40
figure 5-3
Sealing Plate for One Wire per Phase with Multi-core Cable
table 5-2 AC Cable Requirements(One Wire per Phase with Multi-core Cable)
No.
Type
Specification
Cable Diameter(mm)
Cross-sectional Area
(mm
2
)
1
Outdoor four-core cop-
per wire cable
40 ~ 75
L1, L2, L3 wire: 70 ~ 185
PE wire: refer to
2
Outdoor three-core cop-
per wire cable
Outdoor PE cable
L1, L2, L3 wire: 40 ~ 75
PE wire: 15 ~ 32
3
Outdoor four-core alumi-
num wire cable
(1)
40 ~ 75
L1, L2, L3 wire: 70 ~ 400
PE wire: refer to
4
Outdoor three-core alu-
minum wire cable
(1)
Outdoor PE cable
L1, L2, L3 wire: 40 ~ 75
PE wire: 15 ~ 32
(1) A copper to aluminum adapter terminal is required when an aluminum cable is used. For
details, refer to
User Manual