Superior SSDVPF-CNE Installation Instructions Manual Download Page 15

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Blocking

Support Straps
(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4 
mm) minimum 
clearance to 
combustibles

Figure 19

 Figure 21

Another method, where the vent is not adjacent 
to a wall, is illustrated in 

Figure 22

.  Here, 

support straps (96K93) and support plates 
(96K92) can be used to support the weight 
of the vent. 

D.

 

Install fi restop / spacer at ceiling -

 When 

using Secure Vent, use SV4.5VF fi restop / spacer 
at ceiling joists; when using Secure Flex, use 
SF4.5VF fi restop / spacer. If there is living space 
above the ceiling level, the fi restop / spacer must 
be installed on the bottom side of the ceiling. 
If attic space is above the ceiling, the fi restop / 
spacer must be installed on the top side of the 
joist. Route the vent sections through the framed 
opening and secure the fi restop / spacer with 
8d nails or other appropriate fasteners at each 
corner. 

 Remember to maintain 1" (25 mm) 

clearance to combustibles, framing members, 
and attic or ceiling insulation when running ver-
tical chimney sections. Attic insulation shield 
(96K94) may be used to obtain the required 
clearances indicated here. See installation 
accessories o n 

Pages 31 and 32.

E.

 

Support the vertical vent run sections -

Note - 

Proper venting support is very important. 

The weight of the vent must not be supported 
by the fi replace in any degree.

 

Support the vertical portion of the venting 
system every 8 feet (2.4 m) above the fi replace 
vent outlet. One method of support is by utiliz-
ing fi eld provided support straps (conventional 
plumber's tape). Secure the plumber's tape to 
the framing members with nails or screws.
Loop the tape around the vent, securing the 
ends of the tape to the framing.  If desired, 
sheet metal screws #6 x 1/2" length may be 
used to secure the support straps to the vent 
pipe.   See 

Figure 21

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Figure 20

Align the dimple (four places) of the 
upper vent section with the opening 
of the locking incline channel on the 
lower vent section or appliance col-
lar.  Twist vent component clockwise 
to engage and seal until arrow and 
dimple align.

Dimple

Locking Incline 
Channel

Connected Vent 
Sections

Arrow

Arrow

Appliance Collar or 
Vent Section

Vertical (offset) Installation

Analyze the vent routing and determine the 
number of vent sections and elbows required. 
Refer to 

Vertical Vent Figures and Tables

 

on 

Pages 17 and 18

  to select the type of vertical 

installation desired. Refer to the 

Vent Section 

Length Charts 

on

 

Page 14

  for an aid in se-

lecting vent length combinations.  Elbows are 
available in 45° and 90° confi gurations.  Refer 
to 

Figure 23 

for the SV4.5E45 and SV4.5E90 

elbow dimensional specifi cations.   

Where required, a 

Telescopic Vent Section

  

(SV4.5LA)  may be used to provide the installer 
with an option in installing in tight and confi ned 
spaces or where the vent run made up of fi xed 
length pieces develops a joint in a undesirable 
location, or will not build up to the required 
length. The SV4.5LA 

Telescopic Vent Section 

has an effective length of from 1-          1/2" (38 
mm) to 7-1/2" (191 mm). The SV4.5LA  is fi tted 
with a locking inclined channel end (identical to 
a normal vent section component) and a plain 
end with 3 pilot holes. Slip the plain end over the 
locking channel end of a standard  SV4.5 vent 
component the required distance and secure 
with three screws.

Maintain a minimum 1" (25 mm) clearance 
to combustible materials for all vertical 
elements. Clearances for all horizontal ele-
ments are 3" (76 mm) on top, 1" (25 mm) 
on sides and 1" (25 mm) on the bottom.

A.

 

Frame ceiling opening -

 Use a plumb line 

from the ceiling above the appliance to locate 
center of the vertical run. Cut and/or frame an 
opening, 10-1/2" x 10-1/2"  (267 mm x 267 
mm) inside dimensions, about this center mark 

(Figure 19)

.

To attach a vent component to the appliance 
collar, align the dimpled end over the collar, 
adjusting the radial alignment until the four 
locking dimples are aligned with the inlet of 
the four inclined channels on the collar (

refer 

to 

Figure 20

)

.  Push the vent component 

against the collar until it fully engages, then 
twist the component clockwise, running the 
dimples down and along the incline channels 
until they seat at the end of the channels.  The 
unitized design of the 

Secure Vent

 components 

will engage and seal both the inner and outer 
pipe  without the need for sealant or screws.  
If desired a #6 x 1/2" screw may be used at the 
joint, but it not required as the pipe will securely 
lock when twisted.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 
as you would a vent section. 

