SuperiorFireplaces.us.com
900467-01B
5
LOG SIZING REQUIREMENTS*
Log
Size
Minimum Firebox Size
Height
Depth Front
Width
Rear
Width
LMF30MOA/B
29"
15.5"
39"
26.75"
LMF36MOA/B
29''
20''
47''
33''
LMF30GTA/B
29''
15.5''
39''
26.75''
LMF36GTA/B
29''
20''
47''
33''
Carefully follow the instructions below. This will ensure safe
installation into a masonry, UL127-listed manufactured fire
-
place or listed outdoor firebox.
Minimum Clearances For Side Combustible Material,
Side Wall and Ceiling
A. Clearances from the side of the fireplace cabinet to any
combustible material and wall should follow diagram in
Figure 2
.
Example
:
The face of a mantel, bookshelf, etc. is made of
combustible material and protrudes 3-1/2" from the wall.
This combustible material must be 4" from the side of the
fireplace cabinet
(see
Figure 2
).
NOTE
: When installing your gas logs into a manufactured
firebox, follow firebox manufacturer’s instructions for mini
-
mum clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceil
-
ing should not be less than 42".
INSTALLATION
Continued
Figure 2 - Minimum Clearance for Combustible to Wall
*Minimum 16" from Side Wall
*
Example
If Using Mantel
You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble,
tile, etc.) must be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it. Noncombus-
tible material must extend at least 8" up (for all models). If
noncombustible material is less than 12", you must install the
fireplace hood accessory. Even if noncombustible material is
more than 12", you may need the hood accessory to deflect
heat away from your mantel shelf. See
Figure 3 and Figures
4 and 5, Page 6
, for minimum clearances.
IMPORTANT
:
If you cannot meet these minimum clearances,
you must operate appliance with chimney flue damper open.
Go to
Installing Damper Clamp Accessory for Vented Opera-
tion
,
Page 7
.
Heat Resistant
Material
(A)
Figure 3 - Heat Resistant Material (Slate, Marble, Tile,
etc.) Above Fireplace
Noncombustible
Material Distance
(A)
Requirements for Safe Installation
12" or more
Noncombustible material OK.
Between 8" and 12"
Install fireplace hood accessory
(GA6050 - see
Accessories
,
Page 23
).
Less than 8"
Noncombustible material must be ex-
tended to at least 8". See
Between 8"
and 12"
, above. If you cannot extend
material, you must operate appliance
with flue damper open.
MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE
MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
Minimum Noncombustible Material Clearances
If Not Using Mantel
NOTE
: If using a mantel proceed to If Using Mantel. If not
using a mantel, follow these instructions
.
You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile,
etc.) must be at least 1/2" thick. With sheet metal, you must
have noncombustible material behind it. Noncombustible
material must extend at least 8" up (for all models). If noncom-
bustible material is less than 12", you must install the fireplace
hood accessory. See
Figure 3
for minimum clearances.
* When optional MFEB (MAGNIFLAME EMBER BURNER KIT) is
used with these burner systems, the minimum firebox sizes are
different. See MFEB instructions for minimum firebox sizes if this
accessory is used.
f i r e - p a r t s . c o m