When the PV inputs are changed, the corresponding “fault” state
will be shown on the main screen. You can perform the PVS
Detect Reset function to re-detect the PV input strings number.
PVS Detect is only valid in the machine that is equipped with this
feature.
10.13.2 Fre Derating
Main Screen(Press
ENTER
)
→
Menu screen(Press
×
4)
→
Advanced
settings(Press
ENTER
)
→
Enter password(Press
ENTER
)
→
Advanced
settings(Press
ENTER
, Press
)
→
Fre Derating
If the country code set as Other or AT, a Derating
page as shown in the right will appear. Press
to
select. Confirm the selection by Pressing ENTER.
If the country code set as RO, a Derating page as shown below will appear.
Press
to select. Confirm the selection by Pressing
ENTER
.
The following graph shows the automatic reduction in output power when the
frequency exceeds the threshold value.
10.13.3 P-Control
Main Screen(Press
ENTER
)
→
Menu screen(Press
×
4)
→
Advanced
settings(Press
ENTER
)
→
Enter password(Press
ENTER
)
→
Advanced
settings(Press
ENTER
, Press
×
2)
→
P-Control
P-Control can control the active power raise and decline rate. And when Flt
slowup is ON, you can also set the power rise rate when a fault is removed.
If the country code set as RO, AT, CHN or Other,
a P-Control page as shown in the right will
appear. Press
to select. Confirm the selection
by Pressing
ENTER
.