C. Attach vent components to each other 
-

 Other vent sections may be added to the 

previously installed section in accordance with 
the requirements of the vertical vent Figures 
and Tables.  To add another vent component 
to a length of vent run, align the dimpled end 
over the inclined channel end of the previously 
installed section, adjusting the radial alignment 
until the four locking dimples are aligned with the 
inlets of the four incline channels of the previous 
section.  Push the vent component against the 
previous section until it fully engages, then twist 
the component clockwise running the dimples 
down and along the incline channels until they 
seat at the end of the channels.  

This seating 

position is indicated by the alignment of the 
arrow and dimple as shown in

 

Figure 20.

B.

 

Attach vent components to appliance 

-

 

Secure Vent 

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 
featuring positive twist lock connections (

see 

Figure 20

)

.  All of the appliances covered in this 

document are fi tted with collars having locking 
inclined channels.  The dimpled end  of the vent 
components fi t over the appliance collar to cre-
ate the positive twist lock connection.

Summary of Contents for SSDVPF-CNE

Page 1: ...uch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow your gas suppliers instructions If your gas supplier cannot be reach...

Page 2: ...sted for operation and installation with the following vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter nat...

Page 3: ...H I LO W H T P T H T P T P I L O T P I L O T O N i t OFF IN OUT Manifold Pressure Tap Inlet Pressure Tap SIT Millivolt Gas Valve Pilot Adjustment Screw HI LO Variable Flame Height Adjustment Main Gas...

Page 4: ...zontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The...

Page 5: ...mproper installation or use of this appli ance can cause serious injury or deathfromfire burns explosion or carbon monoxide poisoning IMPORTANT These appliances must not be connected to a chimney or f...

Page 6: ...le home where not prohibited by local codes This appliance may be installed as an OEM installation in a manufactured home USA only or mobile home and must be installed in accordance with the manufactu...

Page 7: ...CES These instructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1...

Page 8: ...3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 fee...

Page 9: ...on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air g...

Page 10: ...1 2 3 8 10 40 1 2 1 2 40 100 1 2 1 2 100 150 3 4 1 2 150 200 3 4 1 2 Table 8 Notes All appliances are factory equipped with a flexiblegaslineconnectorand1 2inchshutoff valve see Figure 47 on Page 27 S...

Page 11: ...0 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Louvered Control Compartment Door Left S...

Page 12: ...ry installed vent seal cap see Figures 15 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louvered Control Compartment Door Left Side View T...

Page 13: ...nal Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Use only approved venting components See Approved Vent Compo nents Page 2 These fireplaces must...

Page 14: ...1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1 2 0 4 5 7 9 5 2 1 8 1 0 0 0 2 3 2...

Page 15: ...n installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telesc...

Page 16: ...tions See Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm atal...

Page 17: ...needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run...

Page 18: ...1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet...

Page 19: ...with 8d nails or other ap propriate fasteners at each corner Remembertomaintain1 25mm clearance tocombustibles framingmembers andattic or ceiling insulation when running vertical chimney sections Atti...

Page 20: ...seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall The horizontal te...

Page 21: ...ionKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 3 4 to 20 299 to...

Page 22: ...Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 11 as an aid in venting component selection for a particular range...

Page 23: ...s Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For ev...

Page 24: ...y around the inner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from th...

Page 25: ...el OFF ON Switch TP TH TH Install OFF ON Switch millivolt models 1 Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve 2 Pass the 2 wires through the opening w...

Page 26: ...h wires CAUTION Remove the carton support from the control compartment before operating the appliance Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 FBK 250 Kit...

Page 27: ...igure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The incoming gas line should be piped into th...

Page 28: ...ce Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the t...

Page 29: ...top louver assembly by lifting it up and pulling it out 2 Remove the control compartment access door see removal instructions on Page 27 Removing Control Compartment Door 3 Locate the two 2 latches at...

Page 30: ...erving the flame continu ouslytoensurethattheproperflameappear ance has been achieved see Figure 52 If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the...

Page 31: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 32: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Page 33: ...stallation is not proper and completeuntiltheoperationofthe convertedapplianceischeckedas specifiedintheownerinstructions suppliedwiththekit Thequalified service agency performing this installationass...

Page 34: ...kit is available order Catalog No 87L54 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 61 and the instructions provided with the kit Remove the slotted cap screw o ring pressure...

Page 35: ...nstall the rear burner in the front burner s position BRACKET A BURNER PORTS NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step9 Reassembletheremainingcomponents by reversing the pro...

Page 36: ...o make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information LHP...

Reviews: