figure 5-4
Sealing Plate for Two Wires per Phase with Multi-core Cable
table 5-3 AC Cable Requirements(Two Wires per Phase with Multi-core Cable)
No.
Type
Specification
Cable Diameter(mm)
Cross-sectional Area
(mm
2
)
1
Outdoor three-core cop-
per wire cable
Outdoor PE cable
L1, L2, L3 wire: 47 ~ 59
PE wire: 10 ~ 30
L1, L2, L3 wire: 120 ~
185
PE wire: refer to
2
Outdoor three-core alu-
minum wire cable
(1)
Outdoor PE cable
L1, L2, L3 wire: 47 ~ 59
PE wire: 10 ~ 30
L1, L2, L3 wire: 120 ~
185
PE wire: refer to
(1) A copper to aluminum adapter terminal is required when an aluminum cable is used. For
details, refer to
table 5-4 PE Wire Requirements
PE Wire Cross Section
Note
S/2
(S: Phase wire cross-section S)
The specifications are valid only when the phase wire
and PE wire use the same material. If otherwise, en-
sure that the cross section of the PE wire produces a
conductance equivalent to that of the wire specified in
the table.