PV moduleinstallationmanual

ALTERNATIVE ENERGY(AE) SOLAR Co., Ltd.

Address: No.26, Jingyi Road, Hongze Economic Development

Zone, Huai’an City, Jiangsu Province, P.R. China

Email

[email protected]

Summary of Contents for AE315HM6L-60

Page 1: ...1 PVmoduleinstallationmanual ALTERNATIVE ENERGY AE SOLAR Co Ltd Address No 26 Jingyi Road Hongze Economic Development Zone Huai an City Jiangsu Province P R China Email info ae solar com ...

Page 2: ... CONTENTS 1 Purpose of this manual 3 2 Disclaimer 3 3 General Detailed Rules 3 4 Mechanical installation 5 5 Electrical installation 8 6 Bypass diodes and current protection 10 7 Maintenance 10 8 Note 11 ...

Page 3: ...AE SOLAR reserves the rights to change the manual the Modules the specifications or any other information of the modules without prior notice 3 General Detailed Rules 3 1 Warning Before installing wiring operating or maintaining modules you should read and understand all safety precautions Direct current DC is generated when the battery surface of the module is exposed to direct sunlight or other ...

Page 4: ...n to protect the connector from moisture or the module from sun exposure such as using the connector cover Please protect the packing from damage Follow the recommended unpacking steps to open the module wrapper Opening package transportation and storage procedures should be handled with care The unpacking process must be operated by two people at the same time and modules need to be carried by bo...

Page 5: ...rements Ensure the module installation means and support system sufficiently robust so that the Modules can undertake the preset loading conditions the support installer or supplier shall provide necessary guarantee and other related certifications The installation support system shall pass the inspection and test by the third party test institution with the static mechanic analysis capability and...

Page 6: ...n and module installation structure is capable of withstanding the expected local wind Modules can be mounted in landscape or portrait orientation 4 4 Mounting with bolts Use the corrosion resistant M8 bolt a flat washer and a spring washer for fixing with the installation support through the installation hole in the frame of the module and tighten to a torque of 14 20 N m The frame of each module...

Page 7: ...ps shall contact or make any shading on the modules glass An integrated M8 hex head cap screw tightens down to the frame with a torque between 12 5 18 NM Method Installed Frame L Clamp Position S Design load Mounting with clamps Long Frame 0 S 1 4L 3600Pa Front 1600Pa Back 1 4L 50mm S 1 4L 50mm 1600Pa Front 1600Pa Back Short Frame 0 S 1 4W ...

Page 8: ... to experience conditions that produce more current and or voltage than reported at standard test conditions Accordingly the values of ISC and VOC marked on the Module should be multiplied by a factor of 1 25 when to determining component voltage ratings current ratings fuse sizes and size of controls connected to the PV output Completely cover the Modules with an opaque material to prevent electr...

Page 9: ...e frame It is forbidden to drill any additional grounding hole on the module frame otherwise the warranty will be invalid The grounding of the module shall be performed by qualified electricians The module frame shall be connected to each other with appropriate grounding wires 4 14mm2 copper wire is recommended as the grounding wire Is recommended to be used as the grounding mark All conductive co...

Page 10: ...e module If electrical or mechanical properties are required for inspection or maintenance qualified professionals should be advised to avoid any electric shock or loss of life Inspect for loose or corroded electrical interfaces loose connections between supports and components connections between cables connectors and grounding Replacement modules must be of same type Do NOT touch live parts of c...

Page 11: ...t this is deemed necessary avoid the use of any sharp projects that might damage the penetrating the substrate material 8 Note The output power value described in the manual is the value of the module tested under standard conditions Daily operation environment and standard test conditions are often different ...

Page 12: ...Max Power Pmax Wp 315 320 325 330 335 340 345 Maximum Power Voltage Vmp V 33 26 33 61 33 89 34 17 34 44 34 69 34 95 Maximum Power Current Imp A 9 47 9 52 9 59 9 66 9 73 9 80 9 87 Open Circuit Voltage Voc V 40 7 40 9 41 1 41 3 41 5 41 7 41 9 Short Circuit Current Isc A 10 04 10 15 10 2 10 31 10 36 10 55 10 64 AE425HM6L 72 AE430HM6L 72 AE435HM6L 72 AE440HM6L 72 AE445HM6L 72 AE450HM6L 72 AE455HM6L 72...