3.3
Internal Design of the MV Station
3.3.1 Internal Components
Figure below shows the bottom view of the major electrical components inside the MV
Station:
No.
Device
Description
A
Inverter
Convert the DC current generated from the PV array into AC
current.
B
MV
transformer
Convert low-voltage AC current output from the inverter into grid-
compatible medium-voltage current.
C
Intelligent
PMD
—
3.3.2 Cable Entry Design
For easier onsite cable connection, all cables between the internal devices have been
connected before delivery.
All cables between the MV Station and the external are routed through the bottom of the MV
Station. All cables coming into or out of the MV Station should be protected properly, for
example, use cable pipe to prevent damage by rodents. After cable connection, all cable
entries should be sealed by fireproof mud or other appropriate materials.
The MV Station bottom cable entries are shown below.
Function of each opening is shown below:
System Manual