Superior SDDV-35 Installation Instructions Manual Download Page 19

19

NOTE: DIAGRAMS & ILLUSTRA-

TIONS ARE NOT TO SCALE.

Horizontal / Inclined Run

Support Brackets

Building

Support

Framing

SV4.5E90

Elbow

Ceiling

Fireplace

SV4.5L6/12/24/36/48

Vent Sections

Vertical

Rise

SV4.5HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

Exterior

Wall

SV4.5HT-2

Termination

Shown

Figure 31

See 

Figure 18 

on 

Page 14

 or 

Figure 21

 on 

Page 15 

 for vertical vent section support.

TYPICAL HORIZONTAL VENT INSTALLATION

 Firestop / Spacer

SV4.5VF

 When Using Secure Flex, 

Use Firestop / Spacer SF4.5VF

B.

 

Frame exterior wall opening -

 

Locate the center of the vent outlet on 
the exterior wall according to the dimen-
sions shown in 

Figure 13 

on 

Page 10.

  Cut 

and/or frame an opening, 10-1/2" x 12-1/8" 
(267 mm x 308mm) inside dimensions, about 
this center. 

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 
the center above the appliance. Cut and/or frame 
an opening, 10-1/2" x 10-1/2" (267 mm x 267 
mm) inside dimensions, about this center (refer 
to 

Figure 19 

on 

Page 15

).

D.

 

Attach vent components to appliance - 

To 

attach a vent component to the appliance collar, 
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking 
dimples are aligned with the inlets of the four 
incline channels on the collar (

refer to Figure 

20

 

on 

Page 15).

Push the vent component against the collar 
until it fully engages, then twist the component 
clockwise, running the dimples down and along 
the incline channels until they seat at the end 
of the channels.

The unitized design of the 

Secure Vent

 

components will engage and seal both the 
inner and outer pipe elements with the same 
procedure.  Sealant and securing screws are 
not required.

Note:

 

An elbow may also be attached to the 

appliance collar.  Attach in the same manner 
as you would a vent section. 

E.

 

Attach vent components to each other -

 Other 

vent sections may be added to the previously in-
stalled section in accordance with the requirements 
of the vent tables.  To add another vent component 
to a length of vent run, align the dimpled end of 
the component over the inclined channel end of 
the previously installed section, 

adjusting the radial alignment until the four lock-
ing dimples are aligned with the inlets of the four 
incline channels of the previous section.  Push 
the vent component against the previous section 
until it fully engages, then twist the component 
clockwise running the dimples down and along 
the incline channels until they seat at the end of 
the channels.

This seating position is indicated 

by the alignment of the arrow and dimple as 
shown in

 

Figure 20 on Page 15.

F.

 

Install fi restop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF fi restop/
spacer at ceiling joists; when using Secure Flex, 
use SF4.5VF fi restop/spacer. If there is living 
space above the ceiling level, the fi restop/ spacer 
must be installed on the bottom side of the 
ceiling. If attic space is above the ceiling, the 
fi restop/ spacer must be installed on the top side 
of the joist. Route the vent sections through the 
framed opening and secure the fi restop/spacer 
with 8d nails or other appropriate fasteners at 
each corner.

Remember to maintain 1" (25 mm) clearance 
to combustibles, framing members, and attic 
or ceiling insulation when running vertical 
chimney sections

.

G.

 

Support the vertical run sections - 

See 

Section E

 on 

Page 15.

H.

 

Change vent direction  -

 At transition from or 

to a horizontal/inclined run, install the SV4.5E45 
and SV4.5E90 elbows in the same manner as 
the straight vent sections.  The elbows feature a 
twist section to allow them to be routed about the 
center axis of their initial collar section to align 
with the required direction of the next vent run 
element. 

Twist elbow sections in a clockwise 

direction only so as to avoid the possiblity of 
unlocking any of the previously connected vent 
sections.

 See 

Figure 22 on Page 16

.

HORIZONTAL (OUTSIDE WALL) 
TERMINATION SYSTEM

Figure 31, and Figures 34 to 40 on Pages 
21 to 23 

and their associated  Horizontal Vent 

Table illustrate the various horizontal venting 
confi gurations that are possible for use with 
these appliances.  

Secure Vent

 pipe applications 

are shown in these Figures; 

Secure Flex

 pipe 

may also be used. A Horizontal Vent Table sum-
marizes each system’s minimum and maximum 
vertical and horizontal length values that can be 
used to design and install the vent components 
in a variety of applications. 

Both of these horizontal vent systems terminate 
through an outside wall. Building Codes limit or 
prohibit terminating in specifi c areas. Refer to 

Figure 6

 

on 

Page 8 

for location guidelines.

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 
featuring positive twist lock connection, (

refer 

to 

Figure 20

 

on 

Page 15)

.  All of the appli-

ances covered in this document are fi tted with 
collars having locking inclined channels. The 
dimpled end of the vent components fi t over 
the appliance collar to create the positive twist 
lock connection.

A.

 

Plan the vent run -

 

Analyze the vent routing and determine the 
types and quantities of sections required 

 

 

 

 

 

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 
mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) 
net section lengths are available.  Plan the vent 
lengths so that a joint does not occur at the inter-
section of ceiling or roof joists. Make allowances 
for elbows as indicated in 

Figure 22

.

Maintain a minimum 1" (25 mm) clearance to 
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm) 
on top, 1" (25 mm) on sides, and 1" (25 mm) 
at the bottom.

