3  Installation

3.1  Orientation

Ideally, the front of the solar modules should face 
due south.

The tilt angle can be calculated as follows:
The ideal tilt angle corresponds to the latitude of the 
installation site minus 20°

To achieve a good self-cleaning effect through pre-
cipitation the tilt angle of the solar modules should 
be at least 20°.

≥ 20°

Avoid any shading and heat build-up at the rear of 
the module. Both can lead to significant losses in 
yield!

3.2  Maximum series/parallel configuration

 

CAUTION

Only solar modules of the same type and output class 
may be connected in series! The maximum system 
voltage of the modules must never be exceeded!

To achieve the required system currents the modules 
may be connected in parallel. Only modules of the 
same type and voltage may be used. Ensure that the 
specified permitted load capacity with regard to the 
return current IR is not exceeded!

4  Installation

4.1  General 

 

CAUTION

Mount the modules only on suitable support struc-
tures. These structures must ensure that no mechani-
cal stresses are transferred from the building (e.g. 
the roof structure) to the module.

The minimum distance between modules is 5 mm to 
allow for material expansion.

The modules must be installed such that water flow 
(particularly along the cable) towards the cable 
gland at the junction box is prevented.

The connection cables between the modules and 
towards the inverter must be installed such that the 
closed connectors are not permanently in water. This 
means, for example, that rainwater must be able to 
drain from U-shaped profiles.

Use only the holes provided in the frame! Do not 
drill, nail or weld the module frames.

The mounting systems recommended and approved 
by Sunways can be found on our website at  
http://www.sunways.de.

4.2  Standard mounting

Each module must be secured at a minimum of 
four points (drill holes in the long sides - see dia-
gram in section 2, Your Solar Modules). The frame 
is structurally approved for mounting on the long 
sides. Mounting on the short module sides must be 
avoided. The maximum tolerance is 100 mm.

100
100

100
100

1000

Insertion systems (U-shaped profile over the whole 
long/short side) are permitted under the following 
load conditions:

Short side mounting
Mounting rails only at the short edges without cen-
tral support for loads up to 2400 Pa

Mounting rails at the short edges with central sup-
port for loads up to 5400 Pa

Long side mounting
Mounting rails covering the whole length of the long 
edges for loads up to 5400 Pa

 

2400 Pa

5400 Pa

5400 Pa

Only use corrosion-resistant screws. Use a torque 
wrench and tighten the screws with 20 Nm.

4.3  Installation instructions for laminates (frame-

less modules)

Avoid pointwise support and mounting of the lami-
nates, except with mounting brackets approved by 
Sunways. These brackets are designed for loads up to 
2400 Pa.
Further details and recommendations can be found 
on our website at http://www.sunways.de.

Otherwise the laminates must be linearly supported 
and fixed at both long module sides as a minimum.

All support rails must be aligned such that twisting 
or warping of the laminates is avoided.

Only use mechanical fixtures for mounting the mod-
ules. Do not use adhesives or adhesive tapes for fas-
tening the laminates, unless they have been explicitly 
approved by Sunways.

Please ensure that the laminate edges are not per-
manently in water and are allowed to dry.

Please note that the glass edges of the modules are 
particularly sensitive to impact.

Follow the installation instructions for the respective 
mounting system.

4.4  Other data

Bundling or concentration of solar radiation, for 
example using lenses or mirrors, is prohibited!

Avoid covering the drainage holes in the module 
frames.

For any maintenance and repair work produce a plan 
documenting the module installation layout, includ-
ing serial number allocation and cable layout.

Summary of Contents for SM 230M

Page 1: ... the full open circuit voltage can be expected in the modules During all installation and wiring work the modules must therefore be covered or disconnected from the consumer load Otherwise there is a risk of arc formation on lines carrying direct current Suitable fall protection must be used when working on roof mounted solar generators The standard solar module is a glass film product and must no...

Page 2: ...r points drill holes in the long sides see dia gram in section 2 Your Solar Modules The frame is structurally approved for mounting on the long sides Mounting on the short module sides must be avoided The maximum tolerance is 100 mm 100 100 100 100 1000 Insertion systems U shaped profile over the whole long short side are permitted under the following load conditions Short side mounting Mounting r...

Page 3: ...sure that only connectors of the same polarity can be connected to each other Connecting socket and plug The system is only correctly locked if the locking hooks are recessed flush in the mating piece CAUTION The plug connectors must not be disconnected or connected under load current They may be con nected and disconnected while voltage is present Release the locking mechanism by pressing on the ...

Page 4: ...ny declares under its sole responsibility that the solar module types listed above meet the requirements of the following standards DIN EN 50178 EN 50081 1 2 EN 50082 1 2 DIN VDE 0101 DIN VDE 0110 and therefore comply with the EC Directives listed above Roland Burkhardt CTO Sunways AG Photovoltaic Technology Macairestraße 3 5 78467 Konstanz Germany Phone 49 0 7531 996 77 0 Fax 49 0 7531 996 77 444...

Reviews: