3
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
Ne pas se servir de cet appareil s'il a été plongé
dans l'eau, complètement ou en partie. Appeler
un technicien qualifié pour inspecter l'appareil et
remplacer toute partie du système de contrôle et
toute commande qui ont été plongés dans l'leau.
Test gage connections are provided on the
front of the millivolt gas control valve (identi-
fied OUT for the manifold side and IN for inlet
pressure. A
¹⁄₈
" NPT test gage connection is
provided on the electronic gas control valve
adjacent to the outlet to the main burner.
Minimum inlet gas pressure to these appliances
is 5.0 inches water column (1.24 kPa) for natural
gas and 11 inches water column (2.74 kPa) for
propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to these appli-
ances is 10.5 inches water column (2.61 kPa) for
natural gas and 13.0 inches water column (3.23
kPa) for propane.
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning are similar to
the flu with headaches, dizziness and/or
nausea. If you have these signs, obtain
fresh air immediately. Turn off the gas
supply to the appliance and have it ser-
viced by a qualified professional, as it may
not be operating correctly.
Gas Controls/Control Compartment
Access
The gas controls can be found behind the
control compartment access panel. To open
the control compartment access panel, actuate
the spring loaded magnetic catches securing
the panel. First, gently depress the upper right
top corner of the panel until the magnet catch
"pops" the door free. Then, gently pulling the
panel forward, disengage the left magnet catch
and allow the panel to swing down to open.
Operation of millivolt and electronic gas control
systems are different. Before lighting and op-
erating your appliance determine if you have a
millivolt or electronic appliance. See
Figure 1
for access to the control compartment.
Millivolt appliances will be fitted with the gas
control valve shown in
Figure 3 (SIT) or Figure
4 (Honeywell) on page 4
.
Appliances with electronic systems will be fit-
ted with the electronic valve shown in
Figure 2
on page 4.
Familiarize yourself with the gas control valve
that your appliance uses.
Millivolt Appliances -
To light millivolt appliances refer to the detailed
lighting instructions found on
page 13 (
En-
glish
) and page 14
(French).
Millivolt appli-
ance lighting instructions may also be found
on the pull-out lighting instruction labels at-
tached to the gas control valve
. Refer to
Figure 3 (SIT), 4 (Honeywell) on page 4
for
the location of the piezo ignitor.
Millivolt appliances may be fitted with an op-
tional burner ON/OFF Rocker Switch. The op-
tional ON/OFF Rocker switch will be installed in
the bracket just beneath the gas control valve.
Once the pilot is lit, the ON/OFF rocker switch
will control the appliance ON/OFF operation. To
operate: Toggle the switch between its ON and
OFF positions.
OPERATION AND CARE OF YOUR
APPLIANCE
Appliance operation may be controlled through
a remotely located optional wall switch. Sepa-
rate switches may provide independent control
for the remote controlled fireplace operation
(optional equipment).
In lieu of remote or remote wall switch opera-
tion, the appliance must be operated directly
through the controls located on the front of the
valve located within the control compartment
which is located behind the control compart-
ment access panel below the appliance front
glass enclosure panel. See
Figure 1.
WARNING: DO NOT PLACE CLOTH-
ING OR OTHER FLAMMABLE MATERI-
ALS ON OR NEAR THIS APPLIANCE.
AVERTISSEMENT: SURVEILLER LES
ENFANTS. GARDER LES VÊTEMENTS,
LES MEUBLES, L'ESSENCE OU AUTRES
LIQUIDES À VAPEUR INFLAMMABLES
LOIN DE L'APPAREIL.
WARNING: CHILDREN AND ADULTS
SHOULD BE ALERTED TO THE HAZ-
ARDS OF HIGH SURFACE TEMPERA-
TURES. USE CAUTION AROUND THE
APPLIANCE TO AVOID BURNS OR
CLOTHING IGNITION. YOUNG CHIL-
DREN SHOULD BE CAREFULLY SUPER-
VISED WHEN THEY ARE IN THE SAME
ROOM AS THE APPLIANCE.
The appliance must be isolated from the gas
supply piping system (by closing its individual
manual shut-off valve) during any pressure test-
ing of the gas supply piping system at test
pressures equal to or less than
¹⁄₂
psig (3.5 kPa).
The appliance and its individual shut-off valve must
be disconnected from the gas supply piping system
during any pressure testing of that system at pres-
sures in excess of
¹⁄₂
psig (3.5 kPa).
These appliances must not be connected to a
chimney or flue serving a separate solid fuel
burning appliance.
Any safety guard or screen removed for ser-
vicing the appliance must be replaced prior to
operating the appliance.
WARNING: FAILURE TO COMPLY
WITH THE INSTALLATION AND OPER-
ATING INSTRUCTIONS PROVIDED IN
THIS DOCUMENT WILL RESULT IN AN
IMPROPERLY INSTALLED AND OP-
ERATING APPLIANCE, VOIDING ITS
WARRANTY. ANY CHANGE TO THIS
APPLIANCE AND/OR ITS OPERATING
CONTROLS IS DANGEROUS. IM-
PROPER INSTALLATION OR USE OF
THIS APPLIANCE CAN CAUSE SERI-
OUS INJURY OR DEATH FROM FIRE,
BURNS, EXPLOSION OR CARBON
MONOXIDE POISONING.
Figure 1
Control Compartment Access -
Millivolt Control Valve Shown
WARNING: B-VENT APPLIANCES ARE
NOT DESIGNED TO OPERATE IN NEGA-
TIVELY PRESSURED ENVIRONMENTS
(PRESSURE WITHIN THE HOME IS LESS
THAN PRESSURES OUTSIDE). SIGNIFI-
CANT NEGATIVELY PRESSURED ENVI-
RONMENTS CAUSED BY WEATHER,
HOME DESIGN, OR OTHER DEVICES MAY
IMPACT THE OPERATION OF THESE AP-
PLIANCES. NEGATIVE PRESSURES MAY
RESULT IN POOR FLAME APPEARANCE,
SOOTING, DAMAGE TO PROPERTY AND/
OR SEVERE PERSONAL INJURY. DO NOT
OPERATE THESE APPLIANCES IN NEGA-
TIVELY PRESSURED ENVIRONMENTS.
PROVIDING ADEQUATE VENTILATION
TO THE APPIANCE FOR COMBUSTION
AIR WILL ELIMINATE A NEGATIVE PRES-
SURE ENVIRONMENT.
Piezo Ignitor
Honeywell
Millivolt
Gas Valve
Shown
Control
Compartment
Access Panel
f i r e - p a r t s . c o m