background image

 

 

 

2.3.      Cells in parallel strings

 

Valve-regulated  cells  may  be  connected  in  parallel  to  give  higher  current  capability.  In  the  case  of  parallel 
connected strings, use batteries of the same capacity, design and age only with a maximum of 4 parallel strings. 

If more than 4 strings are required, consult SYSTEMS SUNLIGHT S.A. The resistance of the cables in each string 
must  be  the  same,  e.g.  same  cross-section,  same  length.  In  addition,  each  string  should  be  equipped  with 
disconnect capabilities for maintenance and safety purposes. 

 

2.4.      Preliminary control

 

Check  for  evidence of  leakage. All  cells  with  visible  defects  such  as  cracked  jars,  loose  terminal  posts,  or  other 
unrecoverable problems shall be rejected. 
In case the surface of battery container is dirty before installation wash with soapy water only. 

 

Carry  out  OCV  (open  circuit  voltage)  measurements  on  each  individual  cell  battery  to  check  their  compliance 
against the variation and absolute voltage criteria: 

           

The  cells’  OCV  must  not  deviate  from  average  more  than  ± 0.025 V.  

           

The cells’  OCV must not be lower than 2.07 V.  

Should not compliance noticed, consult SYSTEMS SUNLIGHT S.A.. 

Note: OCV of a fully charge cell is ~2,13 V. Per 10% Depth of Discharge (DOD) the voltage is reduced by ~0,025 

V, for example, OCV of 2,08 V corresponds to 20% discharged cell. 

 

2.5.      Electrical connections

 

Ensure  that  the  cells  are  installed  in  the  correct  polarity.  Check  that  all  contact  surfaces  are  clean.  If  required, 

clean  with  a  brass  brush/pad.  You  may  lubricate  slightly  the  inserts  and  connections  with  silicone  grease. 
Petroleum-based lubricant is not recommended. 

 

Tighten the terminal screws, using the correct torque loading of 22 Nm. 

 

Electrical  connections to  the  battery  and  between cells  on  separate levels  or  racks  should  be  made  to  minimize 
mechanical strain on battery terminal posts. 

 

For systems where the total battery voltage is measured at the controller, use oversized cables to the battery in 
order to minimize the voltage drop. 

 

Check the battery's total voltage. It should match the number of cells connected in series. If the measurement is 
not as expected, recheck the connections for proper polarity. 

 

Batteries with a nominal voltage > 75 V require an EC conformity declaration in acc. with the low voltage directive 
(73/23/EEC), which confirms that the CE marking is applied to the battery. The company installing the battery is 
responsible for the declaration and applying the CE marking. 

 

For future identification, apply individual cell/unit numbers in sequence starting from one end of the battery. Also 
apply identification numbers for the parallel strings. 

 

Connect the battery to the DC power supply, with the charger switched off,  battery fuses removed and the load 
disconnected, ensuring that the polarity is correct. 
 

2.6.      Instrumentation

 

For large installations consider the instrumentation for measurements and alarm. These  include  Voltmeter, 

Ammeter, Ah  counter,  High-  and  low-voltage indicators, Ground  fault  detector(s) and 
Temperature sensor(s) for the battery and the ambient air. For smaller installations use portable test equipment. 

 

The temperature sensors shall be fixed on the cell units (side wall or negative pole). 

 

The use of monitoring and recording systems is mandatory in “Hybrid” systems. 

 

2.7.      Commissioning charge

 

The initial charge is very important for the future battery operation and the battery’s service life. It is performed 
as a full charge in paragraph 3.2.1. Keep the records in the battery’s logbook. 

 

 

 
 

Summary of Contents for RES SOPzV Series

Page 1: ...ply with the OPERATING INSTRUCTIONS repairs carried out with non approved spare parts or unauthorized interference with the battery will invalidate any claim for warranty SYSTEMS SUNLIGHT S A Headquarters 2 Ermou Nikis Str Syntagma Square 105 63 Athens Attica Greece T 30 210 6245400 F 30 210 6245409 Manufacturing Plant Neo Olvio 672 00 Xanthi Greece T 30 25410 48100 F 30 25410 95446 Service Depart...

Page 2: ...tically up and equally on each of the poles Never drag or roll the battery since damage will be caused Do not apply force to the safety valve during handling The batteries are fully charged before shipment Do not short circuit Check for evidence of leakage All cells with visible defects such as cracked jars loose terminal posts or other unrecoverable problems shall be rejected 2 Installation and c...

Page 3: ... correct torque loading of 22 Nm Electrical connections to the battery and between cells on separate levels or racks should be made to minimize mechanical strain on battery terminal posts For systems where the total battery voltage is measured at the controller use oversized cables to the battery in order to minimize the voltage drop Check the battery s total voltage It should match the number of ...

Page 4: ...erature stays within the allowable limits The maximum allowable discharge per cycle Max Daily DoD MDDOD is 20 for Stand alone and 60 for Hybrid systems For discharge currents lower than 0 1 C10 the MDDOD is expressed in of the C10 value For example the cell RES 6 SOPzV 850 has C10 687Ah therefore a 60 MDDoD means 413 Ah extractable per day The maximum allowable DoD MDOD is 80 of the maximum availa...

Page 5: ...r Connect the battery to the controller and leave it for 1 2 weeks while the application load is disconnected Full charge criteria are not applicable here Use the following voltage settings On off controllers 20 to 0 C 0 to 35 C 35 C High disconnect voltage Vr 2 55V 2 45V 2 40V Low restart voltage Vrr 2 35V 2 30V 2 25V Constant Voltage controllers 20 to 0 C 0 to 35 C 35 C Regulation voltage Vr 2 4...

Page 6: ...over one month Controller type Setting 20 to 0 C 0 to 15 C 15 to 35 C 35 C Constant Voltage one step Vr 2 50V 2 45V 2 40V 2 35V Constant Voltage two steps absorption maximum 2 h per day 2 55V 2 50V 2 45V 2 40V float 2 45V 2 40V 2 35V 2 30V On off High voltage Vr 2 55V 2 50V 2 45V 2 40V Low voltage Vrr 2 35V 2 30V 2 30V 2 25V For systems with oversized PV array and low MDDOD 5 use lower settings se...

Page 7: ... the minimum system voltage In Stand alone systems it is recommended to use controllers with adjustable LVD setting to the battery temperature higher LVD for lower temperature During operation the temperature difference between individual battery cells should be below 3o K 3 5 Current limits The maximum charging current during the bulk charging is 0 2 x C10 while the battery voltage is below the g...

Page 8: ...m To avoid damage periodical equalizing charging see 3 2 1 or permanent float charging has to be made 8 Transport RES SOPzV cells are protected against short circuit If properly packed batteries are no dangerous goods according to the international regulations for dangerous goods on road and on rail ADR and RID Battery Voltage in relation to DoD as a guidance for the initial LVD settings first try...

Reviews: