AAA Series Gas Boiler – Installation and Service Manual
15
BTC Series Display Items in Installer Mode
VIEW MENU
Item Field
in Mode
Description
OUTDR
4,5
Outdoor air temperature measured by outdoor sensor
BOIL
TARGET
1,2,3,4,5
Target boiler supply temperature the control is trying to maintain at the boiler
supply sensor or the boiler outlet sensor
BOIL SUP
2,5
Current boiler supply water temperature as measured by the boiler supply
sensor.
BOIL OUT
1,3,4,6
Current boiler outlet water temperature as measured by the boiler supply
sensor
BOIL IN
All
Current boiler inlet water temperature as measured by the boiler inlet sensor.
BOIL
∆
T
All
Current T (temperature difference) between the boiler outlet sensor and the
boiler inlet sensor
TANK
3
Current DHW tank temperature as measured by the DHW sensor
BOIL ON
All
The total number of running hours of the boiler since this item was last cleared
ADJUST MENU
Item Field
Default
Description
MODE
1
Sets the operating mode for the control. Mode 1 (parallel, setpoint); Mode 2
(primary/secondary, setpoint); Mode 3 (parallel, dedicated DHW generation
only); Mode 4 (parallel, outdoor reset with optional DHW override); Mode 5
(primary/secondary, outdoor reset with optional DHW override)
BOIL
TARGET
180
°
F
Minimum boiler target temperature during reset override, setpoint or DHW
operation.
TANK
TARGET
140
°
F
Sets the DHW storage tank’s temperature. Used in Mode 3 only.
TANK
DIFF
5
°
F
Sets the differential for the DHW storage tank.
OUTDR
START
70
°
F
The outdoor starting temperature used in the reset ratio for the heating system.
OUTDR
DSGN
25
°
F
The design outdoor air temperature used in the heat loss calculations for the
heating system.
BOIL
START
70
°
F
The starting water temperature used in the reset ratio calculation for the
heating system.
BOIL
DSGN
180
°
F
The design water temperature used in the heat loss calculations for the heating
system.
BOIL MAX
210
°
F
The maximum boiler target water temperature.
BOIL
MASS
2
The thermal mass of the boiler used. Always use 2 for the Super Hot AAA
Boiler.
DIFF
20
°
F
The differential that the control is to use when it is operating the boiler.
DLY
0:30 min
Determines when to stop purging the pump.
WWSD
70
°
F
The system’s warm weather shut down.
°
F /
°
C
°
F
The units of measure that all of the temperatures are to be displayed in by the
control.
Summary of Contents for AAA-3000 series
Page 28: ...AAA Series Gas Boiler Installation and Service Manual 28 ...
Page 29: ...AAA Series Gas Boiler Installation and Service Manual 29 Wiring Diagrams Section 7 ...
Page 30: ...AAA Series Gas Boiler Installation and Service Manual 30 ...
Page 31: ...AAA Series Gas Boiler Installation and Service Manual 31 ...
Page 34: ...AAA Series Gas Boiler Installation and Service Manual 34 NOTES Section 9 ...
Page 35: ...AAA Series Gas Boiler Installation and Service Manual 35 NOTES Section 9 ...