AAA Series Gas Boiler – Installation and Service Manual
6
Installation Instructions
Section 2
2.1
RECEIVING
INSPECT SHIPMENT FOR POSSIBLE DAMAGE.
All goods are carefully manufactured, inspected,
checked and packed by experienced workers. The manufacturer's responsibility ceases upon delivery of
goods to the carrier in good condition. Any claims for damage, shortage in shipment or non-delivery must
be filed immediately against the carrier by the consignee.
Use care when receiving and unpacking the boiler. Dropping the boiler may cause damage and prevent
safe and proper operation.
2.2
INSTALLATION CODES AND REQUIREMENTS
All applicable national, provincial/state, and local codes, laws, regulations, and ordinances must be
followed. They expand on and take precedence over any recommendations in this booklet. Authorities
having jurisdiction shall be consulted before installations are made.
In
Canada
, the installation must conform to the requirements of the authority having jurisdiction or, in the
absence of such requirements, to the
CAN/CSA B149 Installation Codes
(current edition). All electrical
wiring must be in accordance with the
Canadian Electrical Code, CSA C22.1 Part 1
(current edition) and
applicable local codes.
In the
United States of America
, the installation must conform to the requirements of the authority having
jurisdiction or, in the absence of such requirements, to the
National Fuel Gas Code, ANSI Z223.1
(current
edition). All electrical wiring must be in accordance with the
National Electrical Code, ANSI/NFPA 70
(current edition) and applicable local codes.
Where required by the authority having jurisdiction, follow the
Standard for Controls and Safety Devices
for Automatically Fired Boilers, ANSI/ASME CSD-1
(current edition).
2.3
LOCATION
AAA boilers are intended for indoor installation only. Observe the following minimum clearances from the
boiler to combustible materials:
Clearances to Combustible Materials
Sides
Rear
Top
Front (service)
Model
in
mm
in
mm
in
mm
in
mm
AAA
6
153
6
153
36
915
40
1016
•
Maintain a clearance of 6" (153 mm) from draft hood and the flue pipe in any direction.
•
Allow ample space for boiler inlet and outlet connections, and gas connection.
•
Boiler must be installed on a stable and level foundation.
•
AAA Series boilers must be installed on a Non-Combustible floor.
•
A hot water boiler installed above radiation level must be provided with a low water cutoff
device at the time of boiler installation.
•
This boiler must be installed such that gas ignition system components are protected from water
(dripping, spraying, rain, etc.) during appliance operation and service.
Summary of Contents for AAA-3000 series
Page 28: ...AAA Series Gas Boiler Installation and Service Manual 28 ...
Page 29: ...AAA Series Gas Boiler Installation and Service Manual 29 Wiring Diagrams Section 7 ...
Page 30: ...AAA Series Gas Boiler Installation and Service Manual 30 ...
Page 31: ...AAA Series Gas Boiler Installation and Service Manual 31 ...
Page 34: ...AAA Series Gas Boiler Installation and Service Manual 34 NOTES Section 9 ...
Page 35: ...AAA Series Gas Boiler Installation and Service Manual 35 NOTES Section 9 ...