9
Alarm circuit contacts provided with the Frequency Trip
Meter, Input Voltage Range Alarm and Phase Loss -
Phase Reversal options are rated 5 amps 240 volts AC.
6.2.8.
Manual Raise / Lower Switches
(A1-S2 &
A2-S3)
Manual raise / lower switches allow the user to disable
the automatic control unit and manually raise or lower
the output voltage using the motor drive. The man/auto
switch must be in the manual position for the
raise/lower switch to operate.
6.2.9.
Soft Start
The soft start option controls the WHR Series Voltage
Regulator so that when power is applied the regulator’s
output voltage starts out approximately 10% low and
after a preset time delay, the output voltage ramps up to
the selected regulated output voltage.
When input power is lost, the soft start controls
automatically drives the POWERSTAT power module(s)
to the minimum output voltage position using the output
power from a small uninterruptible power supply (UPS).
The UPS then turns off automatically. For UPS care
and maintenance see the UPS manual.
When regulator power is restored, the load voltage will
be approximately 7% less than the input voltage on
narrow range WHR Regulators and 13% less than the
input voltage on wide range models. After a short time
delay, the regulator output voltage ramps up to the
selected, regulated output voltage.
6.3. ALL-BUCK AND ALL-BOOST OPERATION
All WHR Series regulators can be connected to provide
all-buck (unit will only lower the input voltage) or
all-boost (unit will only increase the input voltage)
operation. This feature can be used to shift the nominal
voltage or to correct input voltages that are always
extremely high or extremely low.
6.3.1.
4.4.1 All-Boost Operation
When connected for all-boost, the units will bring extra
low voltages up to nominal, but will not correct high
input voltages. Since operation in the all-boost mode
will increase the voltage and heating in the WHR
regulator, the rated load current, and in some cases the
maximum rated nominal input voltage, must be
reduced. Refer to the “All Buck and All Boost Rating
Chart” for the all-boost ratings. For all-boost operation
the input line to each POWERSTAT variable
transformer must be moved from terminal 2 to terminal
5.
6.3.2.
4.4.2 All-Buck Operation
When connected for all-buck operation, the units will
bring extra high input voltages down to nominal, but will
not correct low input voltages. Since all-buck operation
reduces the voltage in the regulator, the nominal input
voltage can be increased. The current ratings remain
the same. Refer to the “All Buck and All Boost Rating
Chart” for all-buck ratings. All-buck operation requires
moving the input line to each POWERSTAT Variable
Transformer from terminal 2 to terminal 4.
All Buck and All Boost Rating Chart
Standard Rating
All Buck Operation
All Boost Operation
(max output voltage = input voltage)
(min output voltage = input voltage)
Maximum Nominal
Input Voltage
§
Minimum
Output
Voltage
(% of
Input)
† High
Input
Voltage
Range
(% of
Output)
Maximum Nominal
Input Voltage
§
Maximu
m Output
Voltage
(% of
Input)
‡ Low
Input
Voltage
Range
(% of
Output)
Current
De-rating
(% of
rated)
Voltage
Range
50 Hz
60 Hz
50 Hz
60 Hz
208 X 240
Narrow
240
270
80%
125%
173
208
125%
75%
77%
Wide
260
300
67%
150%
173
208
150%
65%
72%
§ Selectable output voltage is a function of the control module and must remain within the limits specified in the unit rating charts.
† In all buck operation the input voltage range is from the selected output voltage to the 'high input voltage range'.
‡ In all boost operation the input voltage range is from the 'low input voltage range' to the selected output voltage.
Summary of Contents for STABILINE WHR32 Series
Page 2: ...2...
Page 16: ...16 11 0 SCHEMATIC For reference only use full size supplied with unit...
Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...
Page 19: ...19 Enclosures A through G continues Note All dimensions are inches millimeters...
Page 20: ...20 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...
Page 21: ...21 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...
Page 22: ...22 Enclosures DD through GG Note All dimensions are inches millimeters...
Page 23: ...23 Enclosures DD through GG continues Note All dimensions are inches millimeters...
Page 24: ...24 Enclosures EEE through GGG Note All dimensions are inches millimeters...
Page 25: ...25 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...