background image

 

 

3.2.      Charging 

 

3.2.1.  Full charge 

The full charge is a prolonged charge at an elevated voltage, performed under the supervision of the user. It 
lasts until certain full charge criteria are fulfilled but not outside certain minimum and maximum duration limits. 
It is used mainly 

    

as Commissioning charge after installation in paragraph 2.7 

    

as Corrective Equalizing charge in paragraph 3.2.2.2 

    

as preparation charge before a capacity test in paragraph 6 

    

as refresh charge during long storage period (in paragraphs 1.2, 7) 

 

During charge, the battery temperature shall be continuously monitored. It should never exceed 45

o

C, otherwise 

the charge shall be interrupted for sufficient time to cool down the battery. 

 

Case 1) With external charger of IU - characteristic.

 

For the commissioning charge the current shall be limited to 0.1*C10 Amps. 

 

Battery 
temperature 

Voltage settings 

Minimum and maximum 
charging times 

Full charge criteria. 

15-30

o

2.35 – 2.40 V 

36h – 72h 

when the individual cell voltages have not 

risen for a period of 4 hours. 

30-40

o

2.32 – 2.35 V 

24h - 48h 

0-10

o

2.38 – 2.45 V 

48h - 72h 

 

Case 2) With external charger of IUI or I - characteristic.

 

Using  an  IUI  or  I  charger  that  can  charge  the  battery  with  constant  current  at  a n   elevated  voltage,  higher  than 

2.60 Vpc up to 2.80 Vpc. 

 

Bulk 

charge 

current 
limitation 

Voltage  settings 
for U phase 

gassing 

charge 

current limitation 

Minimum  and  maximum 
charging 

times 

at 

gassing phase 

Full charge criteria 

0.2*C10 

2.33 – 2.40 V 

0.012*C10 
(1.2 A  per 

100Ah 

nominal capacity) 

5h – 8h 

when  the  individual  cell 
voltages  have  not  risen 
for a period of 1 hour. 

 

Case 3) Using the solar controller.

 

Connect the battery to the controller and leave it  for 1-2 weeks while the application load is disconnected. Full 
charge criteria are not applicable here. Use the following voltage settings: 

 

On-off controllers 

-20 to 0°C 

0 to 35°C 

>35°C 

High disconnect voltage (Vr) 

2,55V 

2,45V 

2,40V 

Low restart voltage (Vrr) 

2,35V 

2,30V 

2,25V 

 

Constant Voltage controllers 

-20 to 0°C 

0 to 35°C 

>35°C 

Regulation voltage (Vr) 

2,45V 

2,37V 

2,33V 

 
 

3.2.2.  Equalizing 

3.2.2.1.    Functional Equalizing

 

During  a  cycling  operation,  the  target  is  to  achieve  an  almost  complete  recharge  (100%  SOC)  after  every 
discharge  cycle  otherwise  a  permanent  capacity  decrease  will  threaten  the  battery’s  state  of  health.  This  is  not 
always possible in Stand-alone applications where the RES source depends on the weather conditions and the load 
is possible to exceed the expected level. Here, a proper “Array to Load ratio” as given in paragraph 3.1, is critical 
for  the  life  expectancy  of  the  battery.  For  Hybrid  systems  with  diesel  generator  (e.g.  mainly  telecom  hybrid 
systems),  the  charging  source  is  always  available  but  the  boost  charging  time  is  restricted  to  achieve  a  more 
efficient utilization of the diesel. In both cases, a scheduled (functional) equalizing charge shall be given at regular 
intervals (see next) to protect the battery from sulphation and lagging cells. 

 

Equalizing frequency is adjusted according to the charge deficit. The less complete the daily recharge is, the 
more frequent the equalizing is required. 

    

The charging duration is fixed. 

    

The voltage settings are the same values used for a normal recharge. 

 

3.2.2.2.    Corrective Equalizing

 

Equalizing  charges  are  also  required  after  incidents  of  excessive  stress  for  the  battery  (deep  discharges  with 

inadequate charges) or when the individual cell voltages show excessive deviation from the average (lagging cells 

Summary of Contents for RES SOPzV Series

Page 1: ...ply with the OPERATING INSTRUCTIONS repairs carried out with non approved spare parts or unauthorized interference with the battery will invalidate any claim for warranty SYSTEMS SUNLIGHT S A Headquarters 2 Ermou Nikis Str Syntagma Square 105 63 Athens Attica Greece T 30 210 6245400 F 30 210 6245409 Manufacturing Plant Neo Olvio 672 00 Xanthi Greece T 30 25410 48100 F 30 25410 95446 Service Depart...

Page 2: ...tically up and equally on each of the poles Never drag or roll the battery since damage will be caused Do not apply force to the safety valve during handling The batteries are fully charged before shipment Do not short circuit Check for evidence of leakage All cells with visible defects such as cracked jars loose terminal posts or other unrecoverable problems shall be rejected 2 Installation and c...

Page 3: ... correct torque loading of 22 Nm Electrical connections to the battery and between cells on separate levels or racks should be made to minimize mechanical strain on battery terminal posts For systems where the total battery voltage is measured at the controller use oversized cables to the battery in order to minimize the voltage drop Check the battery s total voltage It should match the number of ...

Page 4: ...erature stays within the allowable limits The maximum allowable discharge per cycle Max Daily DoD MDDOD is 20 for Stand alone and 60 for Hybrid systems For discharge currents lower than 0 1 C10 the MDDOD is expressed in of the C10 value For example the cell RES 6 SOPzV 850 has C10 687Ah therefore a 60 MDDoD means 413 Ah extractable per day The maximum allowable DoD MDOD is 80 of the maximum availa...

Page 5: ...r Connect the battery to the controller and leave it for 1 2 weeks while the application load is disconnected Full charge criteria are not applicable here Use the following voltage settings On off controllers 20 to 0 C 0 to 35 C 35 C High disconnect voltage Vr 2 55V 2 45V 2 40V Low restart voltage Vrr 2 35V 2 30V 2 25V Constant Voltage controllers 20 to 0 C 0 to 35 C 35 C Regulation voltage Vr 2 4...

Page 6: ...over one month Controller type Setting 20 to 0 C 0 to 15 C 15 to 35 C 35 C Constant Voltage one step Vr 2 50V 2 45V 2 40V 2 35V Constant Voltage two steps absorption maximum 2 h per day 2 55V 2 50V 2 45V 2 40V float 2 45V 2 40V 2 35V 2 30V On off High voltage Vr 2 55V 2 50V 2 45V 2 40V Low voltage Vrr 2 35V 2 30V 2 30V 2 25V For systems with oversized PV array and low MDDOD 5 use lower settings se...

Page 7: ... the minimum system voltage In Stand alone systems it is recommended to use controllers with adjustable LVD setting to the battery temperature higher LVD for lower temperature During operation the temperature difference between individual battery cells should be below 3o K 3 5 Current limits The maximum charging current during the bulk charging is 0 2 x C10 while the battery voltage is below the g...

Page 8: ...m To avoid damage periodical equalizing charging see 3 2 1 or permanent float charging has to be made 8 Transport RES SOPzV cells are protected against short circuit If properly packed batteries are no dangerous goods according to the international regulations for dangerous goods on road and on rail ADR and RID Battery Voltage in relation to DoD as a guidance for the initial LVD settings first try...

Reviews: