Alarm circuit contacts provided with the Frequency Trip 
Meter,  Input  Voltage  Range  Alarm  and  Phase  Loss  - 
Phase Reversal options are rated 5 amps 240 volts AC. 
 

6.2.8. 

Manual Raise / Lower Switches

 (A1-S2 & 

A2-S3) 

Manual  raise  / lower  switches  allow  the  user to  disable 
the  automatic  control  unit  and  manually  raise  or  lower 
the output voltage using the motor drive.  The man/auto 
switch  must  be  in  the  manual  position  for  the 
raise/lower switch to operate.  
 

6.2.9. 

Soft Start 

The  soft  start  option  controls  the  WHR  Series  Voltage 
Regulator so that when power is applied the regulator’s 
output  voltage  starts  out  approximately  10%  low  and 
after a preset time delay, the output voltage ramps up to 
the selected regulated output voltage.  
 
When  input  power  is  lost,  the  soft  start  controls 
automatically drives the POWERSTAT power module(s) 
to the minimum output voltage position using the output 
power from a small uninterruptible power supply (UPS). 
The  UPS  then  turns  off  automatically.  For  UPS  care 
and maintenance see the UPS manual. 
 
When  regulator  power  is  restored,  the  load voltage  will 
be  approximately  7%  less  than  the  input  voltage  on 
narrow  range  WHR  Regulators  and  13%  less  than  the 
input voltage  on  wide  range  models.  After  a  short  time 
delay,  the  regulator  output  voltage  ramps  up  to  the 
selected, regulated output voltage. 
 

6.3.  ALL-BUCK AND ALL-BOOST OPERATION 

All WHR Series regulators can be connected to provide 
all-buck  (unit  will  only  lower  the  input  voltage)  or 
all-boost  (unit  will  only  increase  the  input  voltage) 
operation. This feature can be used to shift the nominal 
voltage  or  to  correct  input  voltages  that  are  always 
extremely high or extremely low. 
 

6.3.1. 

4.4.1 All-Boost Operation 

When  connected for  all-boost,  the  units  will  bring  extra 
low  voltages  up  to  nominal,  but  will  not  correct  high 
input  voltages.  Since  operation  in  the  all-boost  mode 
will  increase  the  voltage  and  heating  in  the  WHR 
regulator, the rated load current, and in some cases the 
maximum  rated  nominal  input  voltage,  must  be 
reduced.  Refer  to  the  “All  Buck  and  All  Boost  Rating 
Chart”  for  the  all-boost  ratings.  For  all-boost  operation 
the  input  line  to  each  POWERSTAT  variable 
transformer must  be moved from terminal  2 to terminal 
5. 
 

6.3.2. 

4.4.2 All-Buck Operation 

When  connected  for  all-buck  operation,  the  units  will 
bring extra high input voltages down to nominal, but will 
not  correct low  input voltages.  Since  all-buck  operation 
reduces  the  voltage  in  the  regulator,  the  nominal  input 
voltage  can  be  increased.  The  current  ratings  remain 
the  same.  Refer  to  the  “All  Buck  and  All  Boost  Rating 
Chart”  for  all-buck  ratings.  All-buck  operation  requires 
moving  the  input  line  to  each  POWERSTAT  Variable 
Transformer from terminal 2 to terminal 4. 
 
 

 

 

All Buck and All Boost Rating Chart 

Standard Rating 

All Buck Operation 

All Boost Operation 

(max output voltage = input voltage) 

(min output voltage = input voltage) 

 

 

Maximum Nominal 

Input Voltage 

§ 

Minimum 

Output 

Voltage 

(% of 

Input) 

† High 

Input 

Voltage 

Range 

(% of 

Output) 

Maximum Nominal 

Input Voltage 

§ 

Maximu

m Output 

Voltage 

(% of 

Input) 

‡ Low 

Input 

Voltage 

Range 

(% of 

Output) 

Current 

De-rating 

(% of 

rated) 

Voltage 

Range 

50 Hz 

60 Hz 

50 Hz 

60 Hz 

208 X 240 

Narrow 

240 

270 

80% 

125% 

173 

208 

125% 

75% 

77% 

Wide 

260 

300 

67% 

150% 

173 

208 

150% 

65% 

72% 

 

 

 

 

 

 

 

 

 

 

 

§ Selectable output voltage is a function of the control module and must remain within the limits specified in the unit rating charts. 

† In all buck operation the input voltage range is from the selected output voltage to the 'high input voltage range'. 

‡ In all boost operation the input voltage range is from the 'low input voltage range' to the selected output voltage. 

 

 
 

 

Summary of Contents for STABILINE WHR32 Series

Page 1: ...owing WHR62 T WHR92 T WHRS32 T WHRS62 T or WHRS92 T Superior Electric reserves the right to make engineering changes on all its products Such refinements may affect information given in the instructio...

Page 2: ...2...

Page 3: ...nd Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL WHR32 T Series STABILINE Automatic Voltage Regulators are...

Page 4: ...S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit Brea...

Page 5: ...ange of knockouts are provided in the base and the rear panel of the unit for wire entry and exit The location of the power connections varies depending on the options provided On units with an input...

Page 6: ...SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial oper...

Page 7: ...are wired to trip the input breaker The Shunt Trip Connections Diagram shows the typical connections 6 2 1 2 Under Voltage Trip L1 In unit where the model number designates the circuit breaker as CR...

Page 8: ...g without storing them in memory If the user changed the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The...

Page 9: ...onnected for all boost the units will bring extra low voltages up to nominal but will not correct high input voltages Since operation in the all boost mode will increase the voltage and heating in the...

Page 10: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 11: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 12: ...50 2700 INPUT VOLTAGE 208Y 120 X 240Y 138 FREQUENCY 50 60 Hz X 60 Hz CONNECTION 3 Phase 4 Wire Wye RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 208Y 120 X 240Y 138 CONNECTION 3 Phase 3 or 4 Wire M...

Page 13: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 14: ...1 227412 001 SM A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICATOR GREEN 227571 001 A1 M1 VOLTMETER 212917 004 A1 S1 SWITCH ROCKER SPST ON ON 227572 002 10 3 POWER COMPONENTS The following...

Page 15: ...r details The replacement brush assembly is listed along with its corresponding POWERSTAT Variable Transformer in the power component section 10 5 AUX POWER MODULE There are two standard power modules...

Page 16: ...16 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 17: ...17 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 25: ...25 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 26: ...offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available t...

Reviews: