To ensure IP66 protection, use only the connector within the scope of
delivery or the connector with the same ingress of protection.
5.6.2 Connection Procedure
High voltage may be present in the inverter!
Ensure all cables are voltage-free before performing electrical operations.
Do not connect the AC circuit breaker before finishing electrical
connection.
Use the MC4 DC terminal within the scope of delivery. Damage to the device
due to the use of incompatible terminal shall not be covered by the warranty.
Step 1
Strip insulation layers of all DC cables by
about 7mm.
7mm
Step 2
Assemble the cable ends with the crimping
pliers.
Positive Crimp Contact
Negative Crimp Contact
Step 3
Lead the cable through cable gland, and insert into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm
connection. Tighten the cable gland and the insulator (torque 2.5 N
m
to 3 N
m).
Crimp Contact
Positive Insulator
Cable Gland
Crimp Contact
Negative Insulator
Cable Gland