Summary of Contents for SDDV-35

Page 1: ...OUR SAFETY What to do if you smell gas DO NOT light any appliance DO NOT touch any electrical switches Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone...

Page 2: ...mponents are labeledforidentification DONOTuseanyother manufacturer s vent components with these appliances Use only the correct size venting 4 1 2 inner 7 1 2 outer These appliances comply with Natio...

Page 3: ...eld converted Inlet Gas Supply Pressure all models Fuel Minimum Maximum Natural Gas 5 0 WC 1 24 kPa 10 5 WC 2 61 kPa Propane 11 0 WC 2 74 kPa 13 0 WC 3 23 kPa Table 4 Gas Pressure All Models Tables 4...

Page 4: ...rizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection T...

Page 5: ...n SeeMaintenanceinstructionsin Homeowner s Manual WARNING Carbon monoxide poisoning early signs of carbon monoxide poisoning are similar to the flu withheadaches dizzinessand or nausea If you have the...

Page 6: ...thesearecommonlyusedforlocat ing television sets and decorative plants Be awarethatthisisaheatproducingappliance Objects placed above the unit are exposed to elevated temperatures To provide for the l...

Page 7: ...2 1 2 64 mm or less See Figure 5 For projections exceeding 2 1 2 64 mm see Figure 6 For additional vent location restrictions refer to Figure 6 on Page 8 Figure 5 Side Elevation View Note See Figure...

Page 8: ...15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearanc...

Page 9: ...inimum Distance to Unprotected Side Wall Top View of Fireplace 45 o At 14 minimum side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figu...

Page 10: ...eld Wiring a MillivoltAppliances Theoperatingcontrol switch is factory installed b Electronic Appliances Connect 120 VAC electrical power to the appliance recep tacle Step 5 Page 25 Install blower kit...

Page 11: ...8 1019 37 1 8 943 24 610 34 1 2 876 40 1 8 1019 27 1 2 698 26 1 2 675 13 3 4 337 G H Top View Co Axial Direct Vent Pipe Collars Top Rear Vent Flue Outlet 4 1 2 114 Combustion Air 7 1 2 190 275 FRAMING...

Page 12: ...under 100 lbs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition o...

Page 13: ...ve and discard the vent cover plate Reinstall and securely tighten all four cover plate screws Reinstall the lintel cover plate When the rear vent is being used from inside thefirebox removethetwoscre...

Page 14: ...0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0 0 0 2 2 6 9 8 1 0 1...

Page 15: ...lectinglengthcombinations Elbows areavailablein90 and45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent sec...

Page 16: ...t the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of...

Page 17: ...WhenusingSecureFlex useFirestop Spacer SF4 5VF Ceiling Firestop Spacer SV4 5VF Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When usin...

Page 18: ...048 2 0 610 15 4 572 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 40 ft 12 192 m Max Table C H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10...

Page 19: ...ureVent useSV4 5VFfirestop spaceratceilingjoists whenusingSecureFlex use SF4 5VF firestop spacer If there is living spaceabovetheceilinglevel thefirestop spacer must be installed on the bottom side of...

Page 20: ...ing of the Horizontal Square Termination SV4 5HT 2 SeeFigure13 onPage 11 for Min Distance to Base of Appliance For thicknesses greater than 10 see Table 12 I Continue installation of horizontal inclin...

Page 21: ...ES H H 28 in 711 mm Maximum 7 in 178 mm When using Secure Flex use Firestop Spacer SF4 5HF Wall Firestop Spacer SV4 5HF H Wall Firestop Spacer SV4 5HF V When using Secure Flex use Firestop Spacer SF4...

Page 22: ...Example If 20 feet of H H1 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 fe...

Page 23: ...e 12 on Page 21 as an aid in venting component selection for a particular range of exte rior wall thicknesses Example If 20 feet total H H1 horizontal vent run is needed then 4 feet minimum of V verti...

Page 24: ...inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free...

Page 25: ...power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within th...

Page 26: ...BLACK BL BLUE R RED W WHITE G GREEN BK W BK BK BL R GROUND 24 V Transformer View A J Box Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which...

Page 27: ...mpartment access door Removing Control Compartment Door Openthedoorby gentlyliftingitupwarduntilthe hook catches on boths sides clear the locating slots Then pull door out to remove D Turn on burner t...

Page 28: ...ogs have locating notches which cor respond to locating brackets and holes which correspond to locating pins to help ensure that they are properly positioned Proper log placement is critical to preven...

Page 29: ...g Installation Instructions refer to Figure 52 Carefully position the ceramic fiber logs into the firebox as shown here Logs should be placed in the order shown and per the following instructions 1 Se...

Page 30: ...G The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to...

Page 31: ...Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting f...

Page 32: ...77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 INSTALLATION ACCESSORIES The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashi...

Page 33: ...12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Hor...

Page 34: ...ed exactly a fire explosion or produc tion of carbon monoxide may result causing property damage personal injury or loss of life The installation is not proper and complete until the operation of the...

Page 35: ...rtoFigure59 andremovethepilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Pilot for SIT Millivolt Gas Valve Figure 59 Pilot Orific...

Page 36: ...move the orifice from the manifold and replace it with the one provided in the kit See Table 14 for orifice sizes fornaturalandpropanemodels Figure 61 illustrates the orifice b Retrievetheburnerandhol...

Reviews: