Superior BBV-36REN Installation Instructions Manual Download Page 7

7

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 12

CAUTION: DO NOT CONNECT THE WALL
SWITCH TO A 120V POWER SUPPLY.

Step 5. Field Wiring – Refer to Section A for
millivolt appliances and Section B for electronic
appliances.

A. Millivolt Wiring – Units may be fitted at the
factory with either a Honeywell millivolt gas
control valve or an SIT millivolt gas control
valve.  Both valves have been tested with and
approved for use with these appliances and
are listed accordingly.  Refer to 

Figure 11 for

wiring of Honeywell systems and 

Figure 12

for wiring of SIT systems.

The gas valve has been set in place and has been
pre-wired at the factory. No additional wiring is
required unless the optional wall switch or op-
tional remote control kit is to be installed. Locate
the optional wall switch or optional remote con-
trol in the desired location and connect the
millivolt wire 

(see Figures 11 and 12 ).

Note: Optional wall switch not supplied. If the
optional wall switch is not installed, the ends of
the 15' coiled wire must be connected with a wire
nut (not supplied) for the appliance to operate.

Figure 13

Figure 11

Figure 14

Step 6. Connecting Gas Line – Make gas line
connections. All codes require a shut-off valve
mounted in the supply line. 

Figure 16  illus-

trates two methods for connecting the gas
supply. The flex-line method is acceptable in
the U.S., however, Canadian requirements
vary depending on locality. Installation must
be in compliance with local codes.

A. Mix a 50% dish soap, 50% water solution.

B. Light the appliance (refer to the lighting
instructions provided in the Homeowner's Care
and Operation Instructions).

C. Brush all joints and connections with the
soapy water solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” position.
Either tighten or refasten the leaking connec-
tion and retest as described above.

D. When the gas lines are tested and leak free,
observe the individual tongues of flame on the
burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.

Step 7. Installing Outside Air Kit – These
appliances are equipped with an outside (make-
up) air door and integral actuator arm. If the
appliance is to be installed with an outside air
vent system, use only Lennox Models FAOK-4
or FAOK-4LD Combustion Air Kits.

After completing the installation of the optional
combustion air vent system the actuator arm
must be put in service and tested to ensure
proper operation before completing any enclo-
sure around the firebox. Failure to do so may
result in extensive and costly rework.

The gas control valve is located in the lower
control compartment. To access the valve  re-
move the refractory access panel and set aside
(Figure 14 ).  The millivolt control valve has a 

³⁄₈

"

(10 mm) NPT thread inlet port. The electronic
control valve has a 

¹⁄₂

" (13 mm) NPT thread inlet

port and is fitted with a 

¹⁄₂

" x 

³⁄₈

" (13 mm x 10 mm)

NPT fitting. Both the millivolt and electronic
models are fitted with a 3" (76 mm) long nipple,

³⁄₈

" NPT. Plan the connections accordingly.

Secure all joints tightly using appropriate tools
and sealing compounds (ensure propane resis-
tant compounds are used in propane applica-
tions). Turn on gas supply and test for gas leaks
using a soapy water solution. Never use an
open flame to check for leaks.

B. Electronic Wiring – The electronic appliance
must be connected to the main power supply.
To install:
1. Route a 3-wire 120V 60Hz power supply to
the appliance junction box and ground. 

(See

Figures 13 and 15 ).
2. 
 Locate and install a low voltage (24V) wall
switch (not supplied) in the desired location.
Connect the low voltage wire to this switch 

(see

Figure 13 ).
3. After wiring is complete, replace the appli-
ance junction box cover and secure with the hex
head screws previously removed.

IMPORTANT: Ground lead must be connected
to the green screw located on the outlet box.
See 

Figure 13 . Failure to do so will result in

a potential safety hazard. The appliance must
be electrically grounded in accordance with
local codes or, in the absence of local codes,
the National Electrical Code, ANSI/NFPA 70-
(latest edition). (In Canada, the current CSA
C22-1 Canadian Electrical Code.)

Refractory

Access Panel

SIT Valve

Shown

1. If any of the original wire as supplied must be replaced,

1.  

it must be replaced with

 

Type AWM 200

°

C – 18 GA. wire.

2. 120V, 60Hz – Less than 3 amps.

BK

Junction Box

Transf.

120 V.

24 V

Factory Wired

Field Wired

BL

Electronic Wiring Diagram (Honeywell)

(Optional ON/OFF Switch Wiring)

R

BK

BL

To Opposite Side

OPT
FAN

G

W

OPT. ACCESSORY

SWITCH

120

 VAC.

BK

LIMIT

SWITCH

W

Gas Valve

B

BL

OPTIONAL

ON/OFF SWITCH

OR

WALL SWITCH

R

R

IGNITER

CONTROL

PILOT

ASSEMBLY

Break

Off Tab

DAMPER

SWITCH

BK

BK

WHT

BK

BK

SIT Millivolt Wiring Diagram

* For Wall Switch Attachment Only.

If any of the original wire as supplied must be replaced, it
must be replaced with

 

Type AWM 200

°

C – 18 GA. wire.

Thermopile

TH

TP

TH

TP

Limit
Switch

Damper Switch

BK

BK

BK

BK

WHT

*

Thermopile

Damper

Switch

TH

TP

TH

TP

Honeywell Millivolt Wiring Diagram

If any of the original wire as supplied must be replaced, it
must be replaced with

 

Type AWM 200

°

C – 18 GA. wire.

TH

TPTH

TP

* For Wall Switch Attachment Only.

*

Limit

Switch

BK

WHT

BK

BK

BK

Summary of Contents for BBV-36REN

Page 1: ...S CURIT Nepasentreposerniutiliser d essencenid autrevapeursouliquidesinflammables dans le voisinage de cet appareil ou de tout autre appareil POUR VOTRE S CURIT Que faire si vous sentez une odeur de g...

Page 2: ...mperative that the control compartment burners and circulating airpassagewaysoftheappliancebekeptclean S assurerquelebr leuretlecompartimentdes commandes sont propres Voir les instruc tions d installa...

Page 3: ...r vent system routing to the exterior and access to the fuel supply are also important Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Con...

Page 4: ...t appliances provided that there is at least 2 ft 0 6m between the proximal edges of the vent caps These appliances may be vented adjacent to a chimney vent servicing a solid fuel fireplace provided t...

Page 5: ...ENCE The typical sequence of installation follows however eachinstallationisuniqueresultingin variations to those described 1 Construct the appliance framing 2 Route gas supply line to appliance locat...

Page 6: ...d specifications on pages 4 and 5 for framing dimensions and details Framing header may be positioned di rectly on the fireplace top spacers Step 4 Install the Vent System and Exterior Termination A C...

Page 7: ...ensure proper operation before completing any enclo sure around the firebox Failure to do so may result in extensive and costly rework The gas control valve is located in the lower control compartment...

Page 8: ...hen push the end of the actuators to the right until the step in the actuator moves behind the appliance front face within the slotted opening Operate the actuator through several cycles including the...

Page 9: ...for the line to purge itself of air Once purging is complete the pilot and burner will light and operate as indicated in the in struction manual Subsequent lightings of the appliance will not require...

Page 10: ...ombustible mantel shelf projecting a maximum of 12 305 mm from the wall and which must be installed a minimum distance of 14 368 mm from the top of the firebox opening Orifice Air Shutter Burner Tube...

Page 11: ...r the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Figure 24 64 1626 mm Min to Ceiling 14 Min...

Page 12: ...e available to adapt your appliance from the use of one type of gas to the use of another These kits contain all the neces sary components needed to complete the task including labeling that must be a...

Page 13: ...ner clip andcarefullyremovetheignitorassembly Exercise extreme care to prevent damage to or breakage of the ignitor assembly Remove the screw securing the pilot assembly to its mounting bracket Back o...

Page 14: ...14 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE...

Page 15: ...15 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE...

Page 16: ...00 000M REV H 07 2004 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consul...

Reviews: