17
figure 2-7
Wiring diagram for other regions *
* Ensure that only the PE cable at the backup port of the master inverter is grounded in re-
gions beyond Australia and New Zealand.
If there is more than one inverter in the system, the backup terminal of inverters
cannot be connected to loads, nor can they be connected in parallel. If there is only
one inverter in the system, the load should be connected to the backup terminal.
For the wiring of other terminals, please refer to the wiring of the master inverter in
the off-grid parallel system above.
•
In MicroGrid mode, the grid-connected port can only be connected to the gen-
set, not to the grid.
•
In MicroGrid mode, the smart switch is necessary.
•
If the number of connected inverters is different from the number set on the
master inverter, the system may fail to start.
The master inverter is connected to the smart switch and the meter through RS485 commu-
nication for the system to control the smart switch. For details about cable connections. Re-
fer to
The following settings are required for the off-grid parallel connection of inverters: