installationass...

Page 34: ...kit is available order Catalog No 87L54 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 61 and the instructions provided with the kit Remove the slotted cap screw o ring pressure...

Page 35: ...nstall the rear burner in the front burner s position BRACKET A BURNER PORTS NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step9 Reassembletheremainingcomponents by reversing the pro...

Page 36: ...o make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP...

Reviews: