Superior SDDV-35 Installation Instructions Manual Download Page 4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

4

Note:

 The following requirements reference various Massachusetts 

and national codes not contained in this document.

Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every 
dwelling, building or structure used in whole or in part for residential 
purposes, including those owned or operated by the Commonwealth and 
where the side wall exhaust vent termination is less than seven (7) feet 
above fi nished grade in the area of the venting, including but not limited 
to decks and porches, the following requirements shall be satisfi ed: 

Installation Of Carbon Monoxide Detectors 

At the time of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gasfi tter shall observe that a hard 
wired carbon monoxide detector with an alarm and battery back-up is 
installed on the fl oor level where the gas equipment is to be installed. 
In addition, the installing plumber or gasfi tter shall observe that a bat-
tery operated or hard wired carbon monoxide detector with an alarm is 
installed on each additional level of the dwelling, building or structure 
served by the side wall horizontal vented gas fueled equipment. It shall 
be the responsibility of the property owner to secure the services of 
qualifi ed licensed professionals for the installation of hard wired carbon 
monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment 
is installed in a crawl space or an attic, the hard wired carbon monoxide 
detector with alarm and battery back-up may be installed on the next 
adjacent fl oor level.

 In the event that the requirements of this subdivision can not be met at 
the time of completion of installation, the owner shall have a period of 
thirty (30) days to comply with the above requirements; provided, how-
ever, that during said thirty (30) day period, a battery operated carbon 
monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the 
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certifi ed.

Signage

A metal or plastic identifi cation plate shall be permanently mounted to 
the exterior of the building at a minimum height of eight (8) feet above 
grade directly in line with the exhaust vent terminal for the horizontally 
vented gas fueled heating appliance or equipment. The sign shall read, in 
print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

Inspection

The state or local gas inspector of the side wall horizontally vented gas 
fueled equipment shall not approve the installation unless, upon inspection, 
the inspector observes carbon monoxide detectors and signage installed 
in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

•  The equipment listed in Chapter 10 entitled “Equipment Not Required 

To Be Vented” in the most current edition of NFPA 54 as adopted by 
the Board; and

•  Product Approved side wall horizontally vented gas fueled equipment 

installed in a room or structure separate from the dwelling, building 
or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally 
vented gas equipment provides a venting system design or venting sys-
tem components with the equipment, the instructions provided by the 
manufacturer for installation of the equipment and the venting system 
shall include:

•  Detailed instructions for the installation of the venting system design 

or the venting system components; and 

•  A complete parts list for the venting system design or venting sys-

tem.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally 
vented gas fueled equipment does not provide the parts for venting the 
fl ue gases, but identifi es “special venting systems”, the following require-
ments shall be satisfi ed by the manufacturer:

•  The referenced “special venting system” instructions shall be included 

with the appliance or equipment installation instructions; and 

•  The “special venting systems” shall be Product Approved by the 

Board, and the instructions for that system shall include a parts list 
and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall 
horizontally vented gas fueled equipment, all venting instructions, all 
parts lists for venting instructions, and/or all venting design instructions 
shall remain with the appliance or equipment at the completion of the 
installation.

•  Installation and repair must be done by a plumber or gas fi tter licensed 

in the Commonwealth of Massachusetts.

•  The fl exible gas line connector used shall not exceed 36 inches (92 

centimeters) in length.

•  The individual manual shut-off must be a T-handle type valve.

Summary of Contents for SDDV-35

Page 1: ...OUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Page 2: ...mponents are labeledforidentification DONOTuseanyother manufacturer s vent components with these appliances Use only the correct size venting 4 1 2 inner 7 1 2 outer These appliances comply with Natio...

Page 3: ...eld converted Inlet Gas Supply Pressure all models Fuel Minimum Maximum Natural Gas 5 0 WC 1 24 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4...

Page 4: ...rizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection T...

Page 5: ...n SeeMaintenanceinstructionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have the...

Page 6: ...thesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide for the l...

Page 7: ...2 1 2 64 mm or less See Figure 5 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 6 on Page 8 Figure 5 Side Elevation View Note See Figure...

Page 8: ...15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearanc...

Page 9: ...inimum Distance to Unprotected Side Wall Top View of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figu...

Page 10: ...eld Wiring a MillivoltAppliances Theoperatingcontrol switch is factory installed b Electronic Appliances Connect 120 VAC electrical power to the appliance recep tacle Step 5 Page 25 Install blower kit...

Page 11: ...8 1019 37 1 8 943 24 610 34 1 2 876 40 1 8 1019 27 1 2 698 26 1 2 675 13 3 4 337 G H Top View Co Axial Direct Vent Pipe Collars Top Rear Vent Flue Outlet 4 1 2 114 Combustion Air 7 1 2 190 275 FRAMING...

Page 12: ...under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition o...

Page 13: ...ve and discard the vent cover plate Reinstall and securely tighten all four cover plate screws Reinstall the lintel cover plate When the rear vent is being used from inside thefirebox removethetwoscre...

Page 14: ...0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1...

Page 15: ...lectinglengthcombinations Elbows areavailablein90 and45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent sec...

Page 16: ...t the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of...

Page 17: ...WhenusingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When usin...

Page 18: ...048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max Table C H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10...

Page 19: ...ureVent useSV4 5VFfirestop spaceratceilingjoists whenusingSecureFlex use SF4 5VF firestop spacer If there is living spaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of...

Page 20: ...ing of the Horizontal Square Termination SV4 5HT 2 SeeFigure13 onPage 11 for Min Distance to Base of Appliance For thicknesses greater than 10 see Table 12 I Continue installation of horizontal inclin...

Page 21: ...ES H H 28 in 711 mm Maximum 7 in 178 mm When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF H Wall Firestop Spacer SV4 5HF V When using Secure Flex use Firestop Spacer SF4...

Page 22: ...Example If 20 feet of H H1 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 fe...

Page 23: ...e 12 on Page 21 as an aid in venting component selection for a particular range of exte rior wall thicknesses Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum of V verti...

Page 24: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Page 25: ...power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within th...

Page 26: ...BLACK BL BLUE R RED W WHITE G GREEN BK W BK BK BL R GROUND 24 V Transformer View A J Box Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which...

Page 27: ...mpartment access door Removing Control Compartment Door Openthedoorby gentlyliftingitupwarduntilthe hook catches on boths sides clear the locating slots Then pull door out to remove D Turn on burner t...

Page 28: ...ogs have locating notches which cor respond to locating brackets and holes which correspond to locating pins to help ensure that they are properly positioned Proper log placement is critical to preven...

Page 29: ...g Installation Instructions refer to Figure 52 Carefully position the ceramic fiber logs into the firebox as shown here Logs should be placed in the order shown and per the following instructions 1 Se...

Page 30: ...G The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to...

Page 31: ...Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting f...

Page 32: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 33: ...12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Hor...

Page 34: ...ed exactly a fire explosion or produc tion of carbon monoxide may result causing property damage personal injury or loss of life The installation is not proper and complete until the operation of the...

Page 35: ...rtoFigure59 andremovethepilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Pilot for SIT Millivolt Gas Valve Figure 59 Pilot Orific...

Page 36: ...move the orifice from the manifold and replace it with the one provided in the kit See Table 14 for orifice sizes fornaturalandpropanemodels Figure 61 illustrates the orifice b Retrievetheburnerandhol...

Reviews: