INSTALLATION 

Continued

Figure 10 - External Regulator on Propane/LP Supply Tank with 

Vent Pointing Down 

External 

Regulator 

Vent 

Pointing 

Down 

Propane/LP 

Supply Tank 

Installation must include an equipment shutoff valve, union and 

plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge 

hook up. NPT tap must be upstream from fireplace 

(see

 Figure 10

).

IMPORTANT:

 Install equipment shutoff valve in an accessible loca-

tion. The equipment shutoff valve is for turning on or shutting off 

the gas to the appliance.
Check your building codes for any special requirements for locating 

equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent 

excess sealant from going into pipe. Excess sealant in pipe could 

result in clogged fireplace valves. Never use sealant on flare threads.

 WARNING: Use pipe joint sealant that is resistant 

to liquid petroleum (LP) gas. 

We recommend that you install a sediment trap in supply line as 

shown in

 Figure 11

. Locate sediment trap where it is within reach for 

cleaning. Install in piping system between fuel supply and fireplace. 

Locate sediment trap where trapped matter is not likely to freeze. A 

sediment trap traps moisture and contaminants. This keeps them 

from going into fireplace gas controls. If sediment trap is not installed 

or is installed wrong, fireplace may not run properly.

Figure 11 - Gas Connection

* Purchase the optional equipment shutoff valve from your dealer.
** Minimum inlet pressure for purpose of input adjustment.

Sediment Trap

3" Minimum

Cap Pipe Tee

 

 Nipple   Joint

Equipment Shutoff Valve 

With 1/8" NPT Tap*

Natural Gas

From Gas Meter 

(5" W.C.** to 10.5" 

W.C. Pressure)

Propane/LP 

From External 

Regulator 

(11" W.C.** to 14" 

W.C. Pressure)

CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed

•  5/16" hex socket wrench or nut-driver
•  sealant (resistant to propane/LP gas, not provided)
1.  Route flexible gas line (provided by installer) from equipment 

shutoff valve to fireplace. Route flexible gas supply line through 

one of the access holes on side of fireplace.

2.  Attach flexible gas line from gas supply to control valve 

(see 

Figure 12

).

3.  Check all gas connections for leaks. See Checking Gas Connec-

tions, 

Page 13

.

Figure 12 - Connecting Incoming Gas Line to Flex Gas Line

NOTE:

1) Wire connections not shown for clarity

2) * 1/8" NPT Plugged Tapping

MAIN

IN

OUT

PILOT

ADJ

PILOT

Inlet Pressure Tap

Outlet Pressure Tap

Gas Shutoff Valve

Flexible Gas Line Do 

NOT Kink

1/2" NPT Incoming Gas Line

Set Screw

Summary of Contents for VRL4543

Page 1: ...installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on Page 7 of this manual WARNING If the information in this manua...

Page 2: ...trying to assemble operate or ser vicethisheater Improperuseofthisheatercancause serious injury or death from burns fire explosion electrical shock and carbon monoxide poisoning Aftermarket Completion...

Page 3: ...bustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Fireplaces become very hot when running firepla...

Page 4: ...off If heated the vapors from these prod ucts may create a white powder residue within burner box or on adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This...

Page 5: ...a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a...

Page 6: ...te of a structure is known the Known Air Infiltration Rate Method may be used Follow The National Fuel Gas Code ANSI Z223 1 NFPA 54 to use this method to determine if the space is confined or unconfin...

Page 7: ...ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors C Install a lower Btu Hr fireplace if lower Btu Hr siz...

Page 8: ...ealer where you bought fireplace for proper type fireplace WARNING This appliance is equipped for either natural gas or propane LP gas but not both Gas type is indicated on the rating plate Field conv...

Page 9: ...16 5 2 E 14 A B C D E 1 2 3 4 5 Wall Supplied firebox hood must be used at all times Note All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf Noncombustible mat...

Page 10: ...7 1 2 29 5 8 29 5 8 16 3 8 7 1 8 1 7 8 8 1 4 44 1 8 1 1 55 1 8 52 47 16 1 2 11 3 4 8 1 4 5 8 INSTALLATION Continued Figure 8 VRL4543 Series Dimensions Electrical Outlet Gas Line Access Gas Line Access...

Page 11: ...e LP gas equipment shutoff valve test gauge connection sediment trap optional tee joint pipe wrench approved flexible gas line with gas connector if allowed by local codes not provided An equipment sh...

Page 12: ...diment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap is not installed or is...

Page 13: ...he gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its eq...

Page 14: ...a guide screw the rear panel to the fireplace as shown in Figure 16 INSTALLING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 17 2 Tighten screws securing...

Page 15: ...ont of the fireplace unscrew 4 corner brackets from the firebox top See Figure 21 2 Remove 2 side walls and then the rear wall Discard rear wall 3 Replace 2 side walls and reinstall the corner bracket...

Page 16: ...ner shuts OFF Figure 26 Gas Module Right Side Figure 27 Gas Module Left Side Remote Control Feature The module has a built in remote control receiver that allows the user to program the remote transmi...

Page 17: ...supplied with the unit into the battery compart ment It is recommended that ALKALINE batteries always be used for this product Be sure the batteries are installed with the and ends facing the correct...

Page 18: ...tory default or degrees C Press the UP and DOWN Buttons simultaneously to change between degrees F and C SET TEMP While in THERMOSTAT mode press the UP or DOWN Button to change the SET TEMP 45 90 deg...

Page 19: ...Flame A setting number will flash in the FLAME Zone REMOTE CONTROL OPERATION Continued LIGHT ADJUSTMENT Transmits a light setting command to the control module to adjust the light output level Availa...

Page 20: ...rt of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS This appliance requires 120V electricity for normal operation Control module should be plugged into electr...

Page 21: ...ave heater inspected yearly by a qualified service person We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using com...

Page 22: ...the fireplace running Some burner flame holes may become blocked by debris or rust with no flame present If so turn off fireplace and let cool Remove blockage Blocked burner flame holes will create so...

Page 23: ...ot Main HI LO DC Motor Drive Light Module Black Black Brown Red Orange Orange To Ground Igniter Sensor PILOT BATTERY PACK WIRING DIAGRAM Black Blk White SIZE AA SIZE AA SIZE AA SIZE AA Blk Brown Yello...

Page 24: ...ontact local propane LP gas company 3 Clean ODS pilot see Cleaning and Main tenance Page 21 or replace ODS pilot assembly 4 Replace gas regulator 1 Contact local natural or propane LP gas company 2 Cl...

Page 25: ...cting while cooling 1 Burner orifice is clogged or damaged 2 Damaged burner REMEDY 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance Page 21 1 Refer to Air for Com...

Page 26: ...LP only 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Control valve or gas co...

Page 27: ...4 15 16 17 18 19 20 24 21 5 22 23 6 2 1 13 10 9 12 Cat No Description F1186 VRL4543ZEN F1187 VRL4543ZEP WARNING Failure to position the parts in accordance with these diagrams or failure to use only p...

Page 28: ...tery Backup 1 20 J6205 Battery Backup 1 21 J6833 Connector 3 8 Tube x 3 8 MPT 1 22 J8033 Valve NG 1 J8040 Valve LP 1 23 J7939 Control Module Skytech AF4000MOD 1 24 J6868 Switch Rocker ON OFF Remote 1...

Page 29: ...S VRL4543ZEN VRL4543ZEP 1 4 6 2 8 9 7 5 3 5 11 12 13 14 10 7 8 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heat...

Page 30: ...essory part kit s can result in poor performance and safety hazards CAT NO MODEL DESCRIPTION KIT LINEAR DECORATIVE SURROUND KITS Not Shown F4216 DS BLK 43 Decorative Surround for 43 Linear Fireplace B...

Page 31: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Page 32: ...your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products P N 126861 01 Rev P 01 2020 1769 East Lawrence Street Russellville AL 35654 SuperiorFireplaces us...

Reviews: